Laserfiche WebLink
DESIGN CRITERIA: STRUCTURAL STEEL NOTES: SYMBOLS: <br /> 1. THE STRUCTURAL DESIGN OF THIS PROJECT IS IN ACCORDANCE WITH THE 1. SHOP DRAWINGS FOR STRUCTURAL STEEL SHALL BE SUBMITTED TO THE <br /> INTERNATIONAL BUILDING CODE 2009 WITH WASHINGTON STATE BUILDING CONSULTANT FOR REVIEW PRIOR TO FABRICATION. ,. GRID REFERENCE --: at&t <br /> CODE AMENDMENTS (2009 SBC) _ <br /> 2. STRUCTURAL STEEL DESIGN, FABRICATION AND ERECTION (INCLUDING FIELD (AS PER ACCIDENT PREVENTION PROGRAM BY PERMISSION OF WREN <br /> 2. DESIGN LOADS: WELDING, HIGH STRENGTH FIELD BOLTING, EXPANSION BOLTS, AND THREADED CONSTRUCTION, INC. - 03/01/99) i' 'x\'1 DETAIL REFERENCE Your World. Delivered. <br /> DESIGN DATA FOR EVERETT, WA 98201 EXPANSION ANCHORS) SHALL BE BASED ON THE A.I.S.C. "SPECIFICATION FOR q,---%' <br /> THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR FALL PROTECTION METHODS AND EQUIPMENT <br /> -ROOF SNOW LOAD N/A (NOT A ROOFTOP SOLUTION) BUILDINGS" LATEST EDITION. SUPERVISION SHALL BE IN ACCORDANCE WITH <br /> ROOF TOP INSTALLATIONS r <br /> 2006 IBC CHAPTER 22, BY A QUALIFIED TESTING AGENCY DESIGNATED BY THE , �1 ELEVATION REFERENCE �„ <br /> -BASIC WIND SPEED 85 MPH (100 MPH 3 SECOND GUSTS) CONSULTANT. THE CONSULTANT SHALL BE FURNISHED WITH A COPY OF ALL 1. FOR WORK IS BEING PERFORMED WITHIN 25' OF AN UNPROTECTED ROOF �,__Y, <br /> INSPECTION REPORTS AND TEST RESULTS. EDGE, THE CONSTRUCTION SUPERVISOR SHALL DESIGNATE A TRAINED r�, <br /> -WIND EXPOSURE C SAFETY MONITOR TO OBSERVE THE MOVEMENTS AND ACTIVITIES OF THEa. <br /> f <br /> 3. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING REQUIREMENTS: CONSTRUCTION WORKERS. �` SECTION REFERENCE <br /> -SEISMIC ZONE D <br /> TYPE OF MEMBER 2. SAFETY MONITOR SHALL WARN CONSTRUCTION WORKERS OF HAZARDS (I.E., <br /> BACKING UP TOWARD A ROOF EDGE, ETC.) OR UNSAFE ACTIVITIES. THE ,,,,....r, <br /> CENTERLINE <br /> SAFETY MONITOR MUST BE ON THE SAME ROOF AND WITHIN VISUAL AND <br /> A. PLATES, SHAPES, ANGLES, AND RODS -- -- --- <br /> CONCRETE NOTES: B. SPECIAL SHAPES AND PLATES ASTM ASTM A36, FFy36 KSI <br /> KSl VERBAL DISTANCE OF THE CONSTRUCTION WORKERS. PROPERTY/LEASE LINE <br /> C. PIPE COLUMNS <br /> 1. ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH ACI-318. D. STRUCTURAL TUBING ASTM A53 Fy 35 KSI 3. CONSTRUCTION INVOLVING WORKERS TO APPROACH WITHIN 6' OR LESS ofPACIFIC TELECOM SERVICES, <br /> E. ANCHOR BOLTS ASTM A500, Fy 46 KSI AN UNPROTECTED ROOF EDGE, REQUIRES WORKERS TO USE SAFETY LINE. -- MATCH LINE <br /> 2. CONCRETE SHALL BE MIXED PROPORTIONED CONVEYED AND PLACED IN F. CONNECTION BOLTS ASTM A307 LLC <br /> ACCORDANCE WITH CHAPTER 19 OF THE 2009 IBC. STRENGTHS AT 28 DAYS ASTM A325 TWIST-OFF-TYPE 4. SAFETY LINE SHALL BE MINIMUM 1" DIAMETER NYLON, WITH A NOMINAL <br /> AND MIX CRITERIA SHALL BE AS FOLLOWS. 4. ALL MATERIAL TO BE HOT DIPPED GALVANIZED AFTER FABRICATION PER TENSILE STRENGTH OF 5400 LBS. - - - WORK POINT <br /> A123/A123M-00. <br /> TYPE OF CONSTRUCTION 28 DAY STRENGTHS W/C MINIMUM CEMENT 5. SAFETY LINE SHALL BE ATTACHED TO A SUBSTANTIAL MEMBER OF THE GROUND CONDUCTOR <br /> RATIO CONTENT 5. ALL WELDING SHALL BE IN CONFORMANCE WITH A.I.S.C. AND AWS STANDARDS STRUCTURE. <br /> A. (f�) PER CUBIC YARD AND SHALL BE PERFORMED BY W.A.B.O. CERTIFIED WELDERS USING E70 XX ------- <br /> SLABS ON GRADE 6. SAFETY LINE LENGTH SHALL BE SET ALLOWING CONSTRUCTION WORKER TO - TELEPHONE CONDUIT <br /> TOPPING SLABS ELECTRODES. ONLY PREQUALIFIED WELDS (AS DEFINED BY AWS) SHALL BE <br /> CONCRETE PIERS 2,400 PSI <.45 5 Y2 SACKS USED. WELDING OF GRADE 60 REINFORCING BARS (IF REQUIRED) SHALL BE REACH EDGE OF ROOF, BUT NOT BEYOND. <br /> L ELECTRICAL CONDUIT <br /> PERFORMED USING LOW HYDROGEN ELECTRODES. WELDING OF GRADE 40 8828 REGISTERED <br /> B. ALL STRUCTURAL CONCRETE 4,000 PSI _.45 6 Y2 SACKS REINFORCING BARSIF REQUIRED) SHALL BE PERFORMED USING E70 XX 7. SAFETY BELTS SHALL BE WORN BY ALL CONSTRUCTION WORKERS. <br /> A COAXIAL CABLE 7 r ARCHITECT <br /> ( -- <br /> EXCEPT WALLS ELECTRODES. WELDING WITHIN 4" OF COLD BENDS IN REINFORCING STEEL IS / <br /> rj,'H <br /> 8. MONTHLY SAFETY INSPECTION AND MAINTENANCE OF THE FALL PROTECTION <br /> NOT PERMITTED. SEE REINFORCING NOTE FOR MATERIAL REQUIREMENTS OF EQUIPMENT SHALL OCCUR BY THE SAFETY COMMITTEE REPRESENTATIVES, OVERHEAD SERVICE I <br /> , <br /> C CONCRETE WALLS 4,000 PSI <.45 6 Y2 SACKS WELDED BARS. -INCLUDING: CONDUCTORS B.HALL <br /> CEMENT SHALL BE ASTM C150, PORTLAND CEMENT TYPE II U.N.O. 6. COLD-FORMED STEEL FRAMING MEMBERS SHALL BE OF THE SHAPE, SIZE, AND \ ATE OF WASHINGTON <br /> INSPECTION OF CONSTRUCTION AREA FOR HAZARDS E'.._______. ,-=.] GROUT OR PLASTER <br /> 3. THE GENERAL CONTRACTOR SHALL SUPERVISE AND BE RESPONSIBLE FOR THE GAGE SHOWN ON THE PLANS. PROVIDE MINIMUM SECTION PROPERTIES USE OF AN INSPECTION CHECKLIST EXPIRATION DATE OF THE <br /> METHODS AND PROCEDURES OF CONCRETE PLACEMENT. INDICATED. ALL COLD-FORMED STEEL FRAMING SHALL CONFORM TO THE A.I.S.S. INTERVIEWING COWORKERS REGARDING SAFETY CONCERNS 08/20/13 <br /> "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL REPORTING AND DOCUMENTING ANY HAZARDS I_;_._Lr_ L7 ,_L.,....4 _1 (E) BRICK <br /> 4. ALL CONCRETE WITH SURFACES EXPOSED TO STANDING WATER SHALL BE MEMBERS." REPORTING HAZARDS TO THE SAFETY COMMITTEE FOR CONSIDERATION <br /> AIR-ENTRAINED WITH AN AIR-ENTRAINING AGENT CONFORMING TO ASTM C260, POSTING RESULTS OF INSPECTION AND ANY ACTION TAKEN Ll'c/z.z/z/../I OIcs (E) MASONRY <br /> C494, C618, C989 AND C1017. TOTAL AIR CONTENT SHALL BE IN 7. BOLTED CONNECTIONS SHALL USE BEARING TYPE ASTM A325 BOLTS (3/4" DIA.) RECEIVING AN UNBIASED REVIEW OF ONE'S OWN WORK AREA BY ANOTHER <br /> ACCORDANCE WITH TABLE 1904.2.1 OF THE 2009 IBC. <br /> AND SHALL HAVE A MINIMUM OF TWO BOLTS UNLESS NOTED OTHERWISE. COWORKER SAFETY REPRESENTATIVE 11 •. ' , :' ,- 1 CONCRETE <br /> 5. REINFORCING STEEL SHALL CONFORM TO ASTM A615 (INCLUDING SUPPLEMENT 8. NON-STRUCTURAL CONNECTIONS FOR STEEL GRATING MAY USE 5/8" DIA. ASTM REFER TO ROOFTOP WORK AREA SAFETY PROTOCOL I 1:=I i-11 I <br /> / � 11 >LLL 1 1 1 111 EARTH <br /> 51), GRADE 60, fy=60,000 PSI. EXCEPTIONS: ANY BARS SPECIFICALLY SO A307 BOLTS UNLESS NOTED OTHERWISE. NATIONAL ASSOCIATION OF TOWER ERECTORS 2000 PUBLICATION <br /> NOTED ON THE DRAWINGS SHALL BE GRADE 40, fy=40,000 PSI. GRADE 60 <br /> • ,.;0<>..<; : GRAVEL <br /> REINFORCING BARS INDICATED ON DRAWINGS TO BE WELDED SHALL CONFORM 9. ALL STEEL WORK SHALL BE PAINTED IN ACCORDANCE WITH THE DESIGN & REFERENCED OSHA REGULATION/STANDARDS SHALL BE REVIEWED BY TOWER tet, .,., <br /> TO ASTM A706. REINFORCING COMPLYING WITH ASTM A615(S1) MAY BE CONSTRUCTION SPECIFICATION AND IN ACCORDANCE WITH ASTM A36 UNLESS ERECTORS, <br /> WELDED WELDED ONLY IF MATERIAL PROPERTY REPORTS INDICATING CONFORMANCE WITH NOTED OTHERWISE. EQUIPMENT INSTALLERS, AND TOWER/ROOF TOP CONTRACTORS/SUBCONTRACTORS <br /> WELDING PROCEDURES SPECIFIED IN A.W.S. D14 ARE SUBMITTED. 29 CFR 1926.500 - SCOPE, APPLICATION, AND DEFINITIONS <br /> 10. ALL WELDS TO BE 1/4" FILLET UNLESS NOTED OTHERWISE. 29 CFR 1926.501 - DUTY TO HAVE FALL PROTECTION I - -.1 SAND <br /> 6. REINFORCING STEEL SHALL BE DETAILED (INCLUDING HOOKS AND BENDS) IN 19 CFR 1926.502 - FALL PROTECTION SYSTEMS CRITERIA AND <br /> ACCORDANCE WITH AC1 315 AND 318. LAP ALL CONTINUOUS REINFORCEMENT 11. TOUCH UP ALL FIELD DRILLING AND WELDING WITH 2 COATS OF GALVACON (ZINC PRACTICES L;;>-<.1] WOOD CONTINUOUS <br /> AT LEAST 30 BAR DIAMETERS OR A MINIMUM OF 2'-0". PROVIDE CORNER RICH PAINT) OR APPROVED EQUAL. <br /> BARS AT ALL WALL AND FOOTING INTERSECTIONS. LAP CORNER BARS AT __] WOOD BLOCKING <br /> LEAST 30 BAR DIAMETERS OR A MINIMUM OF 2'-0". LAP ADJACENT MATS OF <br /> WELDED WIRE FABRIC A MINIMUM OF 8" AT SIDES AND ENDS. TOWER/POLE NOTES: I--tz.:_%llll lrizZJ STEEL <br /> 7. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. 1• VERIFICATION THAT THE EXISTING TOWER/POLE CAN SUPPORT THE PROPOSED <br /> ANTENNA LOADING IS TO BE DONE BY OTHERS. <br /> ;:N) NEW <br /> 8. SPIRAL REINFORCEMENT SHALL BE PLAIN WIRE CONFORMING TO ASTM A615, . w O <br /> GRADE 60, fy-60,000 PSI. 2. PROVIDE SUPPORTS FOR THE ANTENNA COAX CABLES TO THE ELEVATION OF ALL (E, EXISTING > N <br /> INITIAL AND FUTURE ANTENNAS. ANTENNA COAX CABLES ARE TO BE SUPPORTED ( T "Tl Qcp <br /> 9. NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL BE FIELD BENT AND RESTRAINED AT THE CENTERS SUITABLE TO THE MANUFACTURER'S i NEW ANTENNA lid O m CI UNLESS SPECIFICALLY SO DETAILED OR APPROVED BY THE CONSULTANT. REQUIREMENTS. <br /> '..01, EXISTING ANTENNA O <br /> 10. CONCRETE PROTECTION (COVER) FOR REINFORCING STEEL SHALL BE AS 0 ,- <br /> FOLLOWS: f- GROUND ROD [..i. 10 j <br /> - FOOTINGS AND OTHER UNFORMED 3" <br /> SURFACES, EARTH FACE r� GROUND BUS BAR N j <br /> w <br /> - FORMED SURFACES EXPOSED (#6 BARS OR LARGER) 2" 0 MECHANICAL GRND. CONN. <br /> L..1... <br /> TO EARTH OR WEATHER (#5 BARS OR SMALLER) 1 1/2" <br /> B CADWELD <br /> - SLABS AND WALLS (INTERIOR FACE) 3/4" <br /> 11. BARS SHALL BE SUPPORTED ON CHAIRS OR DOBIE BRICKS. [(..._ GROUND ACCESS WELL <br /> 12. ANCHOR BOLTS TO CONFORM TO ASTM A307. '....E ELECTRIC BOX <br /> 13. NON-SHRINK GROUT SHALL BE FURNISHED BY AN APPROVED MANUFACTURER <br /> AND SHALL BE MIXED AND PLACED IN STRICT ACCORDANCE WITH THE TELEPHONE BOX <br /> MANUFACTURER'S PUBLISHED RECOMMENDATIONS. GROUT STRENGTH SHALL BE <br /> AT LEAST EQUAL TO THE MATERIAL ON WHICH IT IS PLACED (3,000 PSI , -. LIGHT POLE <br /> MINIMUM). <br /> 14. ALL EXPANSION ANCHORS TO BE HILTI BRAND. ADHESIVE ANCHORS REQUIRE C) FND. MONUMENT <br /> TESTING TO CONFIRM CAPACITY UNLESS WAIVED BY ENGINEER. <br /> !Si SPOT ELEVATION <br /> SET POINT REVISIONS <br /> NO. DATE DESCRIPTION INITIAL <br /> A 02/24/12 ISSUED FOR PCD REVIEW TB <br /> /r,\ REVISION 0 03/19/12 ISSUED FOR FINAL CONSTRUCTION WJR <br /> 1 04/19/12 REVISED FOR FINAL CONSTRUCTION WJR <br /> 2 04/24/12 REVISED FOR FINAL CONSTRUCTION AF <br /> 3 05/14/12 REVISED FOR FINAL CONSTRUCTION PHD <br /> 4 09/11/12 ISSUED FOR FINAL CONSTRUCTION SS <br /> SPECIAL INSPECTIONS REQUIRED: 5 09/18/12 SUBMITTAL SET PHD <br /> SOILS COMPLIANCE PRIOR TO FOUNDATION INSPECTION ❑ VERIFICATIONS OF MILL REPORT ❑ SPRAYED -ON- FIREPROOFING <br /> CONCRETE OVER 2400 PSI (5Y2 SACK MIX) AT 28 DAYS ❑ IDENTIFICATION OF STEEL AND AT JOB SITE ❑ STRUCTURAL MASONRY <br /> CONCRETE PLACEMENT AT SLAB ON GRADE NOT FOR CONSTRUCTION UNLESS <br /> WRITTEN CERTIFICATION FOR PROPER PLACEMENT OF 111 ADHESIVE BOLTS IN CONCRETE OR MASONRY ❑ PRESTRESSED CONCRETE LABELED AS CONSTRUCTION SET <br /> REINFORCEMENTS AT SLAB ON GRADE <br /> ❑ ALL FIELD WELDING <br /> FOUNDATION EXCAVATION AND FILL INCLUDING UTILITY TRENCHES ❑ ANCHOR BOLTS INSTALLATION AND PLACEMENT IN <br /> CERTIFICATION OF BUILDING PAD, FOUNDATION AND FILL BY CONCRETE ❑ REINFORCING PLACEMENT SHEET TITLE <br /> THE GEOTECHNICAL ENGINEER OF THE RECORD ❑ HIGH STRENGTH BOLTING ❑ DESIGNER SPECIFIED (SEE SHEET#__) GENERAL NOTES <br /> ❑ OTHER <br /> SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE ARCHITECT OR ENGINEER OF RECORD, SHEET NUMBER <br /> WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED <br /> SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND THAT THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH <br /> . THE DESIGN OF THE BUILDING. THE DEFERRED AND SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN AND <br /> 2707 Colby Ave 81209-035 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL. G_2 <br /> THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARRIER SERVICES IS STRICTLY PROHIBITED. <br />