Interior Lighting - Building Area Method LTG-INT-BLD
<br /> 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2,R3,R4 over 3 stories and all R1 Revised August 2016
<br /> Project Title: Enhanced Services Facilities(ESF)+Retail Date 10/13/2017
<br /> Calculation O O Addition- O Addition For Building Department Use
<br /> Area NOTE 8 stand alone +existing
<br /> O Spaces where<50%of O Spaces where z 50%of O
<br /> luminaires are replaced luminaires are replaced
<br /> LPA 0 Standard O Additional Efficiency Package Option O
<br /> Calculation C406.3 Reduced Interior Lighting Power
<br /> To comply with C406.3,the Proposed LPD shall be 25%lower than the Target LPA.
<br /> Type Refer to C406.3 for additional requirements.
<br /> Maximum Allowed Lighting WattageNOTE 1
<br /> Location(plan#, Gross Interior Allowed Watts Allowed
<br /> Building Area room#,or ALL) Area Description Area in ft2 Watts per ft2 (watts/ft2 x area)
<br /> Dormitory E211,E213,E214 ESF Facility 6786 0.46 3122
<br /> Parking garage E211 Parking Garage 5055 0.16 809
<br /> Retail E211 Retail 3013 1.01 3044
<br /> Total 14854
<br /> Proposed Lighting Wattage
<br /> Location(plan#, Number of Watts per
<br /> Building Area room#) Fixture Description NOTE 2,a,a,s Fixtures Fixture NOTE 6 Watts Proposed
<br /> Dormitory A 1x4 surface mtd,LED,1 bulb 14 39 546
<br /> Dormitory B 2x2 recessed troffer,LED,1 bulb 41 33 1353
<br /> Dormitory C Recessed downlight,LED,1 bulb 50 9 450
<br /> Dormitory C-Sleeping Units Recessed downlight,LED,1 bulb,C405.4.1 Ex.1.6 64
<br /> Dormitory D 2x4 surface mount,LED, 1 bulb 4 32 128
<br /> Dormitory E undercabinet light,LED,1 bulb 2 18 36
<br /> Dormitory F Ceiling fixture,LED,2 bulb 6 32 192
<br /> Dormitory G Ceiling fixture,LED,2 bulb 6 28 168
<br /> Dormitory H Wall sconce,LED,1 bulb 4 14 56
<br /> Dormitory I Pendant 1X4,LED, 1 bulb 3 32 96
<br /> Dormitory XA Emergency lighting,led,1 bulb,C405.4.1,Ex.1.2 7
<br /> Dormitory EX Exit sign,LED,1 bulb,C405.4.1,Ex.7 8
<br /> Parking garage A 1x4 surface mtd,LED,1 lamp 20 39 780
<br /> Parking garage C Recessed downlight,LED,1 lamp 2 9 18
<br /> Parking garage EX Exit sign,LED,1 bulb,C405.4.1,Ex.7 2
<br /> Retail A 1x4 surface mtd,LED, 1 lamp 2 39 78
<br /> Retail B 2x2 recessed troffer,LED, 1 lamp 7 33 231
<br /> Retail EX Exit sign,LED,1 bulb,C405.4.1,Ex.7 6
<br /> Compliance by Building Area NOTE 7
<br /> Total Allowed Total Proposed Interior Lighting
<br /> Building Area Warnings Watts Watts Power Allowance
<br /> Dormitory 3122 3025
<br /> Set Calculation
<br /> Area
<br /> Parking garage 809 798
<br /> Set Calculation
<br /> Area
<br /> Retail Confirm all fixtures are reported under proposed lighting-low watts 3044 309 Set Calculation
<br /> relative to maximum allowed. Area
<br /> Note 1-List all unique building areas per Table C405.4.2(1)that occur in the Totals 6 975 4132
<br /> project scope.Select building area category from drop down menu.
<br /> Note 2-Proposed fixtures must be listed in the building area in which they occur.List all proposed lighting fixtures including exempt
<br /> lighting equipment and existing-to-remain fixtures.
<br />
|