Laserfiche WebLink
17. Specify minimum header size in bearing walls. <br /> 18. Specify U-value of all new windows and doors per Table 6-1 Wa State Energy Code <br /> (WSEC). <br /> 19. Specify insulation requirements per Table 6-1 WSEC. <br /> 20. Provide lateral analysis for the front (east) wall at the lower level for wind and seismic <br /> loading prepared by a licensed Washington State structural engineer. <br /> 21. Insulation baffle in attic shall extend to a point, measured vertically, 6"above batts and <br /> 12"above loose fill insulation. Show on plans. <br /> Please prepare a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: jheilman@ci.everett.wa.us <br /> (-30 <br /> S:\1Common\Clerical\]Heilman\CW1207-001(5106 South 3rd Ave).doc <br />