MECHANICAL SPECIFICATIONS SLABS OR OTHER CONDITIONS THAT NEED TO BE TAKEN INTO ACCOUNT IN SETTING OF ANCHORS. UTILIZE MCCULLOUGH CONNECTIONS CONFORMING TO REQUIREMENTS OF ASME B1 .20.1 ; POLYTETRAFLUOROETHYLENE (PTFE) SEAT AND SEAL. <br /> "KWIK—BOLT", PHILLIPS SELF—DRILLING ANCHORS, GREGORY "BULLDOG," OMARK "DRILL ANCHORS", OR OTHER APPROVED PROVIDE STEM EXTENSION FOR USE IN INSULATED PIPING. VALVE SHALL MEET MINIMUM PRESSURE RATING OF 150 PSIG <br /> MECHANICAL WORK, GENERAL ANCHOR TO ATTACH TO CONCRETE STRUCTURES. WHERE BUILDING STRUCTURE IS WOOD OR STEEL, OBTAIN ARCHITECT AT 230 DEGREES F. <br /> APPROVAL OF HARDWARE AND METHODS TO BE UTILIZED FOR ATTACHMENT TO THE STRUCTURE. <br /> A. GENERAL REQUIREMENTS WASTE AND VENT PIPING: HUBLESS, CAST—IRON SOIL PIPE AND FITTINGS; HEAVY—DUTY HUBLESS PIPE COUPLINGS; AND <br /> ADDITIONAL FRAMING: PROVIDE STEEL FRAMING MEMBERS TO TRANSFER LOAD FROM SUPPORT POINTS AT HANGERS TO COUPLED JOINTS. <br /> CONTRACT REQUIREMENTS: COMPLY WITH BIDDING AND CONTRACT REQUIREMENTS AS OUTLINED BY THE OWNER AND LOCATIONS WHERE CONNECTIONS CAN BE MADE TO THE BUILDING STRUCTURE. FRAMING MEMBERS SHALL BE 12—GAUGE <br /> ARCHITECT. MINIMUM, 1 -3/8" X 1 -5/8" MINIMUM CROSS—SECTION SIZE; UNISTRUT, POWERSTRUT, OR OTHER APPROVED. SELECT PLUMBING FIXTURES <br /> MEMBER S�ZE AND TYPE, AS APPROPRIATE FOR LOAD PER MANUFACTURER GUIDELINES. � <br /> WORK INCLUDED: THIS SECTION APPLIES TO ALL MECHANICAL WORK NORMALLY SPECIFIED UNDER DIVISIONS 22 AND 23. A. PLUMBING FIXTURE ACCESSORIES <br /> PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, TOOLS, FIELD DESIGN, SHOP DRAWINGS, HOISTING, SCAFFOLDING, PIPE HANGERS: CLEVIS OR RING HANGERS WITH STEEL RODS. HANGERS FOR INSULATED PIPING SNALL BE SIZED FOR <br /> SUPERVISION AND OVERHEAD FOR THE CONSTRUCTION, INSTALLATION, CONNECTION, TESTING AND OPERATION OF ALL OUTSIDE INSULATION AND 6" SHIELDS SHALL BE PROVIDED AT ALL HANGERS TO PROTECT INSULATION. PIPE SUPPORT FIXTURE CARRIERS: PROVIDE CAST IRON OR STEEL CARRIERS FOR ALL WALL—HUNG FIXTURES WITH CONCEALED FIXTURE <br /> MECHANICAL WORK AS SHOWN AND SPECIFIED. THE WORD "PROVIDE" USED HEREINAFTER MEANS TO FURNISH AND SPACING PER IMC. PROVIDE PLASTIC SEPARATION BETWEEN CLAMPS AND COPPER PIPE. CARRIERS CONSTRUCTED FOR THE FIXTURE, HEAVY DUTY CONSTRUCTION WITH SECURE ANCHORING TO CONCRETE FLOOR. <br /> INSTALL. ALL WORK AND MATERIALS REQUIRED FOR COMPLETE FUNCTIONING SYSTEMS ARE NOT OUTLINED HERE BUT SMITH, WADE, ZURN, OR APPROVED. BACK LUG OF WATER CLOSET CARRIERS SHALL BE ANCHORED TO FLOOR. PROVIDE <br /> SHALL BE PROVIDED AS PART OF THIS WORK. HANGER RODS: HOT ROLLED STEEL ROD, ASTM A 36; SIZE TO "CODE FOR PRESSURE PIPING", ANSI B 31 .1 , WITH 4—BOLT CARRIERS FOR SYPHON JET WATER CLOSETS. PROVIDE BARIATRIC CARRIERS FOR ADA WATER CLOSET STALLS. <br /> SAFETY FACTOR OF 5. MINIMUM ROD SIZE; 1 " PIPE AND SMALLER (240 POUNDS) = 1/4" ROD, 1 -1/4" TO 2" PIPE <br /> CODES: COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES OF THE LOCAL AND STATE CODE ENFORCING » » » � � _ � » » » � BARIATRIC CARRIERS: PROVIDE CAST IRON OR STEEL CARRIERS FOR WALL—HUNG FIXTURES WITH CONCEALED FIXTURE <br /> (T0 610 POUNDS) = 3/8 ROD, 2-1/2 TO 4 PIPE TO 1 ,130 POUNDS — 1 2 ROD, 5 TO 8 PIPE TO 1 ,810 CARRIERS CONSTRUCTED FOR THE FIXTURE, EXTRA HEAVY DUTY CONSTRUCTION (1 ,000 POUND CAPACITY BARIATRIC) WITH <br /> AGENCIES. OBTAIN PERMITS, APPROVALS, AND INSPECTIONS, AND PAY ALL COSTS AND FEES FOR PERMITS, REVIEWS, POUNDS) = 5/8" ROD. <br /> AND INSPECTIONS. SECURE ANCHORING TO CONCRETE FLOOR. SMITH, WADE, ZURN, OR APPROVED. . <br /> INSTALL HIGH DENSITY PRE—MOLDED PIPE INSULATION 180 DEGREES HALF—SHELLS ON BOTTOM HALF OF PIPE AT DRAINS AND TRAPS: PROVIDE GRID STRAINER DRAINS FOR ALL LAVATORIES UNLESS INDICATED OTHERWISE. PROVIDE <br /> ABBREVIATIONS: WHERE ABBREVIATIONS ARE USED IN THE SPECIFICATIONS AND ON THE DRAWINGS THE COMMON � � <br /> INDUSTRY DEFINITION SHALL APPLY UNLESS INDICATED OTHERWISE. THE TERM A/E SHALL REFER TO THE PROJECT SUPPORTS FOR PIPING GREATER THAN 1" IN DIAMETER, 6" LONG FOR PIPING 6" IN SIZE OR SMALLER. FOR COLD PIPE TRAPS AND TAILPIECES AT ALL FIXTURES UNLESS TRAP IS INTEGRAL WITH FIXTURE. <br /> ARCHITECT AND MECHANICAL CONSULTING ENGINEER AS IF ONE ORGANIZATION. SUPPORTS USE 3.0 PCF DENSITY POLYISOCYANURATE INSULATION. HOT PIPE SUPPORTS SHALL BE HIGH DENSITY <br /> POLYISOCYANURATE FOR FLUIDS UP TO 300 F, OR CALCIUM SILICATE. INSULATION AT SUPPORTS SHALL HAVE SAME STOPS AND SUPPLIES: PROVIDE CHROME STOPS AT EACH WATER CONNECTION TO EACH FIXTURE, EXCEPT WHERE A <br /> SUBMITTALS: SUBMIT PRODUCT DATA AND SHOP DRAWINGS FOR ALL SIGNIFICANT MATERIALS, EQUIPMENT, AND FIXTURES THICKNESS AS ADJACENT INSULATION. FAUCET OR CONTROL HAS INTEGRAL STOPS. STOPS SHALL BE A LOOSE KEY PATTERN WITH SHIELD; CHICAGO, <br /> TO THE A/E FOR REVIEW. ALLOW REASONABLE TIME FOR REVIEW AND RETURN PRIOR TO ORDERING. PDF (ELECTRONIC) BRIDGEPORT BRASS, BRASS CRA�f (SPEEDWAY), TELEDYNE, OR EQUIVALENT. PROVIDE 3/8" OUTSIDE DIAMETER CHROME <br /> SUBMITTALS AREA ACCEPTABLE, IF PAPER COPIES ARE SUBMITTED ASSUME OWNER AND A/E WILL RETAIN A TOTAL OF C. EQUIPMENT AND PIPING IDENTIFICATION PLATED TUBING SUPPLIES. <br /> THREE COPIES OF SUBMITTALS. PIPE IDENTIFICATION: ALL PIPING IN SERVICEABLE LOCATIONS (INCLUDING ABOVE LAY—IN CEILINGS) SHALL BE IDENTIFIED <br /> „ CAULKING: PROVIDE SILICONE SEALER BETWEEN THE TOP AND THE SIDES OF PLUMBING FIXTURES AND ADJACENT WALL <br /> WITH SEMI—RIGID PLASTIC OR ADHESIVE IDENTIFICATION MARKERS. MARKERS SHALL CONFORM TO ANSI A13.1 SCHEME � . <br /> , <br /> SAFETY MEASURES: PROVIDE A SAFE ENVIRONMENT TO PROTECT EMPLOYEES AND ALL OTHERS FROM INJURY. COMPLY „ , SURFACES; GENERAL ELECTRIC N0. SCS/202. APPLY PER MANUFACTURER S RECOMMENDATIONS TO FORM A SMOOTH, <br /> WITH LOCAL, STATE AND FEDERAL SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION. FOR THE IDENTIFICATION OF PIPING SYSTEMS , LOCATE MARKERS ADJACENT TO EACH VALVE, AT MINIMUM 30 CENTERS UNOBTRUSIVE JOINT. <br /> WITH AT LEAST ONE MARKER BETWEEN ANY TWO PARTITIONS. PROVIDE DIRECTION OF FLOW ARROWS AT MARKERS. <br /> B. PERFORMANCE OF WORK EXPOSED PLUMBING: IN GENERAL, ALL PIPING SHALL BE CONCEALED UNLESS INDICATED OTHERWISE. ANY PIPING THAT <br /> D. MISCELLANEOUS MATERIALS AND ACCESSORIES MUST BE EXPOSED WITHIN A IN T TH <br /> C B E S OR 0 ERWISE DUE TO CONNECTIONS RE UIRED FOR FIXTURES AND E UIPMENT <br /> , Q Q , <br /> i <br /> COORDINATION: COORDINATE MECHANICAL WORK WITH ALL OTHER TRADES AND TAKE ALL MEASUREMENTS NECESSARY TO SHALL BE PAINTED SILVER. ALL EXPOSED ITEMS, INCLUDING STOPS, TRAPS, ETC., SHALL BE CHROME PLATED. <br /> INSURE PROPER INSTALLATION OF MECHANICAL WORK PRIOR TO START OF FABRICATION. THIS CONTRACTOR SHALL DIELECTRIC UNIONS: PROVIDE AT EACH PIPE CONNECTION BETWEEN DISSIMILAR METALS. 2 INCHES AND SMALLER, 250 <br /> CREATE BUILDING INFORMATION MODELS (BIM) AND/OR LARGE—SCALE DETAIL DRAWINGS WHERE NECESSARY TO PSIG AT 180 DEG. F., ANSI B16.39. OVER 2" USE FLANGE FITTINGS, ANSI B16.42 (IRON) OR ANSI B16.24 (BRONZE), B. PLUMBING FIXTURES <br /> COORDINATE WORK IN TIGHT AREAS. THE CONTRACT DRAWINGS DO NOT ATTEMPT TO SHOW EXACT LOCATIONS OF WATTS 3000 SERIES, EPCO OR EQUIVALENT. <br /> DUCTWORK, PIPING, FIXTURES, AND EQUIPMENT, OR ALL TRANSITIONS AND OFFSETS THAT WILL BE NECESSARY FOR GENERAL: PROVIDE THE PLUMBING FIXTURES AS INDICATED BELOW, AND ON THE DRAWINGS. PROVIDE THE <br /> INSTALLATION. ALL NECESSARY TRANSITIONS AND OFFSETS SHALL BE PROVIDED AS PART OF THIS WORK WITHOUT ADDED FIRE SEALING AT RATED WALLS AND FLOORS: PROVIDE UL LISTED FIRE RATED PUTTY AT ALL PIPE PENETRATIONS OF MANUFACTURER AND MODEL NUMBERS AS INDICATED; HOWEVER, CONTRACTOR SHALL VERIFY MODEL NUMBERS OF <br /> COMPENSATION. RATED WALLS AND FLOORS. PUTTY SHALL BE INSTALLED STRICTLY PER MANUFACTURER INSTRUCTIONS WITH SLEEVES FIXTURES, FLUSH VALVES, FAUCETS, ETC., FIT TOGETHER PROPERLY. <br /> WHERE REQUIRED. OVERALL INSTALLATION SHALL MEET CODE REQUIREMENTS. PIPE INSULATION SHALL NOT BE <br /> CONTINUITY OF SERVICE: ANY SYSTEMS OR SERVICES WITHIN EXISTING OCCUPIED BUILDINGS SHALL BE MAINTAINED WITH CONTINUOUS THROUGH FIRE RATED WALLS OR FLOORS. MULTI—POSITION LAVATORIES: BRADLEY TERREON SEMI—CIRCULAR WALL MOUNTED WASH <br /> MINIMUM INTERRUPTION. COORDINATE ANY NEEDED INTERRUPTIONS WITH THE OWNER. ANY OVERTIME WORK REQUIRED FOUNTAIN, 54" DIAMETER, MODEL #: TCB3104.A.STD.SEC.IRP.TMA.NSD.S—CREEK.NONE.NONE.NONE FOR FOUR USERS, WITH <br /> BY THIS PROJECT TO MAINTAIN EXISTING BUILDINGS IN CONTINUOUS SERVICE, WITHOUT REDUCING THEIR EFFICIENCY, INTERCONNECTING WIRING: PROVIDE ANY NECESSARY INTERCONNECTING WIRING BETWEEN INDIVIDUAL COMPONENTS AND INFRARED SENSOR VALVE ACTUATION AND SECTIONAL SPRAY HEAD. INCLUDE THERMOSTATIC MIXING VALVE, VOLUME <br /> SHALL BE INCLUDED AS A PART OF THIS CONTRACT. ACCESSORIES FURNISHED WITH MECHANICAL EQUIPMENT PACKAGES (UNLESS THAT WIRING IS SPECIFICALLY CALLED FOR CONTROL VALVE, (2) STOPS, SUPPLIES, STRAINER AND CHECK VALVES, NO SHROUD, NO SUPPORT TUBE AND NO TOWEL <br /> ON THE ELECTRICAL DRAWINGS). WIRING AND WIRING ACCESSORIES SHALL BE IN ACCORDANCE WITH THE SPECIFICATIONS DISPENSER. <br /> DEMOLITION: PROVIDE MECHANICAL SYSTEM DEMOLITION IN AREAS OF EXISTING BUILDINGS TO ACCOMMODATE ON THE ELECTRICAL DRAWINGS AND LOCAL ELECTRICAL CODE. WIRING SHALL BE IN CONDUIT OR RACEWAY. WIRING <br /> INSTALLATION OF NEW WORK. EXISTING PIPING, VALVES, AND DUCTWORK, WHERE INDICATED ON THE DRAWINGS, MAY BE SHALL BE PROVIDED AT THE EXPENSE OF THE SUBCONTRACTOR FURNISHING THE EQUIPMENT PACKAGE. MULTI—POSITION LAVATORIES: BRADLEY TERREON FREE—STANDING CIRCULAR WASH <br /> REUSED IN THEIR ORIGINAL LOCATION. DO NOT REUSE EXISTING PIPING, VALVES, OR DUCTWORK ONCE THEY ARE FOUNTAIN, 54" DIAMETER, MODEL �: TCB3104.A.STD.SEC.IRP.TMA.NSD.S—CREEK.NONE.TA.NONE FOR EIGHT USERS, WITH <br /> REMOVED, UNLESS WRITTEN PERMISSION IS OBTAINED FROM OWNER. REMOVE ALL UNUSED PIPING AND DUCTWORK E. EXECUTION OF WORK INFRARED SENSOR VALVE ACTUATION AND SECTIONAL SPRAY HEAD. INCLUDE THERMOSTATIC MIXING VALVE, VOLUME ' <br /> LOCATED IN REMODEL AREAS OF EXISTING BUILDINGS. CONTROL VALVE, (2) STOPS, SUPPLIES, STRAINER, CHECK VALVES AND SUPPORT TUBE, NO SHROUD, AND NO TOWEL <br /> INSTALLATION, GENERAL: FOLLOW MANUFACTURER'S INSTRUCTIONS AND UTILIZE GOOD INDUSTRY PRACTICE WHEN DISPENSER. <br /> CUTTING AND PATCHING: PROVIDE ALL CU171NG OF BUILDING CONSTRUCTION, AS REQUIRED FOR THIS WORK. KEEP INSTALLING ALL WORK. USE ONLY SKILLED TRADESPEOPLE WITH QUALIFIED SUPERVISION. ALL WORK SHALL BE LEFT <br /> CUTTING TO A MINIMUM, AND USE SAW CUTTING TO MAINTAIN NEAT, EVEN OPENINGS. UNLESS PATCHING IS INCLUDED NEAT AND CLEAN. COUNTER LAVATORIES: UNDERMOUNT LAVATORY, �AMERICAN STANDARD OVALYN UNDERCOUNTER 19 WCHES BY 16 INCHES, <br /> UNDER OTHER DIVISIONS OF THIS SPECIFICATION, PROVIDE PATCHING AT ALL CUITING LOCATIONS. ALL PATCHING SHALL VITREOUS CHINA OVAL LAVATORY, WITH CONCEALED FRONT OVERFLOW, MOUNTING ASSEMBLY COMPLETE WITH INSTALLATION <br /> CONFORM TO SPECIFICATIONS FOR THE NEW GENERAL CONSTRUCTION WORK. FINISH TO MATCH EXISTING WORK. CONCEALMENT: PIPING SHALL BE CONCEALED WITHIN BUILDING CONSTRUCTION, UNLESS SPECIFICALLY INDICATED TEMPLATE, MOUNTING SCREW SET AND SEALING COMPOUND. <br /> OTHERWISE. WHERE PIPING IS INDICATED TO BE EXPOSED TO VIEW IN FINISHED SPACES OR CABINETS, PROVIDE CHROME <br /> C. PROJECT COMPLETION ESCUTCHEONS WHERE THE PIPING PENETRATES THE WALL, FLOOR OR CEILING CONSTRUCTION. COUNTER LAVATORY FAUCETS: SLOAN OPTIMA ETF80, CHROME PLATED, DECK MOUNTED, IR ACTIVATION, 24VAC <br /> RECORD DRAWINGS (AS—BUILTS): CORRECTIONS AND CHANGES MADE DURING THE PROGRESS OF THE WORK SHALL BE WATER SEALING AT FLOORS: PROVIDE WATER TIGHT SEALING AT EACH FLOOR PENETRATION INCLUDING PIPING WITHIN TRANSFORMER EL-208 (SEE ELECTRICAL FOR QUANTITY), BELOW DECK THERMOSTATIC MIXING VALVE, 0.5 GPM <br /> NEATLY RECORDED AS ACTUALLY INSTALLED FOR AS—BUILT RECORDS. FURNISH ONE CLEAN SET TO THE A/E UPON WALL CAVITIES. PROVIDE WATER SLEEVES SEALED TO THE FLOOR CONSTRUCTION AND PROJECTING NOT LESS FLOWRATE, 1/2" NPT. . <br /> COMPLETION OF THE PROJECT. THAN 1 .5" ABOVE FLOOR WHERE INSULATED PIPING PENETRATES THE FLOOR. THE INTENT IS TO MINIMIZE PASSAGE OF URINALS: AMERICAN STANDARD LYNBROOK 1 .0, 6601 .012, VITREOUS CHINA FIXTURE, 1 .0 GPF CAPACITY, 1 -1/4" INLET <br /> WATER DURING A SIGNIFICANT WATER LEAKAGE EVENT. SEALING IS REQUIRED FOR CONCRETE FLOORS.) TOP SPUD, BLOWOUT FLUSH ACTION. <br /> � OPERATION AND MAINTENANCE MANUALS: PROVIDE THREE, (3) FINISHED COPIES OF MECHANICAL OPERATION AND <br /> MAINTENANCE MANUALS, FOR WORK UNDER THIS PROJECT. ARRANGE INFORMATION CONTAINED IN THE MANUALS IN AN COORDINATION WITH OTHER TRADES: COMPLETE DRAWINGS AND SPECIFICATIONS OF ALL TRADES WILL BE FURNISHED OR <br /> ORDERLY ARRANGEMENT (BY SPECIFICATION SECTION), SEPARATED BY TABS. PROVIDE EQUIPMENT MANUFACTURER, MODEL WILL BE AVAILABLE FOR INSPECTION IN THE CONSTRUCTION OFFICE AT THE JOBSITE. CAREFULLY CHECK THESE URINALS (ADA): AMERICAN STANDARD LYNBROOK 1 .0, 6601 .012, VITREOUS CHINA FIXTURE, 1 .0 GPF <br /> NUMBER, SIZE, CAPACITY, PERFORMANCE DATA, SCHEDULE OF ROUTINE MAINTENANCE, SUPPLIERS LIST, LIST OF DRAWINGS AND SPECIFICATIONS BEFORE INSTALLING ANY WORK. IN ALL CASES, CONSIDER THE WORK OF ALL OTHER CAPACITY, 1 1/4 INLET TOP SPUD, RIM HEIGHT TO BE 17 INCHES OR LESS FOR ADA COMPLIANCE, BLOWOUT FLUSH <br /> REPLACEMENT PARTS, AND INCLUDE ANY SHOP DRAWINGS. TRADES AND COORDINATE WORK WITH THAT OF THE PLUMBING AND ELECTRICAL SUBCONTRACTORS, SO THAT THE BEST ACTION. <br /> ARRANGEMENT OF ALL EQUIPMENT, PIPING, CONDUIT, AND OTHER RELATED ITEMS CAN BE OBTAINED. <br /> OWNER INSTRUCTION: CONTRACTOR SHALL INSTRUCT THE OWNER IN THE USE AND OPERATION OF ALL SYSTEMS URINAL FLUSH VALVE: SLOAN ROYAL OPTIMA 180-1 .0 ES—S, 1 .0 GPF CAPACITY, FOR 1 -1/4" TOP SPUD CONNECTION, <br /> INSTALLED UNDER THIS CONTRACT. OBTAIN OWNER'S WRITTEN ACCEPTANCE THAT THEY HAVE BEEN ADEQUATELY TRAINED. MECHANICAL INSULATION EL-154 24 VAC TRANSFORMER. . <br /> GUARANTEE: GUARANTEE MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR AFTER THE DATE OF SUBSTANTIAL A. GENERAL SIPHON JET WATER CLOSETS: AMERICAN STANDARD AFWALL 2856.128 WALL—HUNG WATER CLOSET, ELONGATED BOWL, 1 .6 <br /> COMPLETION. REFER TO ADDITIONAL REQUIREMENTS OUTLINED BY ARCHITECT AND OWNER. GPF CAPACITY, 1 -1/2" INLET SPUD, VITREOUS CHINA FIXTURE, DIRECT—FED SIPHON JET ACTION, BACK OIJTLET. <br /> � MANUFACTURERS: MANVILLE, OWENS—CORNING, CERTAINTEED, OR KNAUF. INSTALL IN ACCORDANCE WITH <br /> BASIC MATERIALS AND METHODS �APPLIES TO ALL WORK� MANUFACTURER'S INSTRUCTIONS. SIPHON JET WATER CLOSET FLUSH VALVES: SLOAN ROYAL OPTIMA 111 -1 .28 ES—S TMO, 1 .6 GPF CAPACITY, SENSOR <br /> ACTIVATED WITH TRUE MECHANICAL OVERRIDE, FOR 1 -1/2" TOP SPUD INLETS, EL-154 24 VAC TRANSFORMER. <br /> A. GENERAL INSULATION THICKNESS: REFER TO INSULATION REQUIREMENTS WASHINGTON STATE ENERGY CODE (WSEC) FOR SYSTEMS <br /> TO BE INSULATED AND THICKNESS OF INSULATION. TOILET SEATS: BEMIS 1655SSCT, OPEN FRONT, LESS COVER, ELONGATED, PLASTIC, SELF—SUSTAINING CHECK HINGES. <br /> WORK INCLUDED: THIS SECTION APPLIES TO ALL MECHANICAL WORK NORMALLY SPECIFIED UNDER DIVISIONS 21 , 22 AND <br /> 23, AND REPRESENTS REQUIREMENTS IN ADDITION TO THE REQUIREMENTS STATED IN OTHER SECTIONS. THESE B• INSULATION MATERIALS TESTING, ADJUSTING, AND BALANCING <br /> SPECIFICATIONS DO NOT COVER ALL ITEMS THAT WILL BE REQUIRED FOR COMPLETE AND WORKING SYSTEMS. WHERE TESTING AND ADJUSTING: SUBJECT SYSTEMS TO SUCH OPERATING TESTS AS ARE REQUIRED TO DETERMINE THAT THE <br /> MATERIALS OR EQUIPMENT NEEDED FOR THIS PROJECT ARE NOT COVERED IN THESE SPECIFICATIONS, PROVIDE THE INDOOR PIPE INSULATION: FIBERGLASS PIPE INSULATION WITH ALL—SERVICE (VAPOR BARRIER) JACKET SHALL BE <br /> MATERIALS AND EQUIPMENT OF A QUALITY EQUAL TO OR BETTER THAN THAT GENERALLY UTILIZED BY THE INDUSTRY FOR PROVIDED FOR ALL PIPING SYSTEMS. FITTINGS SHALL BE MITERED SECTIONS OF INSULATION WITH THE SAME THICKNESS EQUIPMENT INSTALLED WILL OPERATE PER THE SPECIFIED CAPACITY, RANGES, AND SEQUENCE OF OPERATION. SIMULATE ALL <br /> SIMILAR PROJECTS IN THE SAME GEOGRAPHIC AREA. AS ADJACENT PIPE INSULATION WITH FACTORY—PREMOLDED ONE—PIECE UL LISTED (25/50) PVC FITTING COVERS. NORMAL AND POSSIBLE ABNORMAL CONDITIONS TO VERIFY PROPER OPERATION IN ALL CONDITIONS. IF TESTS DO NOT <br /> � INSTALLATION MUST REFLECT CAREFUL WORKMANSHIP AND BE NEAT IN APPEARANCE. VAPOR BARRIER SHALL BE SEALED DEMONSTRATE SATISFACTORY SYSTEM PERFORMANCE, CORRECT DEFICIENCIES AND RETEST SYSTEMS. CONTRACTOR SHALL <br /> B. SUPPORT AND HANGERS AT ALL JOINTS ON COLD PIPING. FURNISH TO THE OWNER A SIGNED STATEMENT INDICATING THAT TESTING HAS CONFIRMED PROPER OPERATION OF ALL SYSTEMS. <br /> SUPPORT OF MECHANICAL SYSTEMS: EACH PIECE OF EQUIPMENT SHALL BE SUPPORTED (FROM ABOVE -0R BELOW) IN DOMESTIC WATER AND DRAINAGE <br /> NOT LESS THAN FOUR CORNERS FROM THE BUILDING STRUCTURE. PIPING AND DUCTWORK SHALL BE SUPPORTED AT END OF SPECIFICATION <br /> INTERVALS SPECIFIED, WITH EACH SYSTEM SUPPORTED INDEPENDENTLY FROM THE BUILDING STRUCTURE. A. PIPING SYSTEMS <br /> CONNECTIONS TO THE BUILDING STRUCTURE: PROVIDE ALL NECESSARY CONNECTIONS TO THE BUILDING STRUCTURE FOR DOMESTIC WATER PIPING: TYPE L COPPER WATER TUBE, HARD DRAWN, ASTM B 88. WROUGHT COPPER SOLDER <br /> SEISMIC RESTRAINTS AND SUPPORTS. WHERE CONCRETE STRUCTURE IS PRESENT, REVIEW THE USE OF CONCRETE FITTINGS AND SCREWED ADAPTERS, ANSI B16.22.J. LEAD FREE SOLDER; 95 PERCENT TIN, 5 PERCENT ANTIMONY <br /> � ANCHORS WITH THE ARCHITECT, OWNER, AND GENERAL CONTRACTOR, AND VERIFY THAT THERE ARE NO POST—TENSIONED SOLDER, ASTM B 32, 95TA. <br /> � OFFMAN <br /> SMALL VALVES: BALL VALVES 2" AND SMALLER. LEAD—FREE, TWO_PIECE BODY CONFORMING TO REQUIREMENTS OF W5741115 H G I N E E R S <br /> MSS SP_110; FULL PORT; SOLID BALL; BRONZE BODY; CHROME_PLATED BRASS BALL; BRASS STEM; THREADED END PHASE 1 RENOVATION PACKAGE <br /> 1101 2nd,Suite 400�Seattle,WA 98101 <br /> I FC S U B M ITTAL ph 206.623A717�fax 206.624.3775 <br /> O�.O�.^Q coffman.com <br /> I V LASTING creativity�results�ralatlonships <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> yQ . JQ.j��� ACCEPTABILITY COFFMAN 05.25.18 W5741115 0 R I G 07.02.18 <br /> ORIG WORKPLACE ENVIRONMENT INVESTMENT W5741115 CEI PJ 07.02.18 �1' oF WAsi�l``��> THIS DESIGN AND/OR CHECKED MECHANICAL SPECIFICATIONS . <br /> ���' �'��� SPECIFICATION IS APPROVED P GIN�ERS 05.25.�8 TITLE sHEET <br /> . BOE,��� �� APPROVED BY DEPT. DATE COFFMAN 05.25.18 WORKPLACE ENVIRONMENT INVESTMENT <br /> CHECKED M 2 M 3 <br /> APPROVED <br /> JOB N0. COMP N0. <br /> � ��o� �E ils8��� � BUILDIN 40-SITE W5741115 <br /> �'sSIONAL ��1� APPROVED MECHANICAL MASTER EVERETT, Wq °wc No. 40—SITE—M2 <br /> F/�R/1 R <br />