Laserfiche WebLink
4. The opening into alternative roll-in shower #3 should be shown to be a minimum of 3 <br /> feet wide. ANSI Section 608.2.3 <br /> 5. The end wall of alternative roll-in shower #3 should be shown with a horizontal grab bar <br /> in accordance with ANSI Section 608.3.3 <br /> All codes cited refer to the 2015 International Building Code (IBC), the 2015 International Fire <br /> Code (IFC), the 2015 International Mechanical Code (IMC), and the 2015 Washington State <br /> Energy Code (WSEC), as amended by the State of Washington and adopted by the City of <br /> Everett. The current IBC referenced standard for accessible design is the 2009 "Accessible and <br /> Usable Buildings and Facilities" (ICC/ANSI A117.1). Federal ADA regulations and standards may <br /> be more restrictive. These comments address building issues only. Additional revisions or <br /> additions may be required by other departments (such as Utilities, Traffic, Planning or Fire). All <br /> required submittals must be of sufficient detail and information to ensure that the proposed <br /> structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Tony Lee <br /> Building Official <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425)257-8813 • Page 2 <br />