Laserfiche WebLink
revised to rigid insulation placed on top of the sheathing or attic ventilation should be <br /> provided and detailed. Section 1203.2 <br /> 5. Storefront glazing adjacent to the entry doors should be shown as safety glazing. <br /> Section 2406.4.2 <br /> 6. For interior slab-on-grade insulation, the insulation should be placed on the on the <br /> inside of the foundation wall and extend downward to the bottom of the slab. Once <br /> there, it may extend horizontally for the remainder of the 24". Section C402.2.6 <br /> 7. The air barrier should be detailed on the plans. Testing requirements should be noted. <br /> Section C402.5 <br /> All codes cited refer to the 2015 International Building Code (IBC) the 2015 International <br /> Existing Building Code (IEBC), the 2015 International Fire Code (IFC), the 2015 International <br /> Mechanical Code (IMC), and the 2015 Washington State Energy Code (WSEC), as amended by <br /> the State of Washington and adopted by the City of Everett. The current IBC referenced <br /> standard for accessible design is the 2009 "Accessible and Usable Buildings and Facilities" <br /> (ICC/ANSI A117.1). Federal ADA regulations and standards may be more restrictive. These <br /> comments address building issues only. Additional revisions or additions may be required by <br /> other departments (such as Utilities, Traffic, Planning or Fire). All required submittals must be <br /> of sufficient detail and information to ensure that the proposed structure will be constructed in <br /> compliance with all adopted codes. <br /> Sincerely, <br /> Tony Lee <br /> Building Official <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425)257-8813 • Page 2 / <br />