March 17, 2017 <br />Ned Nelson, Architect <br />e-mail: nednelson@msn.com <br />Permit Scope: ADDITION TO EXISTING BLDG <br />Owner / Tenant: TYTUS WILLIAM B & SUSAN B / POCOCK RACING SHELLS <br />Job Address: 615 80TH ST SW <br />Permit Number: B1612-035 <br />RE: CORRECTIONS FOR BUILDING PLAN REVIEW <br />Dear Ned, <br />The plans submitted for permit have been examined and you are advised that revisions may be <br />necessary before a permit can be issued. Please review and respond to the comments below. <br />Plan review will resume when the requested information is submitted. All required submittals <br />must be of sufficient detail and information to ensure that the proposed structures will be <br />constructed in compliance with all adopted codes, with two sets of drawings submitted for <br />revisions. <br />Additional revisions or additions may be required by other departments (such as Public Works, <br />Utilities, Planning, or Fire). <br />All revisions require the person delivering the drawings to replace revisions into the two review <br />sets here at our offices. For significant revisions, please provide two full replacement sets. If <br />the revisions are coming directly from the blue -printer, please make arrangements with them to <br />print two replacement sets. <br />General <br />1. The method of compliance with the IEBC should be identified in the code analysis, to <br />include whether it is prescriptive, work area, or performance compliance. For the <br />purpose of this plan review, I will assume work area method for the addition. <br />Occupancy <br />1. Please confirm if boat fabrication is occurring, which should be identified as F-1, per IBC <br />section 306.2 as amended by the State of Washington. <br />2. The original permit B0302-006 included a B occupancy. Please clarify if the B occupancy <br />is limited to the mezzanine, or whether it is also an occupancy or use in the addition. <br />,/3. Please summarize total occupant load count (by occupancy and floor area) in the <br />addition, per IBC table 1004.1.2. <br />4. Please show the following on the drawings: <br />a. A discernible path of egress should be shown with illuminated exit signs on the <br />drawings, per IBC section 1011.1, to include the existing building and mezzanine. <br />b. Emergency lighting should be shown on the drawings, per IBC section 1006.1. <br />L,'' 5. The drawings should indicate specific signage at the main entrance door and the exit <br />doors to indicate that these doors will be open during business hours, per IBC section <br />1010.1.9.3, item 2.2. <br />CITY OF EVERETT PERMIT SERVICES 3200 CEDAR ST, EVERETT, WA 98201 425-257-8810 <br />website: www.everettwa.gov/permit January 24, 2017 ( email., everetteps(oeverettwa.gov <br />