MEIN • <br /> MINIM <br /> MEI <br /> MEM <br /> MINIM <br /> 6. The elevator system appears to be laterally supported by GL6-3/4x24 posts spanning <br /> between the floor levels. See page 12 of the structural calculations. The design should be <br /> revised based on the following: <br /> a. The calculation is based on a clear span of 16 feet. The actual clear span appears to <br /> be approximately 18 feet per Section 8/A8.1. <br /> b. The design appears to consider a maximum bending stress of 2,400 psi corresponding to <br /> strong-axis bending. The post appears subject to weak-axis bending and should consider <br /> a nominal bending stress of 1,450 psi per NDS-2015 Supplement Table 5A. See IBC <br /> Section 2306.1 <br /> c. The design does not clearly indicate if the member has been evaluated for strong-axis <br /> or weak-axis bending. The calculations should be reviewed and revised as needed. <br /> DCI Response: An added elevator is no longer part of this project. <br /> Z Detail 3/AF1.0 states that a maximum 1:1 cut shall be performed for the elevator foundation <br /> excavation. Section 8/A8.1 indicates an excavation depth of at least 6 feet. Section 1/AF1.0 <br /> indicates an existing wall face within 2 feet of the foundation. The site conditions should be <br /> reviewed and revised if needed. Calculations substantiating the elevator foundation wall for <br /> building surcharge loads in addition to other loading should be submitted for review. See IBC <br /> Sections 1603.1 and 1604.1. <br /> DCI Response: An added elevator is no longer part of this project. <br /> 8. Plan 1/AF1.0 specifies TS5x5 and GL6-3/4x15 posts in the elevator shaft walls. The purpose <br /> of and loading conditions on the posts is not clear. The posts do not appear to be included in <br /> the structural calculation package. Documentation substantiating their design, including <br /> connections, should be submitted for review. See IBC Section 1604.1. <br /> DCI Response: An added elevator is no longer part of this project. <br /> 9. Detail 4/AF1.0 shows the anchorage of the column to the pedestal below. See IBC Section <br /> 1901.2. The following comments should be addressed: <br /> a. The minimum clear cover should be specified per IBC Section 1808.8.2 and ACI 318- <br /> 14 Table 20.6.1.3.1. <br /> b. The top of the pedestal shall include transverse reinforcement complying with ACi 318- <br /> 14 Section 10.7.6.1.6 <br /> c. The transverse reinforcement shall include cross-ties as required by AC!318-14 Sections <br /> 10.7.6.1.2 and 25.7.2.3. <br /> DCI Response: An added elevator is no longer part of this project. <br /> 10.Details 3/AF1.0 and 4/AF1.0 do not appear to include dowels between the new and existing <br /> slabs. Dowels are recommended to minimize settlement between the slab edges. See IBC <br /> Section 1808.2. <br /> DCI Response: Details 3 and 4/AF1.0 have been removed from the drawings. 00_ <br />