LEVEL 2 ROOM AIR BALANCE LEVEL 2 ROOM AIR BALANCE (CONT)
<br /> ROOM REQ. AIR REQ. ACT. AIR ROOM REQ. AIR REQ. ACT. AIR W C
<br /> 03
<br /> NO. ROOM NAME CHANGES PRESSURE CHANGES SUPPLY EXHAUST PRESS. REMARKS NO. ROOM NAME CHANGES PRESSURE CHANGES SUPPLY EXHAUST PRESS. REMARKS U ‘...)
<br /> (AC/HR) RELATIONSHIPS (AC/HR) AIR (CFM) AIR (CFM) AIR (CFM) (AC/HR) RELATIONSHIPS (AC/HR) AIR (CFM) AIR (CFM) AIR (CFM)
<br /> Z IT3
<br /> A2001 SURGERY WAITING
<br /> 4 NA 4.2 2,000 1,250 750 D2090 CORRIDOR 2 NA 5.6 1,250 0 1,250 la .......
<br /> A2002 RESOURCE AREA 4 NA 19.8 350 0 350 D2086 PATIENT TOILET 10 N 12.4 0 80 -80 0 ..3-(1)
<br /> A2003 PUBLIC TOILET WOM 10 N 13.5 0 400 -400 D2081 SOILED 10 N 13.1 100 200 -100
<br /> A2004 PUBLIC TOILET MEN 10 N 13.7 0 400 -400 02101 CLEAN / LINEN 4 P 11.1 200 130 70
<br /> A2013 IDF ROOM 0 NA 1.9 50 0 50 DEDICATED FCU-201 02095 HSKP 10 N 10.2 0 115 -115
<br /> A2014 ELECTRICAL ROOM 0 NA 15.9 450 450 0 D2097 PATIENT TOILET 10 N 12.4 0 80 -80 ( ' OC +j
<br /> A2016 CHECK-IN STATIONS 4 NA 10.6 400 0 400 D2094 PATIENT STATION 6 NA 8.9 135 135 0 .
<br /> A2017 COPY ALCOVE 4 NA 46.9 0 1,000 -1,000 D2096 PATIENT STATION 6 NA 6.4 135 135 0
<br /> t (1) >''
<br /> A2018 SS CONTROL 4 NA 14.8 300 150 150 D2098 PATIENT STATION 6 NA 8.9 135 135 0
<br /> A2020 PUBLIC ELEV LOBBY 2 NA 6.9 250 0 250 D2102 PATIENT STATION 6 NA 7.1 135 135 0
<br /> 4 EQPT STOR/LOCKER
<br /> 4 NA 12.9 400 500 -100
<br /> 0
<br /> 0208 Q
<br /> 100
<br /> 100 /
<br /> A2021 OFFICE
<br /> 4 NA 9.5 ..........
<br /> A2022 HEIGHT & WEIGHT 4 NA 22.2 0 200 -200 D2088 SOILED 10 N 11.8 100 200 -100
<br /> A2023 PATIENT STATION 6 NA 8.3 150 150 0 D2061 PATIENT TOILET 10 N 10.9 0 80 -80
<br /> A2024 PATIENT STATION 6 NA 8.1 150 150 0 D2106 CORRIDOR 2 NA 2.8 500 500 0
<br /> A2025 PATIENT STATION 6 NA 7.6 150 150 0 E2049 ISO ROOM 12 N 12.2 300 320 -20 EVERETT, WASHINGTON
<br /> A2065 PATIENT STATION 6 NA 7.9 135 135 0 E2049A PATIENT TOILET 10 N 10.1 0 85 -85
<br /> A2069 PATIENT STATION 6 NA 7.4 135 135 0 E2046 STAFF BREAK RM 4 NA 18.7 600 700 -100 .GU NSO�.
<br /> A2067 MEDS CGS 4 P 5.7 150 0 150 E2047 DICTATION 4 NA 11.5 200 200 0 <,,S-":/
<br /> A2073 PATIENT STATION 6 NA 7.6 135 135 0 E2051 TOILET 10 N 10.9 0 80 -80 �,
<br /> 'ZG FL,
<br /> A2074 ISO ROOM 12 N 13.2 250 300 -50 '` E2052 TOILET 10 N 10.5 0 80 -80 N
<br /> A2074A PATIENT TOILET 10 N 11.9 0 80 -80 E2180 CORRIDOR 2 NA 22.5 0 3,340 -3,340 C
<br /> A2075 PATIENT TOILET 11 N 13.3 0 80 -80 E2125 PACU 6 NA 6.0 4,080 4,000 80 I ,
<br /> A2064 CORRIDOR 2 NA 6.1 250 0 250
<br /> E2115 SOILED 10 N 10.1 135 235 -100 tiIT ECS
<br /> 1
<br /> A2076 CLEAN / LINEN 4 P 11.7 200 100 100
<br /> E2176 CLEAN CORE 6 P 5.7 1,050 1,000 50 Architecture/Planning/Interior Design
<br /> A2077 NOURISH 2 N 59.1 150 700 -550 E2116 CLEAN 4 P 13.1 260 160 100 Portland Seattle Los Angeles Washington DC
<br /> A2213 PEDS PLAY 4 NA 12.6 200 200 0 E2117 DICTATION 4 NA 15.3 330 330 0 925 Fourth Ave.,Suite 2400
<br /> A2214 KITCHEN / VENDING 4 NA 34.6 300 550 -250 E2118 NURSE STATION 4 NA 6.7 100 0 100 Seattle,Washington 98104
<br /> A2215 QUIET ROOM 4 NA 6.3 120 120 0 E2177 OR-4 ORTHO 15 P 24.8 3,190 2,790 400
<br /> NA 21.0 315 315 0 E2178 OR-5 ORTHO 15 P 24.8 3,190 2,790 400 (PH)20606232986
<br /> 414
<br /> A2005 QUIET ROOM 4
<br /> (FAX)206 623 7868
<br /> B2006 CONSULT ROOM 4 NA 8.5 200 200 0 E2121 OFFICE 4 NA 6.5 100 100 0
<br /> B2008 CONSULT ROOM 4 NA 7.8 160 160 0 E2122 TOILET 10 N 10.1 0 80 -80
<br /> Consultants
<br /> B2009 STORAGE/ JAN SINK 10 N 11.7 0 200 -200 E2123 EQUIP 2 NA 17.4 200 250 -50
<br /> B2011 CONSULT ROOM 4 NA 7.0 160 160 0 E2124 PRIVATE PATIENT RM 6 NA 7.3 150 150 0 LIFE SAFETY
<br /> ROLF JENSEN & ASSOCIATES
<br /> B2068 CORRIDOR 2 NA 5.7 500 0 500 E2182 CORRIDOR _ _ 2 NA 4.2 750 0 750 _ 19125 North Creek Parkway Suite 120
<br /> B2007 CORRIDOR 2 NA 17.5 320 950 -630 E2183 OR-7 ORTHO P 3,155 2,780inr2 Bothell,Washington 98011
<br /> 11111111111
<br /> 11111111111
<br /> B2071 STAFF TOILET 10 N 13.1 0 100 -100 E2184 OR-8 ORTHO P 3,155 2,780 CIVIL ENGINEER
<br /> 82072 STAFF TOILET 10 N 13.1 0 100 -100 E 8• S LL S'AC 0 NA 1.0 600 800 - OS Magnusson Klemencic Associates
<br /> 1301 Fifth Avenue,Suite 3200
<br /> B2126 SERVICE ELEV LOBB 2 NA 15.8 600 2,300 -1,700 E2187 OR-10 GENERL SHELL 0 NA 0.0 0 0 0
<br /> Seattle,Washington 98101-2699
<br /> B2012 CONSULT ROOM 4 NA 6.9 160 160 0 E2188 OR-11 GENERL SHELL 0 NA 0.0 0 0 0
<br /> B2127 CORRIDOR 2 NA 10.0 150 0 150 E2192 CORRIDOR - SHELL 0 NA 0.0 0 0 0 LANDSCAPE ARCHITECT
<br /> Site Workshop
<br /> B2131 PER OP
<br /> EDUCATOR 4 NA 6.1 120 120 0 F2181 OR-6 ENT/ORTHO 15 P 25.0 3,370 2,970 400
<br /> 927 Post Alley
<br /> B2128 PATHOLOGY 6 N 6.1 275 350 -75 F2193 CORRIDOR 2 NA 5.4 1,500 1,000 500 INCLUDES CORRIDORS C2194 AND F2202 Seattle,Washington 98101
<br /> B2133 SERVICE ELEV LOBB 2 NA 8.3 500 0 500 F2198 DECONT 10 N 15.1 350 450 -100 STRUCTURAL ENGINEER
<br /> B2134 SERVICE ELEV LOBB 2 NA 3.6 215 0 215 SUPPLIED FROM C-WING AHU F2201 CLEAN 4 P 9.2 300 200 100 Magnusson Klemencic Associates
<br /> 82147 CORRIDOR 2 NA 6.2 450 0 450 F2185 OR-9 UROL SHELL 0 NA 0.0 0 0 0 1301 Fifth Avenue,Suite 3200
<br /> Seattle, Washington 98101-2699
<br /> B2135 BUYERS 4 NA 12.9 190 190 0 F2191A ANTE - SHELL 0 NA 0.0 0 0 0
<br /> B2136 MGN SYSTEMS 4 NA 14.4 210 210 0 F2191 OR-12 GENERAL SHELL 0 NA 0.0 0 0 0 MECHANICAL ENGINEER ---
<br /> CDi Engineers
<br /> B2137 SCHEDULING/BILLING 4 NA 16.6 500 500 0 F2203 STAFF TOILET 10 N 11.5 0 100 -100 19203 36th Ave.W,Suite 200
<br /> C2146 IMPLANT RESOURCE 4 NA 7.3 600 600 0 F2204 STAFF TOILET 10 N 14.7 50 130 -80 Lynnwood,Washington 98036 -
<br /> B2161 CORRIDOR 2 NA 3.8 1,000 0 1,000 F2205 ANESTHESIA WKRM 8 N 11.9 730 800 -70 ELECTRICAL ENGINEER
<br /> B2166 CONTROL STATION 4 NA 7.8 250 250 0 F2206 EQUIP STORAGE 2 NA 5.3 400 350 50 SPARLING
<br /> B2165 SUPERVISOR 4 NA 10.0 240 240 0 F2207 OR HSKP 10 N 10.1 145 245 -100 720 Olive Way,Suite 1
<br /> 400 Seattle,Washington 98101-01-
<br /> 1853
<br /> B2163 MANAGER 4 NA 12.8 150 150 0 F2208 IDF ROOM 0 NA 2.1 50 0 50 DEDICATED FCU-204
<br /> B2164 MANAGER 4 NA 13.0 150 150 0 F2212 CORRIDOR 2 NA 13.8 250 0 250 GENERAL CONTRACTOR
<br /> M.A.Mortensen Company
<br /> B2158 EQUIPMENT/STORAGE 2 NA 9.2 1,300 1,400 -100 F2211 ELECT. 0 NA 9.5 0 50 -50 A 14719 N.E.29th Place
<br /> Bellevue,Washington 98007
<br /> B2171 DICTATION 4 NA 16.5 240 240 0 E2185 OR-9 ENT/ORTHO111111111111 P111111111111111111111111111111 2,780IMF
<br /> B2168 ANESTHESIA OFFICE 4 NA 11.6 390 390 0
<br /> 82169 OFFICE 4 NA 9.6 390 390 0 Revisions
<br /> B2173 OR-1 ORTHO 15 P 24.6 3,190 2,790 400
<br /> B2174 OR-2 ORTHO 15 P 24.6 3,190 2,790 400
<br /> DOCUMENT RELEASE 09 11/03/08
<br /> B21 14 PRIVATE PATIENT RM 6 NA 6.6 150 150 0 __
<br /> B2148 ELECTRICAL ROOM 0 NA 17.5 450 450 0 DOCUMENT RELEASE 11 02/09/09
<br /> C2138 COPY ROOM 4 NA 24.1 250 350 -100 DOCUMENT RELEASE 13 03/09/09
<br /> C2141 MEDICAL DIRECTOR 4 NA 14.3 325 325 0 n DOCUMENT RELEASE 21 09/14/09
<br /> C2145 ADMIN ASSISTANT 4 NA 9.1 150 150 0 n WORK CHANGE PROPOSAL 145 06/02/14
<br /> C2142 CLINICAL DIRECTOR 4 NA 10.6 230 230 0
<br /> C2143 TOILET 10 N 12.8 0 100 -100
<br /> C2152 STAFF RESOURCE RM 4 NA 14.3 750 750 0
<br /> C2153 CORRIDOR 2 NA 5.7 530 0 530
<br /> C2154 STAFF LOUNGE 10 N 14.4 1,700 1,630 70
<br /> C2155 CONFERENCE EDUCA 4 NA 13.6 800 800 0
<br /> C2156 PHY'S LOUNGE 10 N 13.8 450 400 50
<br /> C2157 BIOMED 6 P 7.1 205 135 70
<br /> C2175 OR-3 PLASTICS 15 P 24.5 3,360 2,960 400
<br /> B2172 CORRIDOR 2 NA 4.9 750 0 750
<br /> C2195 STAFF TOILET 10 N 12.8 0 100 -100 CLOSEOUT PRINTING 04/01/12
<br /> C2196 STAFF TOILET 10 N 16.9 80 160 -80
<br /> C2197 CART HOLDING 2 NA 4.5 300 400 -100
<br /> C2151 IDF ROOM 0 NA 2.3 50 0 50 DEDICATED FCU-203
<br /> Drawing Title
<br /> D2021 CORRIDOR 2 NA 6.1 1,250 600 650
<br /> D2026 PATIENT STATION 6 NA 8.6 150 150 0 EQUIPMENT SCHEDULES
<br /> D2027 NURSE STATION 4 NA 32.0 300 700 -400
<br /> D2028 PATIENT STATION 6 NA 8.6 150 150 0
<br /> D2031 PATIENT STATION 6 NA 7.9 150 150 0
<br /> D2032 PATIENT STATION 6 NA 7.6 150 150 0
<br /> D2033 PATIENT STATION 6 NA 8.6 150 150 0
<br /> D2034 NURSE STATION 4 NA 32.0 300 700 -400
<br /> D2035 PATIENT STATION 6 NA 8.6 150 150 0
<br /> D2036 PATIENT STATION 6 NA 8.1 150 150 0 . A
<br /> ,,,, 11,
<br /> 02037 PATIENT STATION 6 NA 8.5 210 210 0
<br /> aj i!
<br /> 6 NA 8.8 210 210 0
<br /> 02038 PATIENT STATION 1 d if
<br /> 02041 PATIENT STATION 6 NA 6.6 210 210 0
<br /> V,
<br /> D2042 IDF ROOM 0 NA 2.4 50 0 50 DEDICATED FCU-202
<br /> D2043 ELECT 0 NA 9.5 0 50 -50
<br /> D2053 PATIENT STATION 6 NA 7.6 135 135 0
<br /> D2054 PATIENT TOILET 10 N 10.1 0 80 -80
<br /> Date: NOVEMBER 03,2008
<br /> D2055 PATIENT STATION 6 NA 7.8 135 135 0
<br /> lob No: S80613.01
<br /> D2057 PATIENT STATION 6 NA 7.7 135 135 0
<br /> Drawn By: CDi
<br /> D2058 PATIENT STATION 6 NA 7.7 135 135
<br /> D2105 NOURISH 2 N 38.9 150 700 -550 Checked By: Fl
<br /> D2062 PATIENT STATION 6 NA 7.6 135 135 0
<br /> Drawing No.
<br /> D2063 PATIENT STATION 6 NA 7.8 135 135 0
<br /> D2104 MEDS / CGS 4 P 7.0 150 0 150
<br /> D2078 PATIENT STATION 6 NA 7.8 135 135 0
<br /> D2082 PATIENT STATION 6 NA 6.7 135 135 0
<br /> D2085 PATIENT STATION 6 NA 7.8 135 135 0 M 0
<br /> •
<br /> 23
<br /> D2087 PATIENT STATION 6 NA 7.5 135 135 0
<br /> D2091 PATIENT STATION 6 NA 7.4 135 135 0
<br /> D2092 PATIENT STATION 6 NA 7.8 135 135 0
<br /> 1700 13th St-PGMC 2"Floor Surgery-B1406-017
<br />
|