Laserfiche WebLink
0 <br />units in and out if necessary. There wi// be no step� <br />outside this door, It is just /ike it is sho wn on the <br />p/ans. There is a/so a note that sa ys it is an <br />equipment access door': <br />b. The depth of the stair ano landing on the north side of the <br />data center on this permit submittal is almost 3 feet short of <br />the dimension shown on the permit B1107-012. Sheei <br />A2,1 has been updated to reflect the approved p/an <br />for permit 61107-011 and per attached sketch SK- <br />A001, <br />c. The tread depth for the stair east of door 181A should be <br />shown on the drawings as minimum il inches, per IBC <br />section 1009.4.2. This dimension is indicated on <br />attached sketch SK-A001. <br />d. Two feet minimum should be shown on the drawings <br />between the door strike and the landing edge at door 181A, <br />per ICC/ANSI Ai17.1-2003 figure 404.2.3.1 (�. This <br />dimension is indicated on attached skerch SK-A001. <br />e. The walls and doors of the data center are shown as new on <br />this permit, but they were included in permit 61107-012. To <br />be consistent with the note on the drawings for the data <br />center: "No work this area, work done on a separate <br />permiY', please issue a sketch to clarify the revisions <br />required to permit 61107 — 012 and show these revisions as <br />existing on permit B1107 — 022. Afi.er review, we will issue <br />this sketch to the field for inspection_ for 61107 — 012. <br />Wa//s, doors and stairs fo� the Data Center pe�mit <br />61107-012 have been revised and are shown as <br />existing. Attached sketch SK-A001 c/arifes <br />requested revisions for existing pe�mit BI107-011 <br />and rhese changes are shown as existing on p/an fo� <br />perinit 8.1107-022. <br />3. Panic hardware should be shown the door schedule in all rooms of <br />assembly occupancy, and all door s exiting from those areas to the <br />exit access, exit and exit discharge, per IBC sections 1009.1.10. <br />Existing hardware on doors 140A, i408, 140C, and 140D is <br />nan /atching and to remain. Existing hardware on doors <br />1008 and 131B is non /atching. Panic hardware is existing <br />on doors IOOA, 123A, 131A, and 167A. Panic hardware wi// <br />be p�ovided at doors ZIiC,146A, I68A,169A,1698, see <br />revisea/ doorschedu/e sheetA9,1, <br />