• Piping that conveys fluids lA. .ave not been heated or cooled ihmuph the use of rron�_ .a�vaWe energy. <br /> . - Runout pipinp not exceeding 4 ft in lenglh between shutofl valva and coil and t in.in diameter betweo�i Ihe conUol valve and HVA: <br /> mil. <br /> - Pipe unlons in haating sysloms. <br /> 3. Sarvico hot watar piping,where required, must be insulated to 1I2 in.i(pipe less Ihan 1.S in.nominal diameter. larger pipe must 60 <br /> insulated to 1 in.. Pipe insulation will have a conductivity of less ihan 0.20 Btu.in/(h-fl2=F). <br /> 4. Temperalure wntrolling means musl bo provided to limit�he mazimum lemperalufo of water delivered from lavalory laucets in public <br /> faciliry rostrooms to 110°F. <br /> 5. Hoa�inc�and cooling system dosign loads for sizing sys�ems and equipmenl musl be delorminod using generally accepted engineerinc� <br /> standards and handbooks acceptable�o iho adopti�g authoriry(for example,ASHRAE Handbook of Fundamsntals). <br /> 6. Thermo�its cunlrolling b�ih healing and coo�fng must be ppable of mainlaining a 5°F deadband(a range of tomparature where no <br /> healing or cooling is provided). <br /> Ezception(s): <br /> - Deadband capability is nol required if�he�hertnostat doos not have aubmalic changeover capability between heatlng and cooling. <br /> - Spedal occupancy or spocial appliraCons where vnde temperature tanges are not acceptable and are appioved by 1he aulhoriry <br /> havingjurisditlion. <br /> 7. Demand contml von6lation(DCV)roquired for high design occupancy areas(>40 persoN1000 ft2 In spacos>500 fl2)and sorved hy <br /> systoms with any one of 1)an air-side e�nomizer.2)aulomatic moduia�ing control of tho ouldoor air damper,or 3)a design outduor <br /> aidiow greater Ihar 3000 ctm. <br /> Ezception(s): <br /> - SVstoms wiJi hoat recovery. <br /> - M illiple-zaie syslems withoul DDC oG�ndividual zonos communicaGrg wilh a central control panel. <br /> • Systams wilh n design outdoor airflow less ihan 1200 cfin. <br /> - Spaces where�he supply airtlow rate minus any makeup or outgoing trar,s(er air requiremenl is less than 1200 cfm. <br /> 8. Whnre zone healing and cooling are conWlled by separete zone thertnostals,means(such as limit switches,mechanical stops,or,for <br /> DDC systems,software piogramming)must be provided to prevent simultaneous heating and cooling lo tho zone. <br /> 9. Stair and eleva�or shaft venls niust be equipped vrith molonzed dampers capable of being automalically closed dunng rwrmal bwlding <br /> operation and intertocked to open as required by fire and smoke detection systems. All gravity outdoor air supply and exhaust hoods, <br /> venis,and ventilators musl be equipped with motoriznd dampers that will automatically shul when the spaces served are nol in use. <br /> Exception(s): <br /> - Ventilation systoms serving unconditioned spaces. <br /> - Graviry(non-motorized)dampers are accepta6le in buildings less than three slories in height above grade. <br /> 10. Whore a zone is served 6y a system(s)with bolh humidification and dehumidifiption capability,means(such as limit switches, <br /> mechanical stops,or softwere programming)must be provided to prevent simultaneous operation of humidification and <br /> dehumidification equipment. <br /> Exceplion(s): <br /> - Zones served by desiccant systems,used with direct evaporative cooling in series;Syslems serving zones where specific humidiry <br /> levels are roquired. <br /> 11. All freeze proteciion systems,including sell-regulating I�eat tracing,mus�inGude automatic contmis capable o(shutting oM lhe <br /> systems whun outsido air temperatures are above 40"F or when the wiWitions oF tha pfotected tluid vrill prevent froezing. Snow-and <br /> ice-mellirg syslems must indude automatic conlrols capable of shutling otf the systems when the pavement�emperalure is above <br /> 50°F and no precipitation is falling,and an automatic or manual wniml that�rill allow shutoff when the outdoor tem{w2ture is abovc <br /> 40°F. <br /> 12. Duct and pipe insulation exposed to weather must be suitabla for outdoor service:e.g..Dro�eded by aluminum,sheel metal,painled <br /> canvas,or plaslic cover. Ceilular foam insula6on must be protoded as above or painted with a coating Uiat is wa�er retardant anZ <br /> provides shieWing from solar radiation Ihat can causo degrada6on ol ihe malerial.Insulation covering chilled water piping,refrigerant <br /> suclion piping,or cooling ducls located outside the conditioned space must include a vapor retardant located outside the insulation <br /> (unless the insulalion is inherently vapor retardant),all penetrations and joints of which must be sealed. <br /> 13. Duct Soaling Requiroments: <br /> a)Pressure sensitive tape used as the primary sealanl is certifed to comply with UL-181A or UL-181B, <br /> 6)Longitudinal and transverse seamc for ducts in unconditioned spaces, <br /> c)Longitudinal and transverso seams and dud wall peneVations fc+r duds outside the building. i <br /> d)T2nsverse seams on buried ducis <br /> 74. Gutdoor air supply�nd exhaust systems must have motorized dampers that automalically shW when the systems or spaces served are <br /> not in use. Dampers must be capable of automatically shutting off durirg preocwFancy building wamrup,cool[fown,and selback, <br /> excepl when venlilaUon reduces energy cosls(e.g.,night purge)or when ventilation must be supplied to meel code requiremenis.Both <br /> outdoor air supply and exhaust air dampers must have a maximum leakage rate of 3 cfml(t2 at 7.0 In w.g.when tested in accordance <br /> with AM�A Standard.ri00. <br /> F,cception(s): <br /> - Graviry(non-motorized)dampers are acceptable in buildings less than threa stories in height. <br /> Report date: 08/27112 <br /> Project Title: 7-Eleven Inc <br /> Dala filenamo:J:�2012 Projocls\12-00169 1029573 Everetl,W�cvergreen Way�MEP�Energy Cal:s\72-00169 Everefl WA.�.k Page 7 of 8 <br />