Laserfiche WebLink
PUBLIC WORKS' <br /> 11 November 2017 <br /> Owner: Todd Madison, toddmadison@hotmail.com <br /> Madison Real Property LLC <br /> Job Address: 6502 Evergreen Way <br /> Plan Check No: B1705-014 <br /> RE: Corrections recheck Letter <br /> Dear Mr. Madison, <br /> In response to the application for a building permit, the plans have been examined and you are <br /> advised that revisions may be necessary before a permit can be issued. Please review and <br /> respond to the comments below. <br /> In order for the processing of your application to continue, it will be necessary to provide the <br /> Building Division with two new sets of revised construction documents reflecting the corrections <br /> requested. Please include a response letter which indicates how the corrections were resolved. <br /> Non Structural Comments only <br /> General <br /> 10. Ducts penetrations and damper requirements will be reviewed with the mechanical <br /> submittal. <br /> Egress <br /> 1. The walls separating Staff room 106, Lounge 148 and Lounge 117 from the corridors <br /> appear to exceed the maximum permitted amount of 25% glazing (45 minute glazing). <br /> If the glazing is proposed to be one-hour— please indicate on the plans that the glazing <br /> will meet ASTM E 119 or UL236 (and provide a listing for the glazing). Section 716.6.7.1 <br /> Accessibility <br /> 1. The thresholds of showers #3 &#4 should be shown to be a maximum of 1/2 inch in <br /> height. ANSI Section 608.6 <br /> 2. Roll-in showers #3 & #4 should be shown with seats in accordance with ANSI Section <br /> 608.2.2.3. <br /> 3. The plans should clarify that an in-tub (removable) seat will be provided for Tub #2. <br /> ANSI Section 607.3 <br /> l tf <br />