Laserfiche WebLink
I <br /> 1 LED drivers shall be removable for user replacement. All internal modular components <br /> 2 shall be connected by means of mechanical plug and socket type quick disconnects. <br /> 3 Wire nuts may not be used for any purpose. All external electrical connections to the <br /> 4 luminaire shall be made through the terminal block. <br /> 5 <br /> 6 LED luminaires shall include a 7-pin NEMA photocell receptacle. The LED driver(s) <br /> 7 shall be dimmable from ten volts to zero volts. LED output shall have a Correlated Color <br /> 8 Temperature (CCT) of 4000K nominal (4000-4300K) and a Color Rendering Index (CRI) <br /> 9 of 70 or greater. LED output shall be a minimum of 85% at 75,000 hours at 25 degrees <br /> 10 Celsius. <br /> 11 <br /> 12 LED luminaires shall be available for 120V, 240V, and 480V supply voltages. Voltages <br /> 13 refer to the supply voltages to the luminaires present in the field. LED power usage shall <br /> 14 not exceed the following maximum values for the applicable wattage class: <br /> 15 <br /> Class Max. Wattage 111 <br /> 200W 110W <br /> 250W 165W <br /> 310W 210W <br /> 400W 275W <br /> 16 <br /> 17 Only one brand of LED conventional roadway luminaire may be used on a Contract. <br /> 18 They do not necessarily have to be the same brand as any high-mast, underdeck, or <br /> 19 wall-mount luminaires when those types of luminaires are specified in the Contract. <br /> 20 LED luminaires shall include a standard 10 year manufacturer warranty. <br /> 21 <br /> 22 The list of pre-approved LED Conventional Roadway Luminaires is available at <br /> 23 http://www.wsdot.wa.gov/Design/Traffic/ledluminaires.htm. <br /> 24 <br /> 25 9-29.10(2) Decorative Luminaires <br /> 26 This section, including title, is revised to read: <br /> 27 <br /> 28 9-29.10(2) Vacant <br /> 29 <br /> 30 9-29.12 Electrical Splice Materials <br /> 31 This section is supplemented with the following new subsections: <br /> 32 <br /> 33 9-29.12(3) Splice Enclosures <br /> 34 9-29.12(3)A Heat Shrink Splice Enclosure <br /> 35 Heat shrink splice enclosures shall be medium or heavy wall cross-linked <br /> 36 polyolefin, meeting the requirements of AMS-DTL-23053/15, with thermoplastic <br /> 37 adhesive sealant. Heat shrink splices used for "wye" connections require rubber <br /> 38 electrical mastic tape. <br /> 39 <br /> 40 9-29.12(3)B Molded Splice Enclosure <br /> 41 Molded splice enclosures shall use epoxy resin in a clear rigid plastic mold. The <br /> 42 material used shall be compatible with the insulation material of the insulated <br /> 43 conductor or cable. The component materials of the resin insulation shall be 111 <br /> 44 packaged ready for convenient mixing without removing from the package. <br /> 45 <br /> WEST MARINE VIEW DRIVE UTILITIES PAGE 57 OF 60 August 2018 <br /> WORK ORDER#3588 <br /> WSDOT AMENDMENTS Rev 4/2/18 <br />