v <br /> 8. Sprinkler system worldng plans are required to be submitted for approval before any <br /> equipment is installed or remodeled. Deviation from approved plans wiil requirc <br /> permission. Woridng plans are required to ccmtain all data as indicated in Section 6- <br /> I.1.1, Uniform Building Code Standazd No. 9-1. Also, please provide a copy of the <br /> latest annual cxrtification test form. Sec. 6-1.1.1, Unifr�rm Building Code Standard No. <br /> 9-1 <br /> 9. Complete plans and specifications for the fire alazm system installadon or modification <br /> aro required to be submitted for review and appro�•al prior to system installation. Plans <br /> and spacifications are required W include, but not be limited to, a floor plan; location of <br /> all alarm-initiating and alazm-signaling devices; alarm�ontrol and trouble-signaling <br /> equipment; annunciation; power connection; battery calculations; conductor typt and <br /> sizes; voltage drop calculadons; name, address, and phone number of the company <br /> receiving off-premises transmission of alazm; and manufacturer, model numbers and <br /> listing information for all equipment, devices and materials. Also, please ptovide a copy <br /> of the latest annual certification test form. Sec. 1001.3, Uniform Fire Code <br /> Page 2 of 2 <br />