<br /> Mechanical Permit Plans Checklist MECH-CHK
<br /> 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised January 2017
<br /> Project Title: Dr.Amy Norman Date 6/5/2018
<br /> The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
<br /> Washington State Energy Code,Commercial Provisions.
<br /> Applicable Code Section Code Provision Information Required-Must be in permit documents Location in Building Department
<br /> (yes,no,na) Documents Notes
<br /> pelican
<br /> C403.2.4.10 Group R2/R3 dwelling For primary space conditioning system,indicate 5-2 programmable thermostats capable of two TS200
<br /> Yes units,Group R2 sleeping setback periods per day;for all thermostats indicate purpose(heating only,cooling only,or
<br /> C403.2.4.11 units both),required temperature range and at minimum a 10°F deadband;or exception taken
<br /> Indicate method of ventilation air delivery(natural or mechanical)for each zone
<br /> If mechanically delivered,indicate that systems are configured to provide not more than 150% Economize
<br /> C403.2.6 Ventilation of,but at least the minimum required volume of outdoor air to each zone per IMC,ASHRAE r set at
<br /> C403.2.11.4 62.1 or other applicable code(WAC,OSHA,etc);or exception taken 100%max
<br /> If delivered via natural ventilation,identify required elements per IMC including minimum
<br /> openable area to the outdoors or qualifying adjoining spaces
<br /> Identify spaces>500 sf with occupant load>25 people/1,000 sf per IMC;for each space None
<br /> Demand controlled indicate whether it is served by an HVAC system with total design OSA>3,000 cfm,and/or
<br /> Yes C403.2.6.2 the system has airside economizer or automatic modulating OSA damper;indicate OSA
<br /> ventilation controls are configured to provide demand controlled ventilation or provide supporting
<br /> documentation for applied exception
<br /> For gyms,classrooms,auditoriums and conference rooms>500 sf,indicate occupancy-based
<br /> C403.2.6.3 Occupancy sensors OSA control when space is unoccupied and method(closes OSA damper or shuts-off
<br /> equipment);or alternate means provided to automatically reduce OSA when space is partially
<br /> occupied
<br /> C403.2.6.4 Enclosed loading dock For enclosed loading docks,indicate ventilation/exhaust system method of activation(gas
<br /> C403.2.6.4.1 ventilation detection system for CO and NO2,or occupancy sensors),and control method(staged or
<br /> modulating)
<br /> C403.2.6.4 Enclosed parking garage For enclosed parking garages,indicate ventilation/exhaust system activated by gas detection
<br /> C403.2.6.4.2 ventilation system for CO and NO2,and control method(staged or modulating);or exception taken
<br /> Provide calculations that show a balanced accounting of total kitchen exhaust(include all
<br /> hoods)with%of:supply air,transfer air from adjacent spaces,and make-up air;if applicable,
<br /> C403.2.7.1 Kitchen exhaust hoods indicate that direct make-up air to each hood does not exceed 10%of hood exhaust
<br /> For kitchens with total hood exhaust exceeding 2,000 cfm,indicate exhaust air rate per Table
<br /> C403.2.7.1 and compliance method(DCV,energy recovery,or transfer air that would
<br /> otherwise be exhausted)
<br /> C403.2.7.2 Laboratory exhaust systems Refer to Systems Requiring Energy Recovery for requirements
<br /> Variable flow capacity- For HVAC fan motors 2 7.5 hp,indicate method of variable flow control(VSD,or equivalent
<br /> C403.2.13 HVAC system fans control method that reduces design air volume by 50%at 1/3 static design pressure);note
<br /> exception taken
<br /> DX air handler variable For DX air handlers with economizer and cooling capacity t 65,000 Btu/h,indicate number of
<br /> cooling control %
<br /> cooling stages provided and method(multiple compressors and/or variable speed
<br /> C403.3.1 compressors);indicate minimum displacement(capacity reduction)as of full load Under 65K
<br /> (Under Integrated
<br /> Economizer) Indicate control method(cooling capacity controlled in response to space temperature,space
<br /> temperature controlled by modulating supply airflow,or both)
<br /> For DX air handling units with cooling capacity z 65,000 Btu/h and evaporative and chilled
<br /> water air handling units with fan z 0.25 hp,indicate whether system is single zone or multiple
<br /> zone and related control method(cooling capacity controlled in response to space
<br /> temperature,space temperature is controlled by modulating supply airflow,or both) Single zone
<br /> For mechanical cooling systems(includes DX and chilled water coils)that control cooling
<br /> capacity in response to space temperature-Provide a minimum of two stages of fan control;
<br /> C403.2.11.5 Fan airflow control indicate minimum fan speed is 5 66%of full speed drawing<_40%of full speed fan power
<br /> during periods of low cooling or ventilation only
<br /> For other mechanical cooling systems(includes DX and chilled water coils)that control space
<br /> temperature by modulating airflow(in lieu of,or in addition to,controlling capacity in response
<br /> to space temperature)-Provide fan controls for modulating supply airflow;indicate minimum
<br /> fan speed is 5 50%of full speed drawing 5 30%of full speed fan power during periods of low
<br /> cooling or ventilation only;or exception taken
<br /> Provide central and zone level DDC controls as required based on system application,
<br /> C403.2.4.12 DDC system capabilities capacity or size thresholds and other qualification per Table C403.2.4.12.1
<br /> Identify all DDC system input/output control points;indicate capability for trending and
<br /> graphical display
<br /> Ducting Systems
<br /> C403.2.8.1 Indicate on plans that all ductwork is constructed and sealed per IMC
<br /> C403.2.8.3 Duct construction For OSA ductwork,also indicate on plans that ductwork meets air leakage requirements per
<br /> C402.5 and vapor retarder requirements per the IBC
<br /> C403.2.8.3 Duct pressure Identify location of low,medium and high pressure ductwork on plans
<br /> classifications
<br /> C403.2.8.3.3 High pressure duct leakage Indicate high pressure duct leakage testing requirements on plans;provide test results to
<br /> test jurisdiction when completed j __