Laserfiche WebLink
if <br /> r <br /> �i O MECFiANICAL NOTES: <br /> O 1. DUCT MATERIAL IS 26 GA. GALV. AND FLEX DUCT. DUCTWORK SHALL BE SUPPORTED PER 2015 IMC <br /> WAC CHAPTER 6. SECTION 603 <br /> 2. MATERIAL IN DUCTS SHALL HAVE A FLAME SPREAD INDEX OF LESS THAN 25, SMOKE DEVE�OPMENT <br /> OF 50 PER 2015 IMC WAC CHAPTER 6. SECTION 602 <br /> 3. LOW PRESSURE DUCT SYSTEMS SHALL HAVE LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND <br /> CONNECTIONS OF SUPPLY AND RETURN DUCTS AND PLENUMS SECURELY FASTENED AND SEALED WITH <br /> WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS EMBEDDED-FABRIC SYSTEMS OR APPROVED TAPES <br /> INSTA�LED IN ACCORDANCE WITH 2O15 IMC WAC CHAPTER 6 SECTION 603.9. <br /> CD-1 CD-1 <br /> 10" 10" 4. WHEN ISOLATION SLEEVES ARE USED AT LINE CONNECT�ONS TO PLENUMS, THEN THEY SHALL COMPLY . <br /> WITH IMC CHAPTER 6 <br /> WALL MOUNT <br /> 7 RETURN 5. 10" DIFFUSERS WITH NO MANUAL DAMPERS. USE FLOW CONTROLS AT WYES, TYPICAL AS NOTED ON PLAN <br /> 2� ��� �o <br /> 10 12 6. MINIMUM OUTSIDE AIR VENTILATION PER 2015 IMC WAC CHAPTER 4, TABLE 403.3.1.1. <br /> 1 0 ,� 2 7. OUTSIDE AIR DAMPERS SHALL COMP�Y WITH 2O15 WSEC, SECTION C403.2.4.3. <br /> HP-1 <br /> 0�1� � _ 8. SINGLE PACKAGE UNITARY FAN COOLING UNITS HAVING A TOTAL COOLING CAPACITY OF GREATER THAN <br /> '� o r TCURBF 20,000 Btu/h REQUIRE ECONOMIZERS PER WSEC 403.3. EXCEPT AS PERMITTED BY C403.3 EXCEPTION 1 <br /> o _ _ _ _ _ _ _ _ _ � - _ _ �2 _ _ _ _ _ <br /> SUPPLY PLENUM <br /> #Pws�3� I�ECHANICAL NOTES: (cont.) <br /> OCCUPIED SET POINT MECHANICAL EQUIPMENT INSTALLATION IN OR ON THIS BUILDING SHALL BE IN ACCORDANCE WtTH <br /> TO BE CONTROLLED BY THE REQU(REMENTS OF THE 2015 IMC WAC CHAPTER 6. <br /> nLIGHT OCCUPANCY <br /> SENSORS ROUND FLEX DUCT SHALL BE U.L LISTED CLASS 1, STANDARD 181 - FACTORY MADE AIR pUCTS AND AVR <br /> CONNECTORS. MEASURED IN ACCORDANCE TO ASTM C 518 OR ASTM C 177 AT 75DEG F MEAN <br /> TEMPERATURE. INSTALLATION SNALL BE IN ACCORDANCE WITH MANUFACTURES INSTALLATION INSTRUCTIONS <br /> CD-1 CD-1 <br /> 10" 10" MECHANICAL DRAWINGS SHOW DUCTWORK SIZES TO BE CLEAR INSIDE DIMENSION. <br /> DUCT INSULATION SHALL COMPLY WITH 2O15 IMC WAC CHAPTER 6, SEC. 604. <br /> ELECTRICIAN MUST VERIFY ALL ELECTRICAL REQUIREMENTS AND LOCATIONS. <br /> THERMOSTAT SCNEDULING TO BE PERFORMED ON SITE BY OTHERS. ' <br /> ALL HVAC EQUIPMENT LEAVES FACTORY WIRED FOR 240 VOLT OPERATION <br /> OTHE ACCEPTABLE OPERATING RANGE FOR THE 240V & 208V TAPS ARE: <br /> � TAP RANGE <br /> 240 253-216 <br /> � 208 220-187 <br /> 1/4" = 1'-0" SITE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THE RIGHT TAP IS CONNECTED FOR <br /> THE APPLIED SITE VOLTAGE. <br /> MINIMUM VENTILATION RATES PER IMC SECTION 403 AIR FILTERS IN HVAC UNITS OR SYSTEMS ARE TO BE CHANGED EVERY 30 DAYS BY OTHERS ON SITE. <br /> Rp ' <br /> room# name Az (sf) sf/1000 Occ. Dens Pz(calc} Pz(usedj (cfm/person� Ra(cfm/sf) Vbz(cfm) REGISTER AIR FLOW TEST AND BALANCE OF HVAC SYSTEM TO BE PROVIDED AND PERFORMED BY OTHERS ON SITE. <br /> 1 Classroom $17 0.817 35 29 29 10 0,12 388 <br /> 388cfm HVAC SITE CONTRACTQR IS RESPONSBLE FOR BALANCING TH� SYSTEM. (2015 IMC WAC 403.3.3.1.5) <br /> Az=room area (sf) <br /> Occ. Dens=occupant density(fram Table 403.3) <br /> Pz(calc) =zone popu(ation or occupant quantity(calculated) <br /> Pz(usedj =zone population or occupant quantity(user can override the calculation-increase only) <br /> Rp=people outdoor airflow rate in breathing zone {cfmJperson� <br /> Ra=area outdaor airflow rate in breathing zone (cfm/sfj <br /> Vbz=Breathing zone outdvor air flow rate per eq. 41( Rp*Pz+Ra*Az) <br /> PACKAGE *SPVU* HIGH EFF►CIENCY WALL MOUNT HEAT PUMP - SCHEDULE <br /> DOAS/ERV/ELECTRICAL 1Q DOAS/ERV/ELECTRICAL � COOLING CAPACITY� HEATING CAPACITY �4 DOAS UNIT HEAT STRIPS <br /> ENERGY RECOVERY ELECT. INFORM. ELECT. INFORM. <br /> DOAS �OW VENTILATION MODE FULL VENTILATION MODE ELEC. ELEC. OPER. <br /> COMP TOTAL ECON. ERV COOL SENS. COOL SENS. HTG HTG OUTDOOR <br /> BARD TYPE CFM BLR. 100% ECM ECM OUTSIDE ENT ENT CAP. CAP. CAP. CAP. OUTSIDE CAP. CAP. SUMMER DB/WB HRS HRL WINTER INDOOR WHR HEAT HEAT WGT. ADDITIONAL <br /> TAG QTY MODEL # TONS SCRO�L NOM. TYPE. FREEFLOW OSA V-PH ERV BLOWER V-PH ERV BLOWER DB DB WB EER IPLV BTUH BTUH BTUH BTUH DB COP BTUH BTUH EFFICIENT DEG'S BTUH BTUH EFFICIENT DB MOP V-PH MCA MOP CKT V-PH MCA BTUH CKT KW BTUH LBS. REMARKS <br /> � PART/FUL VENTIL. MOTOR MOTOR PART LOAD PART LOAD FULL lOAD FULL LOAD PART/LOAD FULL/LOAD � <br /> HP-1 1 C36HA-A10ZP4XXR 3 2-STAGE 750 ECM NQ 388 230/1 AMPS-1.3 AMPS-.87 230/1 AMPS-2.2 AMPS-1J4 95 80 67 11.0 14.5 23.4K 18.5K 35K 26.3K 47 3.3 22.7K 31K 65� 95/70 6,318 1,711 8Q% 1,711 23,328 230/1 27 40 A 240 1 52 60 B 10 34,130 678 1, 2, 3, 4, 5, 6, 7, 8 <br /> 1100 450 WATTS-296 WATTS-95 WATTS-497 WATTS-192 � <br /> ADDITIONAL REMARKS; C36H1 The sequence of operation for the Integrated DOAS system. <br /> 2 - NC UDE BARD WAL.L CURB #TCURBF3642A-4. ERV Watts - Low 296 Watts Blower Full Lood 192 Watts 1. Upon a call from the occupancy sensor the(DOAS) ERV and the indoor(ECM) motor will <br /> 3 - THERMOSTAT, BARD # 8403-060, 7-DAY PRQGRAMMABLE ERV Am s - Low 1.3 Am s Blower Full Load 1 J4 Am s start in low vent mode and ventilate the space continuously as occupied. <br /> 4 - WALL CO2 SENSOR. #8403-067 ERV CFM - Low 300 CFM Blower Part Load 95 Watts Note: 1 on the HVAC Schedule. <br /> 5 - OCCUPANCY SENSOR, (SUPPLIED BY B�AZER} ERV Watts - Med 415 Watts Blower Part Load 0.87 Am s 2, Upon a call from the CO2 sensor the(DOAS} ERV and the indoor(ECM) motor wili <br /> 6 - GPS (FIELD INSTALLED CONTROL KIT). ERV Am s - Med 1.8 Am s <br /> 7 - 2" FILTER. ERV CFM - Med 375 CFM Com ressor Fuil 2588 Watts change to full vent mode and ventilate the space until the CO2 sensor is satisfied and then <br /> 8 - ERV (DOAS) ENERGY RECOVERY. ERV Wotts - Hi 497 Watts Com ressor Full 11.46 Am s revert back to the low vent mode during the occupied time. <br /> 9 - UNIT COLOR IS *BUCKEYE GRAY* ERV Am s - Hi 2.2 Am s Com ressor Part 1734 Watts Note: 2 on the HVAC Schedule. <br /> 1Q - PRE INSTALLED OUTDOOR THERMOSTAT, SET AT 40DEG'S. ERV CFM - Hi 450 CFM Com ressor Part 7.99 Am s 3. The Heating and Cooling section wiltonly work if there is a Heating or Coo�ing call from <br /> '�* M.C. TQ REFER TO lNSTALLATION INSTftUCTIONS FOR START UP AND EQUIPMENT SET. Outdoor Fan 380 Watts the thermostat. This action works entirely independent of the DOAS ventilation portion. <br /> ** M.C. TO CHECK SITE VOLTAGE AND SET CORRECT TAP ON TRANSFORMER. Outdoor Fan 1.67 Am s Note: 3&4 on the HVAC Schedule. <br /> ** M.C. TO SET AND PROGRAM THERMOSTAT PER CUSTOMERS REQUIREMENTS. 4. 7IlIS aCtIOCI WIII k2ep PepOating ItS2lf aS I"2qUifed by th@ OCCUpaIICy SeIISOf, CO2 SetISOC <br /> and Room Thermostat. <br /> 8-18-17 REVISE HEA7 PUMP SCHEDULE,ADD SEQUENCE OF OP. RMS COPYRIGHT 2017, BLAZER INDUSTRIES, WC. Approved for Const: Job No: 19039 <br /> 9-6-17 ADD SUPPLY PLENUM NUMBER(#PWS131) LDG THIS MATERIAL IS TNE EXCL.USIVE PROPERTY MODULAR �`I���I��OI�I f�r' <br /> OF BLAZER INDUSTRIES, WC.AND SHALL ■�I � � � File Copy: � <br /> NOT BE REPRODUCED, USED, OR DISCLOSED � 28 x 32 m <br /> TO OTHERS EXCEPT AS AUTHORIZED BY THE �� INDUSTRIES,INC. � � Drawn By: LDG <br /> DATE REVISION BY WRITTEN PERMISSION OF BLAZER INDUSTRIES. �� �✓.blazerind.com �/�/A. GOLD Pacific Mobile 17 BLMP-04 A9 WA <br /> ■■ P.O.BOX 489 ■ Aumsville,pR 97325-0489 ISSUB DBte: 9-5-�7 <br /> � <br />