` CtS gm 14 if <br /> Chvec-Putt Commercial UVAC Loads Ca ,di' ' ion Program Elite Software Development,Inc: <br /> jAbossen Engineering <br /> Belles WA 98004; �� `',. <br /> Building Summary Loads <br /> Building peaks in August at 4pm., <br /> Bldg Lead . . Area Sen %Tot Lat Sen Net %Net <br /> Eestlrtion Quan Loss Loss Gain Gain Gain Gain <br /> Roof 0 0 0.00 0 0 0 0.00 <br /> Wall 106 343 1.99 0 167 167 0.64 <br /> Glass 94 1,706 9.90 0 7,131 7,131 27.34 <br /> Floor Slab 0 0 0.00 0 0 0 0.00 <br /> Skin Loads 2,048 11.89 0 7,298 7,298 27.98 <br /> Lighting 1,076 0 0.00 0 3,671 3,671 14.07 <br /> Equipment 2,000 0 0.00 0 6,824 6,824 26.16 <br /> People 8 0 0.00 4,360 2,440 6,800 26.07 <br /> Partition 0 0 0.00 0 0 0 0.00 <br /> Cool. Pret. 0 0 0.00 0 0 0 0.00 <br /> Heat. Pret. 0 0 0.00 0 0 0 0.00 <br /> Cool. Vent. 200 0 0.00 341 646 987 3.78 <br /> Heat. Vent. 200 11,415 66.27 0 0 0 0.00 <br /> Cool. Infil. 63 0 0.00 80 230 309 1.19 <br /> Heat. Infil. 63 3,762 21.84 0 0 0 0.00 <br /> Draw-Thru Fan 0 0 0.00 0 196 196 0.75 <br /> Blow-Thru Fan 0 0 0.00 0 0 0 0.00 <br /> Reserve Cap. 0 0 0.00 0 0 0 0.00 <br /> Reheat Cap. 0 0 0.00 0 0 0 0.00 <br /> Supply Duct 0 0 0.00 0 0 0 0.00 <br /> Return Duct 0 0 0.00 0 0 0 0.00 <br /> Misc. Supply 0 0 0.00 0 0 0 0.00 <br /> Misc. Return 0 0 0.00 .0 0 0 0.00 <br /> Building Totals 17,225 100.00 4,781 21,305 26,086 100.00 <br /> Building Sen %Tot Lat Sen Net %Net <br /> xumrnary Loss Loss Gain Gain Gain Gain <br /> Ventilation 11,415 66.27 341 646 987 3.78 <br /> Infiltration 3,762 21.84 80 230 309 1.19 <br /> Pretreated Air 0 0.00 0 0 0 0.00 <br /> Zone Loads 2,048 11.89 4,360 20,234 24,594 94.28 <br /> Plenum Loads 0 0.00 0 0 0 0.00 <br /> Fan/Duct/Misc Loads 0 0.00 0 196 196 0.75 <br /> Building Totals 17,225 100.00 4,781 21,305 26,086 100.00 <br /> CheckFigures <br /> Total Building Supply Air(based on a 23°TD): 834 CFM <br /> Total Building Vent. Air(23.97%of Supply): 200 CFM <br /> Total Conditioned Air Space: 1,076 Sq.ft <br /> Supply Air Per Unit Area: 0.7754 CFM/Sq.ft <br /> Area Per Cooling Capacity: 495.0 Sq.ft/Ton <br /> Cooling Capacity Per Area: 0.0020 Tons/Sq.ft <br /> Heating Capacity Per Area: 16.01 Btuh/Sq.ft <br /> Total Heating Required With Outside Air: 17,225 Btuh <br /> Total Cooling Required With Outside Air: 2.17 Tons <br /> J:\212158\Calc-Mech\Heat Loss&Gain Calcs\Exercise Room 144.CHV Friday,May 17,2013,07:21 PM <br />