_LEVEL 2 AIR TERMINAL UNITSa)
<br /> MARK TU-2A01 TU-2A02 TU-2A03 A TU-2A04 TU-2A05 TU-2A06 TU-2A07 A TU-2A08 TU-2A09 TU-2A10 TU-2A11 TU-2B01 TU-2B02 TU-2B03 TU-2804 TU-2B05 TU-2B06 TU-2B07 TU-2B08 TU-2B09 TU-2610 TU-2B11 TU-2B12 TU-2B13 TU-2614
<br /> LOCATION LEVEL 2 LEVEL 2 LEVEL 2 NOT USED NOT USED LEVEL 2 LEVEL 2 NOT USED _ LEVEL 2 NOT USED LEVEL 2 NOT USED LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 W 2
<br /> SERVES PEDS PLAY CONSULT RM SS CONTROL PATIENT/ NS OFFICE PATIENT STA ISO CONSULT RM ELEC ROOM SURG WAIT SURG WAIT CORRIDOR OFFICES PATIENT STA CONTROL STA SUPER/ MGRS CONSULT RM ELEV LOBBY OFFICES ELEC ROOMU U
<br /> CAPACITY AIRFLOW: CFM 620 515 300 900 300 405 250 915 450 1300 1750 1000 780 150 750 540 550 1100 900 450
<br /> MAX AIR PD: IN WG 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
<br /> Z ---'M
<br /> UNIT INLET COLLAR: IN. [5] 10 8 6 10 6 6 12 10 6 12 14 10 10 5 10 8 8 12 10 8 ki
<br /> BRANCH INLET: IN. [6] 12 10 8 12 8 8 12 12 8 14 16 12 12 8 12 10 10 14 12 10 ILI ---ID
<br /> OUTLET W x H IN. 14x12.5 12x10 12x8 14x12.5 _ 12x8 _ 12x8 12 14x12.5 12x8 16x15 20x17.5 14x12.5 _ 14x12.5 12x8 14x12.5 12x10 12x10 16x15 14x12.5 12x10 0 „s„„„W
<br /> NOISE CRITERIA NC: RADIATED 28 25 25 28 25 25 20 28 25 27 28 28 28 25 28 25 25 27 28 25
<br /> NC: DISCHARGE 23 25 22 23 22 22 39 23 22 24 21 23 23 22 23 25 25 24 23 25
<br /> HEATING COIL MBH 20.1 16.7 8.1 34.0 9.7 13.1 7.3 24.7 - 42.1 56.7 27.0 21.1 4.1 20.3 17.5 17.8 29.7 29.2 -
<br /> MINIMUM ROWS 2 2 1 2 2 1 2 1 - 2 2 1 1 1 1 1 1 1 2
<br /> EAT: DEG F 55 55 55 55 55 55 55 55 - 55 55 55 55 55 55 55 55 55 55 -
<br /> LAT: DEG F 85 85 80 90 85 85 82 80 - _ 85 85 80 80 80 80 85 85 80 85 -
<br /> _ ,
<br /> EWT: DEC F [7] 180 180 180 180 180 180 180 180 - 180 180 180 180 180 180 180 180 180 180 t,': W=
<br /> LWT: DEG F [7] 150 150 150 160 150 ^ 160 150 150 - 150 150 150 150 150 150 150 150 150 150 '' a) '- :', ce LIJ
<br /> FLOW : GPM 1.5 1.5 1.0 3.5 1.0 J2\ 1.5 0.5 2.0 3.0 4.0 2.0 1.5 0.5 1.5 1.5 1.5 2.0 2.0
<br /> MAX. WATER PD: FT 2 2 2 2 2 2 2 2 - 2 2 2 2 2 2 2 2 2 2 -
<br /> 3/8 2378
<br /> 23
<br /> 7 8 48 23 7 8 23
<br /> 7/8 2378 2
<br /> 378 2378 2378
<br /> 7/823 7 8 26 /
<br /> 23 /
<br /> 23 7 8 /
<br /> 48 28 /
<br /> 48 23 7 8 /
<br /> /
<br /> 23 7 8
<br /> 2378
<br /> 48 /
<br /> /
<br /> SIZE LENGTH MAX /
<br /> 4
<br /> WIDTH, MAX 20 1/2 18 1/2 18 1/2 20 1/2 18 1/2 18 1/2 14 20 1/2 18 1/2 22 1/2 26 1/2 20 1/2 20 1/2 18 1/2 20 1/2 18 1/2 18 1/2 22 1/2 20 1/2 18 1/2
<br /> HEIGHT, MAX 12 1/2 12 1/4 12 1/4 12 1/2 12 1/4 _ 12 1/4 12 12 1/2 12 1/4 15 17 1/2 12 1/2 12 1/2 12 1/4 12 1/2 12 1/4 12 1/4 15 12 1/2 12 1/4
<br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS TITUS _ TITUS PHOENIX TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS
<br /> MODEL DESV DESV DESV DESV DESV DESV CWA-112L DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV
<br /> NOTES [1, 2, 3] [1, 2, 3] [1, 2, 3] [1,2,3,4] [1, 2, 3] [1,2,3,4] [,_1, 2, 3,10,11,12] [1, 2, 3] [1, 2] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3, 4] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2] EVERETT,WASHINGTON
<br /> MARK TU-2C01 TU-2CO2 TU-2CO3 TU-2C04 TU-2C05 TU-2C06 TU-2C07 TU-2C08 TU-2C09 TU-2C10 TU-2C11 TU-2C12 TU-2D01 TU-2D02 TU-2D03 TU-2D04 TU-2D05 TU-2D06 TU-2D07 TU-2D08 TU-2D09 TU-2D10 TU-2D11 Q TU-2D12 TU-2D13
<br /> LOCATION LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 _ LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 NOT USED NOT USED NOT USED NOT USED NOT USED LEVEL 2 LEVEL 2 NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED GU NS'O,
<br /> SERVES EQUIP STOR RESOURCE BIO MED DICTATION CLINICAL DIR MED DIRECT CORRIDOR ADMIN ASST STAFF LNGE CONF EDU PHYS LNGE SUPP CORE PATIENT STA PATIENT STA (c/S-' ,zG F�.
<br /> CAPACITY AIRFLOW: CFM 1300 800 705 990 230 855 700 750 1700 800 780 1200 405 900
<br /> MAX. AIR PD: IN WG 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 N.5 0.5 0.5
<br /> r
<br /> /1
<br /> ,,
<br /> UNIT INLET COLLAR: IN. [5] 12 10 10 10 5 10 8 10 14 10 10 10 6 10 /1\ \ N
<br /> BRANCH INLET: IN. [6] 14 12 12 12 8 12 10 12 16 12 12 12 8 12
<br /> OUTLET W x H IN. 16x15 14x12.5 14x12.5 14x12.5 _ 12x8 14x12.5 12x10 14x12.5 20x17.5 14x12.5 14x12.5 14x12.5 12x8 14x12.5 77' ,<
<br /> NOISE CRITERIA NC: RADIATED 27 28 28 28 25 28 25 _ 28 28 _ 28 28 _ 28 _ 25 _ 28 eh'/TEC')
<br /> NC: DISCHARGE 24 23 23 23 22 23 25 23 21 23 23 23 22 23
<br /> HEATING COIL MBH 42.1 21.6 19.0 26.7 7.5 27.7 18.9 20.3 45.9 25.9 25.3 38.9 13.1 34.0 Architecture/Planning/Interior Design
<br /> MINIMUM ROWS 2 1 1 1 1 2 1 1 1 2 2 2 1 2 Portland Seattle Los Angeles Washington DC
<br /> EAT: DEG F 55 55 55 55 55 55 55 55 55 55 55 55 55 55
<br /> LAT: DEG F 85 80 80 80 85 85 80 80 80 85 85 85 85 90 925 Fourth Ave.,Suite 2400
<br /> EWT: DEG F [7] 180 180 180 180 180 180 180 180 180 180 180 180 ' 180 180 Seattle,Washington 98104 .
<br /> 160 160
<br /> LWT: DEC F [7] 150 150 150 150 150 150 150 150 150 150 150 150 (PH)206 623 9414
<br /> FLOW : GPM 3.0 1.5 1.5 2.0 0.5 2.0 1.5 1.5 3.5 _ 2.0 2.0 3.0 1.5 3.5 (FAX)206 623 7868
<br /> MAX. WATER PD: FT 2 2 2 2 2 2 2 2 2 2 T 2 2 2 2
<br /> SIZE LENGTH, MAX 23 7/8 23 7/8 23 7/8 23 7/8 23 7/8 23 7/8 23 7/8 23 7/8 26 3/8 23 7/8 23 7/8 23 7/8 48 48
<br /> WIDTH, MAX 22 1/2 20 1/2 20 1/2 20 1/2 18 1/2 20 1/2 18 1/2 20 1/2 26 1/2 20 1/2 20 1/2 20 1/2 18 1/2 20 1/2 Consultants
<br /> HEIGHT, MAX 15 12 1/2 12 1/2 12 1/2 12 1/4 12 1/2 12 1/4 12 1/2 17 1/2 12 1/2 12 1/2 12 1/2 12 1/4 12 1/2 LIFE SAFETY
<br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS ROLF JENSEN &ASSOCIATES
<br /> MODEL DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV DESV 19125 North Creek Parkway Suite 120
<br /> NOTES [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1,2,3,4] i2 1,2,3,4,13] Bothell,Washington 98011
<br /> MARK TU-2D14 TU-2D15 TU-2D16 TU-2D17 TU-2D18 TU-2D19 TU-2D20 TU-2D21 TU-2D22 TU-2D23 TU-2D24 TU-2D25 TU-2D26 TU-2D27 TU-2D28 TU-2D29 TU-2D30 TU-2D31 I TU-2E01 I TU-2E02 TU-2E03 TU-2E04 TU-2E05 TU-2E06 TU-2E07
<br /> LOCATION NOT USED NOT USED LEVEL 2 A
<br /> NOT USED LEVEL 2 NOT USED NOT USED LEVEL 2 NOT USED LEVEL 2 NOT USED LEVEL 2 NOT USED LEVEL 2 LEVEL 2 NOT USED LEVEL 2 NOT USED LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 LEVEL 2 CIVIL ENGINEER
<br /> SERVES CORRIDOR _ CORRIDOR _ PATIENT STA EQUIP PATIENT STA CORRIDOR PATIENT STA ISO WEST PACU EAST PACU CORRIDOR BREAK ROOM OFFICE DICTATION PATIENT STA Magnusson Klemencic Associates
<br /> 1301 Fifth Avenue,Suite 3200
<br /> CAPACITY AIRFLOW: CFM //�� 1400 1000 540 500 405 1050 405 300 2040 2040 500 800 595 530 150 Seattle,Washington 98101-2699
<br /> MAX. AIR PD: IN WG /2\ 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
<br /> UNIT INLET COLLAR: IN. [5] 14 10 8 8 6 10 6 12 16 16 8 10 8 8 5 LANDSCAPE ARCHITECT
<br /> BRANCH INLET: IN. [6] 16 12 10 10 8 12 8 12 18 18 10 12 10 10 8 Site Workshop
<br /> OUTLET W x H IN. 20x17.5 14x12.5 12x10 12x10 12x8 _ 14x12.5 12x8 12 24x18 24x18 12x10 14x12.5 12x10 12x10 12x8 927 Post Alley
<br /> NOISE CRITERIA NC: RADIATED 28 28 25 25 25 28 25 20 26 26 25 28 25 25 25 Seattle,Washington 98101
<br /> NC: DISCHARGE 21 23 25 25 22 23 22 39 22 22 25 23 25 25 22 STRUCTURAL ENGINEER
<br /> HEATING COIL MBH 37.8 27.0 17.5 13.5 13.1 28.4 13.1 11.3 55.1 55.1 13.5 25.9 19.3 14.3 4.05 Magnusson Klemencic Associates
<br /> MINIMUM ROWS 1 1 1 1 1 1 1 2 2 2 1 2 2 1 1 1301 Fifth Avenue,Suite 3200 •
<br /> r EAT: DEG F 55 55 55 55 55 55 55 55 55 _ 55 55 55 55 55 55 Seattle,Washington 98101-2699
<br /> LAT: DEG F 80 80 85 80 85 80 85 90 80 80 80 85 85 80 80
<br /> EWT: DEC F [7] 180 180 180 180 180 180 180 180 180 180 180 180 180 180 180
<br /> MECHANICAL ENGINEER
<br /> LWT: DEG F [7] 150 150 160 150 160 150 160 150 150 150 150 150 150 150 150 CDi Engineers r:
<br /> FLOW GPM 3.0 2.0 2.0 1.0 1.5 2.0 1.5 1.0 4.0 4.0 1.0 2.0 1.5 1.0 0.5 19203 36th Ave.W,Suite 200
<br /> Lynnwood,Washington 98036
<br /> MAX. WATER PD: FT 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
<br /> SIZE LENGTH, MAX 26 3/8 23 7/8 48 23 7/8 48 23 7/8 48 28 26 3/8 26 3/8 23 7/8 23 7/8 23 7/8 23 7/8 48 ELECTRICAL ENGINEER k'
<br /> WIDTH, MAX 26 1/2 20 1/2 18 1/2 18 1/2 18 1/2 20 1/2 18 1/2 14 30 1/2 30 1/2 18 1/2 20 1/2 18 1/2 18 1/2 18 1/2 SPARLING
<br /> HEIGHT, MAX 17 1/2 12 1/2 12 1/4 _ 12 1/4 12 1/4 12 1/2 12 1/4 12 18 18 12 1/4 12 1/2 12 1/4 12 1/4 12 1/4 720 Olive Way,Suite 1400
<br /> Seattle,Washington 98101-1853
<br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS TITUS TITUS TITUS PHOENIX TITUS TITUS TITUS TITUS TITUS TITUS TITUS
<br /> MODEL DESV DESV DESV DESV DESV DESV DESV CWA-112L DESV DESV DESV DESV DESV DESV DESV E
<br /> GENERAL CONTRACTOR
<br /> NOTES [1, 2, 3] [1, 2, 3] [1,2,3,4] [1, 2, 3] [1,2,3,4] [1, 2, 3, 14] [1,2,3,4,15] [1, 2, 3,10,11,12] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3, 4] M.A. Mortenson Company
<br /> MARK TU-2F01 TU-2F02 TU-2F03 TU-2F04 TU-2F05 TU-2F06 TU-2F07 14719 N.E.29th Place
<br /> LOCATION LEVEL 2 LEVEL 2 LEVEL 2 NOT USED LEVEL 2 LEVEL 2 LEVEL 2 �_ / \ Bellevue,Washington 98007
<br /> CORRIDOR CLEAN CORRIDOR (FUT. CL CORE) ANESTH WK CORRIDOR CORRIDOR '-
<br /> SERVES _
<br /> CAPACITY AIRFLOW: CFM 750 1200 1000 1230 1700 750
<br /> MAX. AIR PD: IN WG 0.5 0.5 0.5 0.5 0.5 0.5 Revisions
<br /> UNIT INLET COLLAR: IN. [5] 10 12 10 12 14 10
<br /> BRANCH INLET: IN. [6] 12 14 12 14 16 12
<br /> DOCUMENT RELEASE 09 11/03/08
<br /> OUTLET W x H IN. 14x12.5 16x15 14x12.5 16x15 20x17.5 14x12.5
<br /> NOISE CRITERIA NC: RADIATED 28 27 28 27 28 28 DOCUMENT RELEASE 11 02/09/09
<br /> NC: DISCHARGE 23 24 23 24 21 23
<br /> HEATING COIL MBH 20.3 38.9 27.0 39.9 45.9 20.3 DOCUMENT RELEASE 13 03/09/09
<br /> MINIMUM ROWS 1 2 1 2 1 1 /I\ DR 17 ADDENDUM 4 05/15/09
<br /> EAT: DEG F 55 55 55 55 55 55 A DOCUMENT RELEASE 21 09/14/09
<br /> LAT: DEG F 80 85 80 85 80 80
<br /> EWT: DEG F [7] 180 180 180 180 180 180 / \ WCP 27.16 R1 PYXIS REVISION 03/31/11
<br /> LWT: DEG F [7] 150 150 150 150 150 150
<br /> A WORK CHANGE PROPOSAL 145 06/02/14
<br /> FLOW : GPM 1.5 3.0 2.0 3.0 3.5 1.5
<br /> MAX. WATER PD: FT 2 2 2 2 2 2
<br /> SIZE LENGTH, MAX 23 7/8 23 7/8 23 7/8 23 7/8 26 3/8 23 7/8
<br /> WIDTH, MAX 20 1/2 22 1/2 20 1/2 22 1/2 26 1/2 20 1/2
<br /> HEIGHT, MAX 12 1/2 15 12 1/2 15 17 1/2 12 1/2
<br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS TITUS TITUS
<br /> MODEL DESV DESV DESV DESV DESV DESV
<br /> NOTES [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3] [1, 2, 3, 8] [1, 2, 3]
<br /> NOTES:
<br /> 1. DUCT SIZE DOWNSTREAM OF TERMINAL UNIT SHALL BE SAME SIZE AS UNIT OUTLET UNLESS NOTED OTHERWISE ON DRAWINGS. 4
<br /> CLOSEOUT PRINTING 04/01/12
<br /> 2. NC VALUES CALCULATED USING MODELING ASSUMPTIONS BASED ON ARI 880-98, 1.0" SPD FROM INLET TO DISCHARGE OF TU.
<br /> 3. PIPE CONNECTION SIZES: 3/4" 3 GPM MAX, 1" 6.5 GPM MAX, 1 1/4" 12 GPM MAX.
<br /> 4. INTEGRAL SOUND ATTENUATOR BETWEEN TU VALVE AND HEATING COIL BY MANUFACTURER.
<br /> 5. PROVIDE DUCT EXTENSION AT INLET SAME SIZE AS INLET COLLAR FOR LENGTH OF 2 DUCT DIAMETERS.
<br /> Drawing Title
<br /> 6. PROVIDE DUCT TRANSITION FROM BRANCH INLET DUCT TO UNIT CONNECTING COLLAR EXTENSION, 15 DEGREE MAXIMUM TRANSITION ANGLE.
<br /> 7. HEATING COIL FLUID IS WATER. EQUIPMENT SCHEDULES
<br /> 8. SET FOR 900 CFM.
<br /> 9. SERVES FUTURE SHELLED SPACE. SHOWN FOR INFORMATION ONLY.
<br /> 10.PROVIDE DUCT HEATING COIL 20" DOWNSTREAM OF AIR VALVE MAXIMUM AIR VELOCITY 700 FEET PER MINUTE.
<br /> 11.PROVIDE FACTORY MOUNTED PRESSURE SWITCH FOR ALARM TO DDC WHEN AIR VALVE IS OUTSIDE ACCEPTABLE PRESSURE RANGE.
<br /> 12.WRAP AIR VALVE UNIT WITH ACOUSTIC INSULATION AS SPECIFIED.
<br /> 13.SET INITIAL TU SETTING FOR 525 CFM.
<br /> 14.SET INITIAL TU SETTING FOR 700 CFM.
<br /> T k I - gm F.: F„
<br /> 16.PROVIDE COMPLETE DDC CONTROLS FO ACH TERMINAL UNIT TO MATCH EXISTING TERMINAL UNIT CONTROLS AND TIE INTO EXISTING 4
<br /> DDC SYSTEM. UPDATE SYSTEM GRAPHICS AS REQUIRED. ,., �'# iip Al
<br /> jee,,,,,,,,.., ,..„0„
<br /> 414, 4,00,'
<br /> ,„„„,,ty
<br /> t6.ON , .,
<br /> 1.'.
<br /> Date: NOVEMBER 03,2008
<br /> Job No: 580613.01
<br /> Drawn By: CDi
<br /> Checked By: FJ
<br /> Drawing No.
<br /> 1 3
<br /> MO.13
<br /> 1700 13th St-PGMC 2 °Floor Surgery-B1406-017
<br />
|