• <br /> City of Everett,WA <br /> Response Letter <br /> May 5,2017 <br /> Page 2 <br /> Item 4: Please clarify the general notes on accessibility information: <br /> a. 5: please clarify the code reference <br /> b. 10: scoping requirements of the IBC (not OBC) are -primary (charging <br /> .statements)to the referenced standards of ICC A117-1. <br /> Response: Refer to the revised Cover Sheet clarifying the notes in question above. <br /> Item 5: Please verify note 28 on sheet A1.40 (and similar notes within the set) with the Public <br /> Works plan reviewer regarding direct connection of gutter and downspouts to below <br /> grade storm system. <br /> Response: The Civil team has coordinated the storm system design with the Public Works • <br /> plan reviewer. <br /> • <br /> Item 6: Please clarify where building C is shown on the drawings. <br /> Response: • Building C(Lube Shed &Fueling Canopy)is located in the northeast portion of the <br /> site,please refer to sheet C6.0. <br /> • <br /> • <br /> • <br /> Occupancy,Fire Safety,Egress <br /> • <br /> Item I: Please clarify how the S-1 occupancy occupant load was determined based on the <br /> proposed use, per IBC 311.2. If this is Fed-ex package storage, a warehouse occupant <br /> load would be based on 500 gross,per IBC table 1004.1.2. <br /> Response: Refer to the revised Code Summary on the Cover Sheet which aligns with a <br /> warehouse occupant Ioad. <br /> Item 2: The A-3 use appears to be a B occupancy with a higher calculated occupant load, per <br /> IBC 303.1.2. Please' clarify how the A-3 occupancy was determined based on the <br /> proposed use. <br /> Response: Refer to the revised Code Summary on the Cover Sheet removing the A-3 occupancy <br /> per IBC 303.1.2. <br /> Item 3: A discernible path of egress should be shown with illuminated exit signs on the drawings, <br /> per IBC section 1011.1 for building A. <br /> Response: Exit lights are indicated at all exterior man doors on lighting plans (sheets E2.01 and <br /> E2.04). <br /> Item 4: Emergency lighting should be shown on the drawings, per IBC section 1006.1 for <br /> building A. <br /> • Response: Emergency lighting is shown on all the lighting plans,(sheets E2.01 through E2.04). <br />