Laserfiche WebLink
3 No <br /> Awe- <br /> 100 amp overhead single phase 3 wire 120/240v service 1.25" EMT <br /> #2 CU Feeding a 125A 20 circuit split bus cutler hammer panel <br /> Panel is recessed in basement wall framing <br /> Below is a description of the wiring methods used at this residence <br /> Home runs going out of the panel are all copper: <br /> 8/3 w/o ground 1940's cloth web romex <br /> 10/3 w/o ground 1940's cloth web romex <br /> 10/2 w/ground 1940's cloth web romex <br /> 2-12/3 w/ground 1940's cloth web romex (improperly phased) <br /> 2-12/2 w/ground 1940's cloth web romex <br /> 2-12/2 NMB <br /> 1-12/2 NM <br /> #4 Bond wire used for ground (if not rigid metal water supply line then then 2ground rods required) <br /> Bond gas line <br /> Grounds are not all twisted properly but are all well secured in the bus bar and neutrals are all separated <br /> correctly in the bus bar <br /> Stove receptacle kitchen 2 gang and furnace and refrigerator receptacle are on the same circuit <br /> Dishwasher disposal plug to the right of the sink, down stair light, down hall right same circuit <br /> Back Door <br /> 3way switch frayed knob and tube mounted in wood door trim <br /> Sun room ungrounded 3 wire receptical <br /> all other receptacles are grounded (although grounds are not properly spliced) <br /> Front Porch weather proof receptacle is not GFCI protected <br /> Furnace room wiring needs to be fastened and a box needs to be provided for the light <br />