Laserfiche WebLink
0 <br />C <br />I <br />E <br />G <br />L <br />2 <br />3 <br />4 <br />R <br />no <br />7 <br />L? • <br />E <br />m <br />ENERGY CODE NOTES <br />1. LOAD CALCULATIONS HAVE BEEN PERFORMED IN ACCORDANCE WITH WSEC C403.2.1. <br />2. EQUIPMENT HAS BEEN SELECTED PER WSEC C403.2.2. BOILERS AND PUMPS ARE SELECTED FOR <br />PRIMARY/STANDBY OPERATION PER EXCEPTION 1. <br />3. VENTILATION AND THE ABILITY TO REDUCE OUTSIDE AIR TO IMC MINIMUMS SHALL BE PROVIDED PER WSEC <br />C403.2.5. <br />4. MOTORS 1 HP AND LARGER SHALL BE ENERGY EFFICIENT TYPE PER WSEC C403.2.13; MOTORS 1/12 HP TO 1 HP <br />SHALL BE ECM TYPE OR MEET MINIMUM EFFICIENCY REQUIREMENTS PER WSEC C403.2.10.3. <br />5. SYSTEMS WITH COMBINED FAN HORSEPOWER EXCEEDING 5 HP SHALL COMPLY WITH MOTOR SIZING LIMITATIONS <br />OF WSEC C403.2.10. <br />6. HEAT PUMPS SHALL INCLUDE MICROPROCESSOR CONTROLS THAT MINIMIZE SUPPLEMENTAL HEAT USAGE DURING <br />START-UP, SET-UP, AND DEFROST CONDITIONS. THESE CONTROLS SHALL ANTICIPATE THE NEED FOR HEAT AND <br />PROVIDE COMPRESSION HEAT AS THE FIRST STAGE. PROVIDE A VISUAL INDICATION WHEN SUPPLEMENTAL HEAT <br />IS IN USE AND A CONTROL LOCK -OUT OF SUPPLEMENTAL HEAT FOR OUTSIDE AIR TEMPERATURES ABOVE 40 DEG F <br />PER WSEC C403.2.4.1.1. <br />7. TEMPERATURE CONTROL SYSTEM SHALL HAVE A MINIMUM DEAD BAND OF 5 DEGREES AS REQUIRED BY WSEC <br />C403.2.4.2. <br />8. HVAC SYSTEMS SHALL BE EQUIPPED WITH AUTOMATIC CONTROLS CAPABLE OF PROVIDING NIGHT SETBACK, <br />SEVEN DIFFERENT DAILY SCHEDULES, AND OPTIMUM START PER THE REQUIREMENTS OF WSEC C403.2.4.3. <br />9. OUTSIDE AIR INTAKES, EXHAUST OUTLETS, AND RELIEF OUTLETS SHALL BE PROVIDED WITH DAMPERS THAT <br />COMPLY WITH WSEC C403.2.4.4. DAMPER SHALL AUTOMATICALLY CLOSE WHEN SYSTEM OR SPACES SERVED ARE <br />NOT IN USE OR DURING WARM-UP, COOL -DOWN, AND SETBACK. DAMPER MAXIMUM LEAKAGE RATE SHALL NOT <br />EXCEED MAXIMUM ALLOWED BY WSEC C402.4.5.2. <br />10. COMBUSTION HEATING EQUIPMENT WITH A CAPACITY OVER 225 MBH SHALL HAVE MODULATING OR STAGED <br />COMBUSTION CONTROL PER WSEC C403.2.4.6. <br />11. ALL DUCTWORK SHALL BE CONSTRUCTED AND SEALED IN ACCORDANCE WITH IMC, WSEC C402 AND IBC <br />REQUIREMENTS PER WSEC C403.2.7. <br />12. DUCTWORK SHALL BE INSULATED TO THE APPROPRIATE R-VALUE AS REQUIRED BY WSEC C403.2.7. <br />13. PIPING SHALL BE INSULATED AS REQUIRED BY WSEC C403.2.8. <br />14. PIPING INSULATION EXPOSED TO WEATHER SHALL BE PROTECTED FROM DAMAGE, INCLUDING THAT DUE TO <br />SUNLIGHT, MOISTURE, EQUIPMENT MAINTENANCE AND WIND, AND SHALL BE SHIELDED FROM SOLAR RADIATION <br />PER WSEC C403.2.8.1. <br />15. PROVIDE HIGH LIMIT SHUT-OFF CONTROL OF ECONOMIZER COOLING PER TABLE C403.3.1.1.3(2). <br />16. ECONOMIZER DAMPERS SHALL BE CAPABLE OF BEING SEQUENCED WITH MECHANICAL COOLING EQUIPMENT. <br />ECONOMIZERS ON SYSTEMS WITH COOLING CAPACITY GREATER THAN 65 MBH SHALL BE CAPABLE OF PROVIDING <br />PARTIAL COOLING PER WSEC C403.3.1.1.2. <br />17. ECONOMIZER CONTROLS SHALL BE SUCH THAT ECONOMIZER OPERATION DOES NOT INCREASE BUILDING <br />HEATING ENERGY DURING NORMAL OPERATIONS PER WSEC C403.4.1.4, AND SHALL BE INTEGRATED WITH <br />MECHANICAL COOLING SYSTEM AND BE CAPABLE OF PROVIDING PARTIAL COOLING PER WSEC C403.4.1.3. <br />18. FOR VAV SYSTEMS WITH DDC, PROVIDE STATIC PRESSURE RESET PER WSEC C403.4.2.2. <br />19. SUPPLY AIR SYSTEMS SERVING MULTIPLE ZONES SHALL BE VAV TYPE DESIGNED AND CAPABLE OF BEING <br />CONTROLLED TO REDUCE PRIMARY AIR SUPPLY TO EACH ZONE TO A MAXIMUM FLOW RATE AS ALLOWED BY WSEC <br />C403.4.5. <br />20. HVAC SYSTEMS WITH MULTIPLE ZONES SHALL REQUIRE TEMPERATURE RESET CONTROLS WHICH <br />AUTOMATICALLY RESET SUPPLY AIR TEMPERATURES PER WSEC C403.4.5.4. <br />21. COOLING SYSTEMS SHALL NOT USE HOT GAS BYPASS OR OTHER EVAPORATOR PRESSURE CONTROL SYSTEMS <br />UNLESS THERE ARE MULTIPLE STEPS OF UNLOADING. HOT GAS BYPASS CAPACITY SHALL BE LIMITED PER TABLE <br />C403.4.7. DOES NOT APPLY TO UNITARY PACKAGED SYSTEMS 90 MBH OR SMALLER. <br />22. HYDRONIC HEATING SYSTEMS CONSISTING OF A SINGLE BOILER GREATER THAN 500 MBH INPUT CAPACITY SHALL <br />HAVE MULTI -STAGE OR MODULATING BURNER PER WSEC C403.4.3. <br />23. HYDRONIC HEATING SYSTEMS CONSISTING OF MULTIPLE BOILERS DELIVERING HOT WATER OR STEAM TO A <br />COMMON DISTRIBUTION SYSTEM SHALL INCLUDE AUTOMATIC CONTROLS CAPABLE OF SEQUENCING BOILERS PER <br />C403.4.3. <br />24. BOILER PLANTS SHALL HAVE THE CAPABILITY TO AUTOMATICALLY REDUCE FLOW TO THE PLANT WHEN A BOILER <br />IS SHUT DOWN AND SHALL AUTOMATICALLY SHUT OFF FLOW TO THE CORRESPONDING CHILLER/BOILER PER <br />WSEC C403.4.3.5. <br />25. FOR HYDRONIC SYSTEMS 300 MBH AND LARGER, PROVIDE THE CAPABILITY TO AUTOMATICALLY RESET SUPPLY <br />WATER TEMPERATURES BASED ON RETURN WATER TEMP OR OUTSIDE AIR TEMPERATURE AND REDUCE SYSTEM <br />PUMP FLOW BY AT LEAST 50% PER WSEC C403.4.3.4. <br />26. AIR AND HYDRONIC SYSTEMS SHALL BE BALANCED AS REQUIRED IN SECTION C408.2.2.1 AND C408.2.2.2 OF THE <br />WSEC. <br />27. PROVIDE COMMISSIONING PLAN & REPORT REQUIREMENTS FOR PRELIMINARY AND FINAL COMMISSIONING PER <br />SECTION C408.1. PROVIDE SEQUENCE OF OPERATIONS AND TEST PROCEDURES PER SECTION C408.1.2 AND <br />SUBMIT COMPLIANCE CHECKLIST PER SECTION C408.1.3.4 OF THE WSEC TO THE BUILDING OFFICIAL UPON <br />SUBSTANTIAL COMPLETION. <br />28. THESE "ENERGY CODE NOTES" ARE LISTED TO SATISFY THE BUILDING DEPARTMENT'S REQUIREMENT THAT <br />CERTAIN INFORMATION BE PLACED ON THE PLANS, BUT DO NOT DIMINISH THE FULL PROJECT REQUIREMENTS. <br />PROVIDE ITEMS IN EXCESS OF CODE WHERE NOTED ON DRAWINGS AND IN SPECIFICATIONS. FOR OTHER ADDED <br />REQUIREMENTS, SEE SPECIFICATIONS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: <br />ITEM SECTION# <br />AS -BUILT DOCUMENTS 20 05 00 <br />O&M MANUALS 20 02 00 <br />PIPING & DUCT INSULATION 20 07 00 <br />DUCTWORK SEALING & TESTING 2331 00 <br />CONTROLS DIVISION 25 <br />-1 A I B <br />54 <br />MECHANICAL GENERAL NOTES <br />1. ALL DUCT PENETRATIONS THRU WALLS AND FLOORS SHALL BE PROVIDED WITH CLOSURE <br />COLLARS (BOTH SIDES OF PENETRATION) AND BE TIGHTLY SEALED TO PREVENT THE <br />TRANSMISSION OF NOISE. <br />2. CONTRACTOR SHALL CAREFULLY COORDINATE WORK W/ ALL OTHER TRADES, ESPECIALLY IN <br />CEILING SPACES WHERE SPACE IS TIGHT. SHEET METAL CONTRACTOR SHALL HAVE PRIORITY <br />OVER OTHER MECHANICAL TRADES IN CEILING SPACE WHERE CONFLICTS OCCUR. <br />3. ALL PIPING & DUCTWORK SHOWN IS SCHEMATIC, CONTRACTOR SHALL PROVIDE ALL <br />OFFSETS/ELBOWS AS REQ'D TO ALLOW ROUTING AROUND STRUCTURE, ELECTRICAL, & OTHER <br />INTERFERENCES. <br />4. FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 8 FEET, & MAY ONLY BE USED WHERE <br />SPECIFICALLY SHOWN. <br />5. PROVIDE MANUAL VOLUME DAMPERS IN ALL BRANCH DUCTS AND SPLITS IN MAIN DUCTS AND <br />WHERE REQ'D BY BALANCERS; ONLY SOME OF THE REQ'D DAMPERS ARE SHOWN ON THE <br />PLANS. <br />6. WHERE DUCT SIZES ARE NOT SHOWN (OR NOT CLEAR), PROVIDE THE FOLLOWING SIZED <br />CONNS. (OR EQUIVALENT RECTANGULAR). <br />DUCTS TO OTHER DUCTS TO OTHER <br />CFM DIFFUSERS DUCTS CFM DIFFUSERS DUCTS <br />0 - 100 6" 0 6110 701 - 900 18,10 14" 0 <br />101 - 150 8110 8110 901 - 1200 20" 0 16" 0 <br />151 - 250 10" 0 8" 0 1201 - 1500 20" 0 18" 0 <br />251 - 400 12" 0 10,10 1501 - 2000 22" 0 20" 0 <br />401 - 500 14" 0 12" 0 2001 - 2400 24" 0 22" 0 <br />501 - 700 16" 0 12" 0 <br />7. MECHANICAL EQUIPMENT 1/2 HP AND LESS (SINGLE PHASE POWER ONLY) SHALL HAVE ANY <br />REQUIRED STARTER/CONTROL RELAY PROVIDED BY DIVISION 25 (EXCEPT WHERE <br />SPECIFICALLY SHOWN OR SPECIFIED OTHERWISE). <br />8. FOR UNSIZED PIPING (OR SIZE NOT CLEAR), PIPE SIZE SHALL MATCH THE SIZE OF THE LARGEST <br />ADJACENT CONNECTING PIPE SIZE SHOWN. WHERE THE ADJACENT PIPE IS NOT SHOWN (OR <br />NOT CLEAR), THE PIPE SIZE SHALL BE BASED ON THE GPM FLOWING IN THE PIPE (USE TOTAL OF <br />COILS SERVED FOR HYDRONIC SYSTEM, USE FIXTURE UNITS AND CORRESPONDING GPM PER <br />THE UPC FOR DOMESTIC WATER SYSTEMS, USE WASTE FIXTURE UNITS & UPC TABLES FOR <br />WASTE/VENT SYSTEM), AND A VELOCITY NO GREATER THAN 4 FEET PER SECOND. USE UPC <br />CURVES FOR GPM/VELOCITY FOR APPROPRIATE PIPING MATERIAL INVOLVED. <br />9. ALL WORK IS BASE BID UNLESS SPECIFICALLY NOTED AS ALTERNATE BID WORK. <br />10. ALL ITEMS ARE NEW UNLESS SPECIFICALLY NOTED AS EXISTING. <br />11. MECHANICAL WORK IS NOT LIMITED TO MECHANICAL DRAWINGS AND DIVISION 21, 22, 23, & 25 <br />SPECIFICATIONS. THERE IS ADDITIONAL MECHANICAL WORK TO BE INCLUDED IN THE BID <br />INDICATED ON OTHER DRAWINGS AND IN OTHER SPECIFICATION DIVISIONS. CONTRACTOR <br />SHALL REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL MECHANICAL WORK. <br />12. BALANCING NOTES: PROVIDE AIR BALANCING OF HVAC SYSTEM, AND HYDRONIC SYSTEM. SEE <br />SECTION AND 23 05 93 FOR COMPLETE REQUIREMENTS. <br />13. ALL PIPING AND DUCTWORK SHALL BE RUN CONCEALED, UNO. <br />14. PROVIDE TRANSITIONS FROM DUCT SIZES INDICATED TO CONNECTION SIZES AT EQUIPMENT. <br />WHERE THE CONNECTING DUCT IS LINED, THE TRANSITION SHALL BE LINED. USE 2" LINING <br />(UNO). <br />15. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE & SELECT FINAL LOCATIONS <br />OF ALL AIR INLETS/OUTLETS. SHIFT AIR INLETS/ OUTLETS FROM LOCATIONS SHOWN AS REQ'D <br />TO AVOID CONFLICTS W/ STRUCTURE, LIGHTS, & OTHER ITEMS. SUCH SHIFTS SHALL MAINTAIN <br />SYMMETRY OF AIR TERMINALS & SHALL HAVE PRIOR APPROVAL OF ARCHITECT/ENGINEER. <br />16. CEILING SPACE IS TIGHT IN A NUMBER OF AREAS. IN SUCH AREAS, CEILING AIR INLET/OUTLET <br />CONN'S REQUIRE SIDE INLET PLENUM, SEE DETAIL 4, SHEET M4.5. PROVIDE WHERE REQ'D DUE <br />TO SPACE LIMITATIONS TO PREVENT KINKS IN FLEX. DUCT AND ALLOW PROPER CONN. <br />17. SEISMICALLY ANCHOR ALL UNITS & EQUIPMENT TO BUILDING. (UNO). <br />18. FOR HVAC TRANSITIONS, ELBOWS, & CONNECTIONS, SEE DETAILS ON SHEET M4.5. THESE <br />FITTINGS SHALL BE PROVIDED PER DETAILS REGARDLESS OF HOW THE REVIT PROGRAMS <br />INDICATES GRAPHICALLY ON HVAC SHEETS. <br />19. PROVIDE COORDINATION TO ALLOW ALL ITEMS TO BE INSTALLED IN CEILINGS. ANY <br />COORDINATION DRAWINGS NEEDED TO ALLOW CONTRACTOR COORDINATION SHALL BE <br />PROVIDED, BUT THEY ARE NOT REQUIRED TO BE SUBMITTED TO THE ENGINEER FOR REVIEW. <br />FBI <br />E <br />F <br />MECHANICAL LEGEND <br />SYMBOL <br />DESCRIPTION <br />ABBREV. <br />DESCRIPTION <br />WASTE OR SOIL (W) <br />AFF <br />AHJ <br />ABOVE FINISHED FLOOR <br />AUTHORITY HAVING JURISDICTION <br />- - - - - - <br />VENT (V) <br />APPROX <br />ARCH <br />APPROXIMATELY <br />ARCHITECTURAL <br />- <br />COLD WATER CW <br />( ) <br />AUTO <br />AAV <br />AUTOMATIC <br />AUTOMATIC AIR VENT <br />-- <br />HOT WATER (HW) <br />BDD <br />B.O.D. <br />BACKDRAFT DAMPER <br />BOTTOM OF DUCT <br />--- <br />HOT WATER CIRCULATING (HWC) <br />BTU <br />BTUH <br />BRITISH THERMAL UNIT <br />BTHERMAL UNIT/HOUR <br />HWS <br />HOT WATER HEATING SUPPLY (HWS) <br />BLDG <br />CAP <br />BUUIILLDINDIN G <br />CAPACITY <br />HWR <br />HOT WATER HEATING RETURN (HWR) <br />CLG <br />CO <br />CEILING <br />CLEANOUT <br />F <br />FIRE LINE (F) <br />COP <br />CONN <br />COEFFICIENT OF PERFORMANCE <br />CONNECTION <br />C <br />CONDENSATE LINE (C) <br />CONT <br />CFM <br />CW <br />CONTINUE, CONTINUATION <br />CUBIC FEET PER MINUTE <br />COLD WATER <br />Q <br />CLEANOUT <br />DEF, F <br />DIA 0 <br />DEGREE FAHRENHEIT <br />DIAMETER <br />Q <br />FLOOR DRAIN <br />DN <br />DOWN <br />-Do-- <br />ISOLATION VALVE - SEE SPECIFICATIONS FOR TYPE <br />DWG <br />DB <br />DRAWING <br />DRY BULB <br />RG <br />REFRIGERANT GAS (RG) <br />DL <br />DOOR LOUVER <br />EA <br />EACH <br />RL <br />REFRIGERANT LIQUID (RL) <br />EFF <br />EFFICIENCY <br />ELEC <br />ELECTRICAL, ELECTRIC <br />fib-- <br />BALANCING VALVE <br />EER <br />EAT <br />ENERGY EFFICIENCY RATIO <br />ENTERING AIR TEMPERATURE <br />CHECK VALVE <br />EWB <br />ENTERING WET BULB <br />EDB <br />EOL <br />EXH <br />EXIST, (E) <br />ENTERING DRY BULB <br />END OF LINING <br />EXHAUST <br />EXISTING <br />UNION <br />RELIEF VALVE <br />ESP <br />F <br />FV <br />FPM <br />FPS <br />FLEX <br />EXTERNAL STATIC PRESSURE <br />FIRE <br />FACE VELOCITY <br />FEET PER MINUTE <br />FEET PER SECOND <br />FLEXIBLE <br />Q <br />AUTOMATIC AIR VENT <br />STRAINER WITH BLOW -OFF VALVE <br />CONCENTRIC REDUCER <br />FL <br />FCO <br />FLOOR <br />FLOOR CLEAN OUT <br />�y <br />HOSE BIBB <br />FLA <br />GAL <br />GALV. <br />FULL LOAD AMPS <br />GALLON <br />GALVANIZED <br />WATER HAMMER ARRESTOR <br />P.D.I. SIZE AS SHOWN <br />PRESSURE GAUGE <br />HP <br />HORSE POWER <br />HW <br />HWC <br />IN <br />HOT WATER <br />HOT WATER CIRCULATION <br />INCH <br />THERMOMETER <br />20/12 <br />DUCT (FIRST FIGURE, SIDE SHOWN) <br />I.E. <br />KW <br />INVERT ELEVATION <br />KILOWATT <br />20/12L 20/12L' <br />LINED DUCT (DIM. FOR NET FREE AREA) EOL= END * = 2" THICK <br />OF LINING LINING <br />LAT <br />LDB <br />LEAVING AIR TEMPERATURE <br />LEAVING DRY BULB <br />R(D) <br />RISE (R) OR DROP (D) ARROW IN <br />LWT <br />LEAVING WATER TEMPERATURE <br />I I <br />DIRECTION OF FLOW <br />LWB <br />LEAVING WET BULB <br />® <br />DUCT SECTION (SUPPLY) <br />MAX <br />MAXIMUM <br />MFR <br />MBH <br />MANUFACTURER <br />THOUSAND BTUH <br />DUCT SECTION (EXHAUST OR RETURN) <br />MCA <br />MECH <br />MINIMUM CIRCUIT AMPS <br />MECHANICAL <br />0 <br />ROUND DUCT <br />MIN <br />NO <br />MINIMUM <br />NORMALLY OPEN <br />VOLUME DAMPER (MANUAL) <br />NC <br />NORMALLY CLOSED <br />M <br />MOTORIZED DAMPER <br />NTOS <br />OBD <br />ER <br />NOT SCALE <br />OPPOSED BLADE DAMPER <br />FLEXIBLE CONNECTION <br />FIRE DAMPER <br />COMBINATION FIRE/SMOKE DAMPER <br />OA <br />ORL <br />PH <br />P.D.I. <br />OUTSIDE AIR <br />OVERFLOW RAINLEADER <br />PHASE <br />PLUMBING AND DRAINAGE INST. <br />DUCT SMOKE DETECTOR <br />PD <br />RA <br />PRESSURE DROP <br />RETURN AIR <br />FLEXIBLE DUCT <br />REL <br />RL <br />RELIEF AIR <br />RAINLEADER, REFRIGERANT LIQUID <br />ELBOW WITH TURNING VANES <br />RLA <br />REF <br />RATED LOAD AMPS <br />REFERENCE <br />­0 <br />DUCT UP <br />(RECTANGULAR) <br />REQ'D <br />RPM <br />RM <br />REQUIRED <br />REVOLUTIONS PER MINUTE <br />ROOM <br />r_z �--0 <br />DUCT UP (RECTANGULAR) <br />S <br />SA <br />SUPPLY <br />SUPPLY AIR <br />x �] <br />DUCT DOWN (RECTANGULAR) <br />SCO <br />S.O. <br />SURFACE CLEANOUT <br />SCREENED OPENING <br />DUCT DOWN (RECTANGULAR) <br />SS <br />TEMP <br />STAINLESS STEEL <br />TEMPERATURE <br />�m <br />DUCT UP (ROUND) <br />TD <br />TG <br />TSP <br />TRANSFER DUCT <br />TRANSFER GRILLE <br />TOTAL STATIC PRESSURE <br />�-0 <br />DUCT DOWN (ROUND) <br />(WHERE 2 CFM'S SHOWN, 1st = HIGH SPEED CFM <br />®SIZE,SYMBOL <br />CFM <br />CEILING OUTLET <br />2nd =LOW SPEED CFM) <br />TYP <br />UNO <br />VFD <br />TYPICAL <br />UNLESS NOTED OTHERWISE <br />VARIABLE FREQUENCY DRIVE <br />�SIZE,SYMBOL <br />CEILING INLET (WHERE 2 CFM'S SHOWN, 1st =HIGH SPEED CFM <br />CFM <br />Znd =LOW SPEED CFM <br />VTR <br />VERT <br />VENT THROUGH ROOF <br />VERTICAL <br />OT TOOT <br />THERMOSTAT G= WITH GUARD <br />A <br />A= AVERAGED WITH OTHER T <br />V <br />WCO <br />VOLTS, VOLTAGE, VENT <br />WALL CLEAN OUT <br />O <br />SWITCH <br />W <br />WASTE <br />INTERVAL TIMER <br />IT <br />WA <br />WB <br />WATT <br />WET BULB <br />2 <br />DETAIL IDENTIFICATION NUMBER <br />WL <br />WALL LOUVER <br />M3.1 <br />SHEET ON WHICH DETAIL IS SHOWN <br />W/ <br />WITH <br />A <br />SECTION IDENTIFICATION LETTER <br />M3.1 <br />SHEET ON WHICH SECTION IS SHOWN <br />SOUND ATTENUATOR (T LONG, UNO) <br />SEE SYMBOL LIST AND SCHEDULES ON SHEETS M1.01 & M1.02 <br />lei <br />H <br />J <br />K <br />2 <br />3 <br />4 <br />5 <br />�'90 <br />7 <br />• <br />6 <br />ocoI;- <br />U <br />a ° a) <br />' � <br />N F <br />E vz <br />cn 8Xco m ,Q <br />a� <br />�Loo <br />y cm U <br />' M L <br />Q cco <br />0)� r <br />3 <br />r c <br />r <br />0 , <br />w (� <br />war <br />V � <br />w to N <br />_jw� <br />o� w <br />�! <br />UQp:3 <br />_w Qo <br />Z0 wQ <br />�UZ0� 3: <br />>w <br />O=CVwQ� <br />UJW3:j <br />F- LLj <br />c) <br />w=o co <br />cn W <br />wwZ) a <br />w W <br />o�� <br />cl) <br />STAMP <br />LEO T <br />!I <br />s`sf ONAL 8't <br />SIGNED <br />03-10-2016 <br />PROJECT NO. <br />2015-170 <br />DRAWN CHECKED <br />TP MLT <br />DATE <br />03.10.2016 <br />REVISIONS <br />po 02.22.16 ORIGINAL <br />BID SET <br />ADDENDUM[ <br />I� TITLE <br />MECHANICAL <br />LEGEND AND <br />NOTES <br />SHEET <br />Mo. 1 <br />ISSUED FOR <br />REBID SET <br />0" 1" 2' <br />SHEET SIZE IS TRUE SCALE WHEN <br />ABOVE LINE MEASURES AS NOTED <br />