Laserfiche WebLink
t ~ <br /> rw <br /> ++rN <br /> x._ ..�(F <br /> "�. <br /> Plan Ch .k No. B-39803 <br /> April 19, ]993 <br /> Page Two of Five <br /> ✓6. Steel structural members must be protected by 1 hour rated constructed per Table 17-A. <br /> Details E4/A3.11 and B1/A3.13 aze typical examples shuwing unprotected s�eel framing. <br /> �7. The garage ceiling/clinic floor insulation must be noncombustible with noncombusdble facing. <br /> � �8. Provide jus6fying test data for rated corner guards as shown i detail E3/A10.1. <br /> ✓9. Provide details for vehicle barriers to comply with Secdon 1712(b). <br /> ✓10. No point in the building may be more than 200 feet from an exterior exit, horizontal exit, <br /> enclosed stairway, or exit passageway. This item applies to level P2 south an additional exit <br /> should be placed near grid 3 in the west wall. An exit door should also be placed into stair <br /> PIOOS2 for level Pl. <br /> ✓I 1. Exit corridors shall not be interrupted by intervening rooms. Section 3305(a). This item <br /> applies to the following areas: <br /> 6 <br /> ✓a) Provide a door to enclose corridor S100C3 and S100C1 from the waidng area S100W2 <br /> ✓ b) Provide a door to enclose comdor N10005 from comdor N1GJC3. <br /> //c) Provide a door to enclose corridor S200C3 from Corridor 200C 1. <br /> ✓12. Risers on stairways shall be not less than 4 inches nor exceecl7 inches, and runs (treads) shall <br /> be not less than 11 inches. Secdon 3306(c). This applies to Section BI/Al.l and to stair N3 <br /> to the roof. Indicate dimensions on details or sections for all stairs. <br /> ✓13. The top of handrails are to be placed not less than 34 inches nor more than 38 inches above <br />� the nosing of Veads. Section 3306(i). This applies to Section Bl/A1.1. <br /> ✓ 14. The handgrip portion of handrails shall be not less than l�/z inches nor more than 2 inches in <br /> cross sectional dimensicn or the shape should provide an equivalent gripping surface. The <br /> acceptability of equivalent shapes will be determined by the building official. The handgrip <br /> portion shall have a smooth surface with no sharp corners. Section 3306(i). This applies to <br /> the square handrails which exceed 2 inches on the diagonal dimension. <br /> ✓15. Six feet-8 inch minimum headroom clearance for stairways is required. Section 3306(0). <br /> Note that this is measured vertically from a plane tangent to the stairway tread nosing. This <br /> applies to stair k3 to the roof shown with a hatchway at the top which would not comply as <br /> shown. <br /> ,�16. At least one handrail shall extend at least 12 inches beyond the top riser and 23 inches beyond <br /> the bottom riser. Section 3306(i). This applies to Sect�on B1/A1.1. <br />