. . . � ( C� <br /> Plan Check No. B 59621 <br /> September 4, 1998 <br /> Page 4 of 5 <br /> 14. Exit signs should be shown to be provided with emergency back-up system capable of <br /> providing power for 1'/:hours in accordance with the Electrical Code. Section 1003.2.8.5 <br /> Accessibility <br /> 1. The accessible entrances should be identified on the plans. At least 50% of all public <br /> entrances, or a number equal to the number of exits required by Section 1004.23, whichever <br /> is greater,shall be accessible. Section 1103.2.s <br /> 2. The site plan should show an accessible route of travel from the public way to the accessible <br /> enu�nces. Sectiou 1103.2.2 <br /> 3. Stair sections 18c7/A 6.1 show o�+en stair risers. 'fhis si:ould be revised to risers with backs. <br /> Section 1106.9.2 <br /> 4. Areas of evacuation assistance and all their details such as size, location, telephone, fire <br /> protections, signs, etc. should be shown. Note that the basement level will also require an <br /> area of evacuation assistance as the access is not on grade. Section 1104 <br /> 5. Fonvard approach to a door which must be pulled open requires a minimum side clearance of <br /> 18 inches next to the latch on the approach side. This clearance should be dimensioned on <br /> the doors through the area sep:,ration wall. Section 1106.10.3 <br /> 6. Mounting heights, cleazances and dimensions and elevations should be provided for the <br /> accessible restrooms. Section 1105.2.2 <br /> Energy <br /> 1. It should be clarified whether this project is to comply as a semi-heated space per the <br /> submittal by Phcenix Mechanical. If so, the requirements for semi-heated spaces should be <br /> listed on the plans. Additionally, General Note #1 I on the cover sheet should be amended to <br /> show a maximum temperature of 44 degrees. Section 1310.2 <br /> 2. If the project is to be fully-heated, the envelope insulation requiremenu shouid be listed and <br /> shown in the details. Section 1310.1 <br /> STRUCTURAL <br /> l. The structural portion of this project is currently under review. For expediency, the non <br /> structural comments have been forwarded to your office upon completioa. The structural <br /> comments will be sent under separate letter. <br />