a. Previous correction: A rated shaft enclosure is required at the stainvay connecting the <br /> three stories in the change of occupancy from a single family residence to a commercial <br /> structure, per IFC section 4603.3.2. Opening protectives, horizontal and verti�al fire- <br /> reted tested assemblies, hourly separation required, continuity, termination of the <br /> enclosure at top and bottom should be shown on the drawings, per IBC chapter 7. <br /> ��4, Exit door 03 from the stair enclosure is required to have a clear width of 32 inclies, per IBC <br /> section 1008.1.1. <br /> a. Previous correction: The minimum size all nevJ or relocated doors should be shown on <br /> the schedule as minimum 2'-10"wide, 6'-8" high, per IBC section 1008.1.1. <br /> � 5. A landing is required on either side of the doors into the exit stairs, per IBC section 1008.1.5. <br /> Construction <br /> 1. Rated assemblies at the stairs (reference detail 3 on sheet A3) should be shown and targeted <br /> � as details on the drawings, in addition to referencing the reted assembly number. <br /> , 2, Doors in rated enclosures should be shown as rated, per IBC table 7?5.4. <br /> 3. Please specify hardware for poor 06 which does not require tight grasping, tight pinching, or <br /> - twisting, per IBC section 1008.9.1. <br /> a. Previous correction: The hardware set for the accessible entrance door should be shown <br /> on tl�� drewings, per IBC section 1008.9.1 <br /> _ 2. Is there a door planned for Bath 106 in the basement? The existing door is shown as removed. <br /> 3. Previous correction: Handrails should be detailed in section, per IBC section 1012. <br /> 4. Stoves and other fi�ures should be shown in the existing kitchen. <br /> Accessibility <br /> 1. The dimensions of the van accessib�e parking stall and access aisle do not correspond to the <br /> drawing of the stall and access aisle. Please clarify on the drawing that the overall dimension of <br /> the parking area is 16'-0" or greater, and that t(ie dimensions of the van accessible parking <br /> space and access aisle meet the minimum requirements, per IBC section 3411.4.2 (4). <br /> 2. The location of the van accessible signage should be shown on the drawings, per IBC section <br /> 3411.4.2 (3). <br /> 3. The length of the van accessible stall is not dimensioned on the drew�ings. By scale, the length <br /> of the van accessible parking space does not appear to cemply with the requirements of City of <br /> Everett Design and Construction Standard Drawing 3346. Please verify with the civil consultant. <br /> 4. Please provide a section through the threshold connecting the basement hall with the exterior <br /> access aisle. A Floor or landing should be shown at the same elevation on either side of the <br /> door, per IBC section 1008,1.5. <br /> a. Previous correction: An ac.cessible building entrance should be shown on the drawings, <br /> per IBC section 3411.4.2 (i). <br /> 5. The drewings should indicate the marking of the access aisle for the van accessible space. <br />