Laserfiche WebLink
Ray�ond Crerand, AdAinistrator <br /> Progra�, Plans 8 Specifications <br /> CCRS i90369-1546-003 <br /> i90377-1546-004 <br /> April 26, 1990 <br /> Pape 4 <br /> 11. Firc da�pers �nay be reiwved frw� the 30 x 12 duct at the vrall between <br /> Maitinp 739 and corridor 745 and in the supply ducts penetrating the <br /> corridor wall of LDRP roo�s 731 and 735. <br /> 12. Reca�wend that the exhaust repisters in C-section 747 be located neer the <br /> floor to provide better air flow past the patient. <br /> 13. Correct sequence of operation in control specification to suit this <br /> pro�ect. Tise clock control of dey/night te�peraturc does not apply. <br /> EIECTRIGL ITEMS• <br /> 1. All overhead liyht fixtures �nust have protecLive lenses or diffusers. <br /> NAC 248-18-719(4)(d)(1ii) <br /> 2. Please clarify the extent of emergency po►;2r by note on ihe draNinps. (I <br /> understand that everythinp is served by e�erpency power and that shaded <br /> fixtures indicate that they are served by a new critical power panel.) <br /> 3. Provide eait liyhts on both sides of opposed-swinpinp corridor doors. <br /> 1988 UBC section 3314. <br /> 4. Ground fauit interrupter devlces ere required for all receptacles in <br /> totlet bathroo�s and for receptacles located Nlthin five feet of a <br /> lavatory. MAC 248-18-719� Table 719-5, Note (E). <br /> 5. Please sho►v roaa nu�bers on alt floor plans for easier reference. <br /> 6. Co�p lete cireuitinp of receptacles in corridors 745, )51, roon� 750 and in <br /> bathroo� of larye scale typical LDRP roo�. <br /> 7. Mhich receptacle serves the TV in LDRP roa�s? (See sheet E-4 for <br /> location of TV antenna.) <br /> 8. Please show power connection for tub in room 758. <br /> 9. Provide do�e liyhts for nurse cail systeni outside of C-section 741 and <br /> toilet 741. MAC 248-18-719, Tablc 119-6 <br /> 10. Please clerify nurse call system an sheet E-4 to help diffen:ntiate <br /> between annunciator, bed station, toilet and shaver pull cords, emeryency <br /> medical assistance push buttons and duty stations. System shall confon� <br /> to MAC 248-18-719, Table 719-6. <br />