� APPLICABLE CODES AND STANDARDS MEANS OF EGRESS: M. FORCE TO OPEN DOORS, APPLIED AT THE LATCH SIDE. (IBC 1008.1.2) FIRE EXTINGUISHERS (PER BOEING FIRE PROTECTION)
<br /> � A.THE WIDTH OF MEANS OF EGRESS SHALL BE MEASURED !N THE CLEAR AT THE NARROWEST 1) LESS THAN OR EQUAL TO 15 LBF TO OPERATE THE LATCH.
<br /> INTERNATIONAL BUILDING CODE (IBC),2012 WITH STATE OF WASHINGTON AMENDMENTS POINT OF THE EXIT C�MPONENT UNDER CONSIDERATION. PROJECTIONS WHICH DO NOT EXCEED 2) LESS THAN OR EQUAL TO 30 LBS TO SET THE DOOR IN MOTION. A. FIRE EXTINGUISHERS SHALL BE PLACED SO AS TO COMPLY WITH THE TRAVEL DISTANCE
<br /> INTERNATIONAL MECHANICAL CODE (IMC), 2012 4-INCHES ON EACH SIDE ARE PERMITTED BETWEEN THE HEIGHTS OF 27 AND 80 INCHES. 3) LESS THAN OR EQUAL TO 15 LBF TO FULLY OPEN DOOR TO MINIMUM REQUIRED WIDTH. REQUIREMENTS OF NFPA 10 FOR THE OCCUPANCY CLASSIFICATION OF THE BUILDING. FIRE
<br /> INTERNATIONAL FIRE CODE(IFC), 2012 HANDRAILS SERVING STAIRS AND RAMPS ARE PERMITTED TO PROTRUDE 4.5-INCHES FROM THE 4) LESS THAN OR EQUAL TO 5 LBF FOR INTERIOR SIDE-HINGED OR PIVOTED SWINGING DOORS EXTINGUISHERS SHALL BE OF THE RECHARGEABLE TYPE AND SHALL BE UL L.ISTED AND FM �
<br /> UNIFORM PLUMBING CODE (UPC), 2012 WALL. (IBC 1003.3.3) WITHOUT CLOSERS APPROVED.
<br /> INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2012 WITH STATE OF WASHINGTON
<br /> AMENDMENTS B. MEANS OF EGRESS SHALL BE DESIGNED AND MAINTAINED TO PROVfDE HEADROOM NOT LESS N. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE WHENEVER THE B. FIRE EXTINGUISHERS IN THE OFFICE AND SUPPORT AREAS ARE TO BE DRY-CHEMICAL FIRE
<br /> WASHINGTON ADMINISTRATIVE CODE 51-11C(WAC) THAN 7FT 6 INCHES WITH PROJECTIONS FROM THE CEILING NOT LESS THAN 6 FT 8 INCHES BUILDING IS OCCUPIED. LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY,A TOOL, EXTINGUISHERS 3A:40B:C BY AMEREX. UNITS ARE REQUIRED TO BE SIX-POUND (6 LB)UNITS
<br /> NFPA 70, NATIONAL ELECTRICAL CODE (NEC), 2011 NOMINAL HEIGHT ABOVE THE FINISHED FLOOR. THE MINIMUM CEILING HEIGHT SHALL BE OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE EGRESS SIDE, (IBC 1008.1.8) UNLESS OTHERWISE SPECIFIED AND EQUIPPED WITH MOUNTING BRACKETS AND APPROPRIATE
<br /> � NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2010 THE MAIN EXTERIOR DOORS(S)SHALL BE PERMITTED TO HAVE KEY-OPERATED LOCKS FROM THE
<br /> MAINTAINED FOR NOT LESS THAN ONE-HALF OF THE CEfLING AREA OF ANY ROOM OR SPACE (IBC DECALS. THEY SHALL BE MOUNTED AT 42 IN. AFF.
<br /> NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2010 1003.3.1). EGRESS SIDE, PROVIDED THAT THE FOLLOWING CRITERIAARE MET: (IBC 1008.1.8.3)
<br /> 1)ON OR ADJACENT TO THE DOOR ON THE EGRESS SIDE, THERE IS AREADILY VISIBLE, DURABLE C. FACTORY AREAS SHALL BE CONSIDERED MODERATE HAZARD. PROVIDE CLEAN AGENT TYPE
<br /> SIGN IN LETTERS N�T LESS THAN 1 INCH (25 MM) HIGH ON A CONTRASTING BACKGROUND (HALON 1211 OR HALOTRON 1)AND A MINIMUM 2A:10B:C RATING.
<br /> BUILDING SPECIFICS AND CONSTRUCTION REQUIREMENTS C.AN EXIT ENCLOSURE SHALL NOT BE USED FOR ANY PURPOSE THAT INTERFERES WITH ITS THAT READS AS FOLLOWS:
<br /> FUNCTION AS A MEANS OF EGRESS. (IBC 1020.1) EXIT CONSTRUCTION SHALL MEET THE FOLLOWING: THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED '
<br /> PRIMARY OCCUPANCY: SPECIAL INDUSTRIAL 1. PENETRATIONS INTO AND OPENING THROUGH AN EXIT INCLOSURE SHALL BE 2)THE LOCKWG DEVICE IS OF A TYPE THAT IS READILY DISTINGUISHABLE AS LOCKED. EXIT STAIRS
<br /> SECONDARY OCCUPANCIES: PROHIBITED EXCEPT FOR THE FOLLOWING: (IBC '1020.1,2) 3)THE USE OF THE KEY-OPERATED LOCKING DEVICE IS REVOCABLE BY THE BUILDING OFFICIAL
<br /> MISCELLANEOUS STORAGE: STORAGE OCCUPANCY, MODERATE HAZARD (S-1} IBC 311.3 a) ELECTRICAL CONDUIT SERVING THE ENCLOSURE FOR DUE CAUSE. A. PENETRATIONS INTO AND OPENING THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
<br /> OFFICE: BUSINESS OCCUPANCY(B) IBC 304 b) REQUIRED EXIT DOORS PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR
<br /> c)DUCTWORK AND EQUIPMENT SERVING THE EXIT O. STAIRS (IBC 1009, LSC TABLE 40.2.5.2.1} INDEPENDENT VENTILATION, OR PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, ELECTRICAL
<br /> d)SPRINKLER PIPING!STANDPIPES 1)MINIMUM 44 tN. WIDTH WHEN SERVING MORE THAN 50 PERSONS RACEWAY FOR FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
<br /> e) ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND TERMINATED AT A STEEL BOX NOT 2) MINIMUM 36 IN. WIDTH WHEN SERVING 50 PERSOtVS OR LESS THE INTERIOR EXIT STAIRWAY AND RAMP AND TERMINATION AT A STEEL BOX NOT TO EXCEED
<br /> MINIMUM CONSTRUCTION: TYPE II-B FULLY FIRE SPRINKLER-PROTECTED EXCEEDING 16 SQ.IN. 3} MAXIMUM RISER HEIGHT OF 7 INCHES 16 SQ.IN. SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 714.
<br /> 4) MINIMUM RISER HEIGHT OF 4 INCHES THERE SHALL BE NO PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER PROTECTED OR
<br /> ACTUAL BUILDING AREA HEIGHT AND STORIES: D.WHERE TWO EXITS OR TWO EXIT ACCESS DOORS ARE REQUIRED, THEY SHALL BE PLACED AT A 5) MINIMUM TREAD DEPTH OF 11 INCHES NOT, BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS. MEMBRANE PENETRATIONS
<br /> BUILDING AREA(GROSS) FIRST F�OOR: 1,217,869 SF DISTANCE APART EQUAL TO NOT LESS THAN 1/3 THE MAXIMUM OVERALL DIAGONAL DIMENSION OF 6) MAXIMUM VERTICAL RISE BETWEEN LANDINGS OF 12 FEET SHALL BE PERMITTED ON THE OUTSIDE OF THE INTERIOR EXIT STAIRWAY AND RAMP. SUCH
<br /> BUILDING AREA(GROSS)MEZZANINE: 50,848 SF THE SPACE(FULLY SPRINKLER PROTECTED). (IBC 1015.2.1) MINIMUM NUMBER OF SEPARATE
<br /> PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 714.3.2. (IBC 1022.5)
<br /> BUILDING AREA(GROSS) SECOND MEZZANINE: 94,007 SF MEANS OF EGRESS: (IBC TABLE 1019.1 AND LSC TABLE 7.4.1.2} P. HANDRAILS AND GUARDRAILS
<br /> BUILDING AREA(GROSS)THIRD MEZZANWE: 94,007 SF 1-500 OCCUPANTS:2 EXITS 1)STAIRS ANp RAMPS WITH A RISE GREATER THAN 6 INCHES SHALL HAVE HANDRAILS ON BOTH B. EQUIPMENT AND DUCTWORK FOR INTERIOR EXIT STAIRWAY AND RAMP VENTILATION AS
<br /> BUILDING HEIGHT: 104'-6" 500-1000 OCCUPANTS: 3 EXITS SIDES. (IBC 1009.15 AND 1010.9) PERMITTED BY SECTION 1022.5 SHALL COMPLY WITH ONE OF THE FOLLOW ITEMS (IBC 1p22.6):
<br /> OVER 1000 OCCUPANTS: 4 EXITS 2) HANDRAILS SHALL BE PROVIDED WITHIN 30 INCHES OF ALL PORTIONS OF THE STAIR WIDTH 1) SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED EXTERIOR TO THE BUILDING AND
<br /> ALLOWABLE BUILDING AREA AND HEIGHT: REQUIRED FOR EGRESS CAPACITY, (IBC 1012.9) SHALL BE DIRECTLY CONNECTED TO THE INTERIOR EXIT STAIRWAY AND RAMP BY
<br /> SPECIAL INDUSTRIAL OCCUPANCIES: BUILDING AND STRUCTURES DESIGNED TO HOUSE SPECIAL E. EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR OF THE BUILDING, UNLESS OTHERWISE 3)THE HEIGHT OF HANDRAILS AND GUARDS SHALL BE MEASURED VERTICALLY TO THE TOP OF DUCTWORK ENCLOSED IN CONSTRUCTION AS REQUIRED FOR SHAFTS.
<br /> INDUSTRIAL PROCESSES THAT REQUIRE LARGE AREAS AND UNUSUAL BUILDING HEIGHTS TQ PERMITTED BY IBC SECTION 1024.1. THE EXIT DISCHARGE SHALL BE AT GRADE OR SHALL THE GUARD OR RAIL FORM THE WALING SURFACE ADJACENT THERETO. (IBC 1012) 2)WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN THE INTERIOR�XI'T ST'AIRWAY
<br /> ACCOMMODATE CRANEWAYS OR SPECIAL MACHINERY AND EQUIPMENT SHALL BE EXEMPT FROM THE PROVIDE DIRECT ACCESS TO GRADE. THE EXIT DISCHARGE SHALL NOT REENTER BUILDING. (IBC 4) HANDRAIL SHAPE: CIRCULAR CROSS SECTION WITH OUTSIDE DIAMETER GREATER THAN OR AND RAMP, THE INTAKE AIR SHALL BE TAKEN DIRECTLY FROM THE OUTDOORS AND THE
<br /> � BUILDING HEIGHT AND AREA LIMITATIONS OF TABLE 503. (IBC 503.1,1) 1024.1) EQUAL TO 1-1/4 IN AND LESS THAN OR EQUAL TO 2 IN. OR NON-CIRCULAR CROSS EXHAUST AIR SHALL BE DISCHARGED DIRECTLY TO THE OUTDOORS OR SUCH AIR SHALL •
<br /> . SECTION WITH PERIMETER GREATER THAN OR EQUAL TO 4 IN.AND LESS THAN OR EQUAL BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS REQUIRED FOR SHAFTS
<br /> ALLOWABLE BUILDING AREA: UNLIMITED F. OCCUPANT LOAD SHALL BE CALCULATED BASEQ ON APPLICATION OF THE GROSS OR NET TO 6-1i4 IN.AND LARGEST CROSS SECTION LESS THAN OR EQUAL TO 2-1/4 IN WITH 3)WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT AND DUCTWORK SHALL BE
<br /> ALLOWABLE BUILDING HEIGHT: UNLIMITED FLOOR AREA FACTORS OR THE ACTUAL NUMBER OF OCCUPANTS FROM WHOM EACH OCCUPIED ROUNDED EDGE RADIUS GREATER THAN OR EQURL TO 118 IN. (IBC 1012.3) SEPARATED FROM THE REMAINDER OF THE BUILDWG, INCLUDING OTHER MECHANICAL
<br /> ALLOWABLE NUMBER OF STORIES; 3 SEE; IBC, TABLE 503, MODIFICATION PER(504.2) SPACE IS DESIGNED,WHICHEVER IS GREATER. (!BC TABLE 1004.1.2 AND LSC TABLE 7.3.1.2) 5} HANDRAIL HEIGHT GREATER THAN OR EQUAL TO 34 IN.AND LESS THAN OR EQUAL TO 38 IN. EQUIPMENT, WITH CONSTRUCTION AS REQUIRED FOR SHAFTS. IN EACH CASE, OPENING
<br /> ACTUAL NUMBER OF STORIES: 1 ABOVE THE SURFACE OF THE TREAD, MEASURED VERTICALLY FROM THE TOP OF THE RAIL INTO THE FIRE-RESISTANCE-RATED CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED
<br /> OCCUPANCY LOAD FACTpRS: `'� FROM THE LEADING EDGE OF THE TREAD.A CLEARANCE OF NOT LESS THAN 2-1/4 IN.
<br /> FOR MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY OPENING PROTECTIVES
<br /> OCCUPANCY OCCUPANT LOAD FACTOR SHALL BE PROVIDED BETWEEN RAIL AND WALL (LSC 7.2.2.4.4.5) IN ACCORDANCE WITH SECTION 716 FOR SHAFT ENCLOSURES.THE INTERIOR EXIT
<br /> ACTIVE FIRE PROTECTION SYSTEMS , (SQ.FT./PERSON) 6) HANDRAIL-GRIPPING SURFACES SHALL BE CONTINUOUS, WITHOUT INTERRUPTION BY NEWEL
<br /> STAIRWAY AND RAMP VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER BUILDING
<br /> BUSINESS 100 GROSS POSTS OR OTHER OBSTRUCTIONS. (IBC 1012.4) VENTILATION SYSTEMS.
<br /> COMPLETE AUTOMATIC SPRINKLER PROTECTION SHALL BE PROVIDED. (IBC 903.2.4) STORAGE/MECHANICAL 300 GROSS 7) HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR SHALL BE
<br /> PORTABLE FIRE EXTINGU[SHERS SHALL BE INSTALLED PER IFC, NFPA 10,AND BOEING FIRE SPECIAL INDUSTRIAL AREAS 300 GROSS* CONTINUOUS TO THE HANDRAI�OF AN ADJACENT STAIR FLIGHT-0R RAMP RUN.AT Q •
<br /> PROTECTION. (IFC 906) NON-CONCENTRATED ASSEMBLY 15 NET STAIRWAYS WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS MEZZ�'?:!l�'�=
<br /> SHALL EXTEND HORIZONTALLY AT LEAST 12 IN. BEYOND THE TOP RISER AND CONTINUE TO
<br /> *THE OCCUPANT LOAD FACTOR OF 300 GROSS IN SPECIAL INDUSTRIAL AREA SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. (IBC 1012.5) 1)A ME7IANINE OR MEZZANINES IN COMPLIANCE WITH SECTION 505 SHALL BE CONSIDERED A
<br /> PASSIVE FIRE PROTECTION SYSTEMS IS PER AGREEMENT WITH THE CITY OF EVERETT. 8)GUARDS ARE REQUIRED TO PREVENT FALLS OVER THE OPEN SIDE WHEN MEANS OF EGRESS IS PORTION OF THE STORY IN WHICH IT IS CONTAINED. SUCH MEZZANINES SHALL NOT CONTRIBUTE TO
<br /> �� MORE THAN 30 IN.ABOVE FLOOR OF GRADE BELOW. (IBC 1013.1) EITHER THE BUILDING AREA OR NUMBER OF STORIES AS REGULATED BY SECTION 503.1. THE AREA OF
<br /> G. EGRESS CAPACITY FOR APPROVED COMPONENTS OF MEANS OF EGRESS SHALL BE BASED ON � THE MEZZANINE SHALL BE INCLUDED IN DETERMINING THE FIRE AREA DEFINED IN SECTION 902. THE
<br /> EXTERIOR WALLS SHALL HAVE A FIRE RESISTANCE AND OPENING PROTECTION RATWG AS SET 9)GUARDRAIL HEIGHT MINIMUM:42 IN. (IBC 1013.2) CLEAR HEIGHT ABOVE AND BELOW THE MEZZANINE FLOOR CONSTRUCTION SHALL NOT BE LESS
<br /> FORTH IN TABLES 601 AND 602 OF THE IBC AND IN ACCORDANCE WITH SUCH ADDITIONAL THE FOLLOWING FOR A FULLY SPRINKLER-PROTECTED FACILITY: (IBC 1005.3.1, 1005.3.2 AND LSC 10)OPEN GUARDS SHALL HAVE BALUSTERS OR ORNAMENTAL PATTERN TO PREVENT 4 IN. THAN 7 FEET (lBC 505.1).
<br /> PROVISIONS AS SET FORTH IN CHAPTER 6. DISTANCES SHALL BE MEASURED AT RIGHT ANGLES TABLE 7.3.3.1) DIAMETER SPHERE FROM PASSING THR4UGH ANY OPENING UP TO A HEIGHT OF 34 INCHES. 2)THE AGGREGATE AREA OF A MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED ONE-
<br /> FROM THE PROPERTY LINE. THE ABOVE PROVISIONS SHALL NOT APPLY TO WALL AS RIGHT ANGLES L�VEL COMPONENTS: 0.20 IN.7 PERSON FROM 34 INCHES TO 42 INCHES ABOVE THE WALKING SURFACES,A SPHERE 4-3/8 THIRD OF THE FLOOR AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE LOCATED.THE ENCLOSED
<br /> TO THE PROPERTY LINE. BUILDING LOCATED ON THE SAME PROPERTY SHALL BE ASSUMED TO STAIR COMPONENTS: 0.30 IN./PERSON INCHES IN DIAMETER SHALL NOT pASS. (IBC 1013.3-4) EXCEPTION:THE TRIANGULAR PORTION OF A ROOM SHALL NOT BE INCLUDED IN A DETERMINATION OF THE FLOOR AREA OF THE
<br /> HAVE A PROPERTY LINE BETWEEN THEM. *AT THE GROUND LEVEL, AN ALTERNATE MEANS OF COMPLIANCE IN ACCORDANCE WITH OPENINGS FORMED BY THE RISER, TREAD,AND BOTTOM ELEMENT OF A GUARDRAIL AT THE ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING THE ALLOWAB�E MEZZANINE AREA, ,
<br /> SECTION 104.11 OF THE BUILDING CODE HAS BEEN PROVIDED. THE AREA OF THE MEZZANINE SHALL NOT BE INCLUDED IN THE FLOOR AREA OF THE ROOM. (IBC
<br /> A PERFURMANCE BASED DESIGN WAS PROVIDED WITH THE USE OF EGRESS MODELING OPEN SIDE OF A STAIR SHALL BE OF SUCH SIZE THAT A SPHERE 6 INCHES IN DIAMETER 505.2).
<br /> CONSTRUCTION TYPE II-B TO DEM(JNSTRATE THE PROVIDED EXIT CAPACITY IS SUFFICIENT SHALL NOT PASS THROUGH THE TRIANGULAR OPENING. EXCEPTION: IN AREAS THAT ARE NOT
<br /> OPEN TO THE PUBLIC WITHIN �CCUPANCIES F AND FOR ALTERNATING TREAD DEVICES AND 3)A MEZZANINE SHALL BE OPEN AND UNOBSTRUCTED TO THE ROOM IN WHICH SUCH MEZZANINE IS
<br /> LOCATED EXCEPT FOR WALLS NOT MORE THAN 42 INCHES HIGH, COLUMNS AND POSTS. (IBC 505.4)
<br /> TYPE II CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN WHICH THE BUiLDING ELEMENTS H. EXIT 1"RAVEL DISTANCES � SHIP LADDERS, GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE EXCEPTIONS:
<br /> LISTED IN TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS PERMITTED IN IBC 21 INCHES IN DIAMETER. 1) MEZZANINES OR PORTIONS THEREOF ARE NOT REQUIRED TO BE OPEN TO THE
<br /> 1)FOR TOWER LEVELS AND GROUND LEVEL SPECIAL INDUSTRIAL OCCUPANCY,A PERFORMANCE ROOM IN WHICH THE MEZZANINES ARE LOCATED, PROVIDED THAT THE OCCUPANT
<br /> � SECTION 603 AND ELSEWHERE IN THE IBC.(IBC 602.2) �ASED DESIGN WAS USED IN LIEU OF PRESCRlPTIVE CODE TRAVEL DISTANCES AS PERMITTED BY Q. EXIT SIGNS LOAD OF THE AGGREGATE AREA OF THE ENCLOSED SPACE DOES NOT EXCEED 10.
<br /> 104.11 OF THE IBC.AN EVALUAT(ON INCLUDING EGRESS MODELING WAS PREFORMED TO 2)A MEZZANINE HAVING TWO OR MORE MEANS OF EGRESS IS NOT REQUIRED TO BE
<br /> FIRE RESISTANCE REQUIREMENTS C)EMONSTRATE THE TRAVEL D�STANCES IDENTIFIED ARE ACCEPTABLE. 1) EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED SIGN READILY VISIBLE OPEN TO THE ROOM IN WHICH THE MEZZANINE IS LOCATED IF AT LEAST ONE OF THE
<br /> FROM ANY DIRECTION OF EXIT TRAVEL. (IBC 1011.1) MEANS OF EGRESS PROVIDES DIRECT ACCESS TO AN EXIT FROM THE MEZZANINE
<br /> 2 IN GROUP S-1 OCCUPANCY PROTECTED THROUGHOUT BY AN APPROVED SUPERVI ED LEVEL.
<br /> _ ) , S
<br /> TYPE II B CONSTRUCTION STRUCTURAL ELEMENT FIRE RESISTANCE REQUIREMENTS 2)ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY VISIBLE SIGNS IN CASES WHERE 3) MEZZANINES OR PORTIONS THEREOF ARE NOT REQUIRED TO BE OPEN TO THE
<br /> (IBC TABLE 601) P�UTOMATIC SPRINKLER SYSTEM, THE TRAVEL DISTANCE SHALL NOT EXCEED 250 FEET THE EXIT OR THE PATH OF EGRESS TRAVEL IS NOT READILY APPARENT TO THE OCCUPANTS. ROOM IN WHICH THE MEZZANWES ARE LOCATED PROVIDED THAT THE AGGREGATE �
<br /> 3) IN GROUP B, F,AND S OCCUPANCY PROTECTED THROUGHOUT BY AN APPROVED,
<br /> FLOOR AREA OF THE ENCLOSED SPA E D
<br /> �,
<br /> EXIT SIGN PLACEMENT SHALL BE SUCH THATNO POWT IN THE EXIT ACCESS CORRIDOR IS
<br /> C OES NOT EXCEED 10 PERCENT OF THE
<br /> ,.�UPERVISED AUTOMATIC SPRINKLER SYSTEM COMMON PATHS OF TRAVEL SHALL NOT EX E D MEZZANINE AREA.
<br /> C E
<br /> ' MORE THAN 100 FT. FROM THE NEAREST EXTERNALLY ILLUMINATED SIGN AND IS NOT IN
<br /> 4 IN INDUSTRIAL FACILITIES MEZZANINES USED FOR ONTR L E
<br /> 100 FT. IBC 1014.3 LSC TABLE 40.2.5
<br /> ) , C O QUIPMENT ARE
<br /> � ' � EXCESS OF THE MARKED RATING FOR INTERNALLY ILLUMINATE SIGNS. (IBC 1011.1) ED N ALL SIDES.
<br /> STRUCTURAL ELEMENT FIRE RESISTANCE RATING HR. 4 WHERE MORE THAN ONE EXIT OR EXIT ACCESS D ORWAY i
<br /> ) O S REQUIRED THE EXIT
<br /> � � � 5) IN OCCUPANCIES OTHER THAN GROUPS H AND I, THAT ARE NO MORE THAN TWO
<br /> A,CCESS SHALL BE ARRANGE SUCH THAT THERE ARE NO DEAD ENDS IN CORRIDORS MORE 3) EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS SHALL BE LEGIBLE IN BOTH THE NORMAL AND STORIES ABOVE GRADE PLANE AND EQUIPPED THROUGHOUT WITH AN AUTOMATIC
<br /> EMERGENCY LIGHTING MODE. (IBC 1011.5) SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1,A MEZZANINE HAVING
<br /> PRIMARY STRUCTURAL FRAME 0 THAN 20 FEET IN LENGTH. (IBC 1018.4) TWO OR MORE MEANS OF EGRESS SHALL NOT BE REQUIRED TO BE OPEN TO THE
<br /> INTERIOR BEARING WALLS 0 5) IN BUIL�INGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC INTERIOR FINISH RATINGS ROOM IN WHICH THE MEZZANINE IS LOCATED.
<br /> EXTERIOR BEARING WALLS AND PARTITIONS p �PRINKLER SYSTEM, DEAD-END CORRIDORS IN GROUP F, S AND B OCCUPANCIES SHALL
<br /> FLOOR CONSTRUCTION AND ASSOCIATED MEMBERS 0 �IOT EXCEED 50 FT. (IBC 1018.4, EXCEPTION 2) 4)VERTICAL OPENINGS BETWEEN A MEZZANINE COMPLYING WITH SECTION 505 AND THE
<br /> INTERIOR WALL AND CEILING FINISH MATERIALS FOR SPRINKLER-PROTECTED GROUP B FLOOR BELOW SHALL BE PERMITTED (IBC 712.1.10) EXIT STAIR ENCLOSURES HAVE BEEN
<br /> ROOF CONSTRUCTION AND ASSOCIATED MEMBERS 0 OCCUPANCIES SHALL BE MINIMUM CLASS B IN EXIT ENCLOSURES AND PASSAGEWAYS AND CLASS PROVIDED.
<br /> TYPE II-B CONSTRUCTION EXTERIOR WALL RATING (IBC TABLE 602 I. MINIMIJM CLEAR WIDTH OF MEANS OF EGRESS DOORS SHALL BE 32 INCHES. (IBC 1008.1.1) �
<br /> ) C IN CORRIDORS AND ROOMS AND ENCLOSED SPACES AS DEFINED IN ACCORDANCE WITH ASTM
<br /> E84, I.E. FLAME SPREAD 76-200, SMOKE DEVELOPED 0-450. (IBC TABL.�803.5)
<br /> J. DOOR ASSEMBLIES IN FIRE BARRIERS SHALL BE ON AN APPROVED TYPE WITH APPROPRIATE
<br /> PERFORMANCE BASED STUDIES
<br /> FIRE PROTECTION RATING FOR THE LOCATION IN WHICH INSTALLED AND SHALL COMPLY WITH THE Q
<br /> FIRE SEPARATION DISTANCE (FT.) FIRE RESISTANCE RATING (HR.) FOLLOWING: SM�KE AND HEAT VENTS �
<br /> 1) DESIGN STUDY FOR SMOKE MANAGEMENT AT BOEING BUILDING 40-58, EVERETT WASHINGTON,
<br /> 1)FIRE DOORS SHALL BE INSTALLED IN ACCORDANCE WITH IBC 715 AND NFPA 80, AUGUST 15, 2014. HUGHES ASSOCIATES, INC. LAKE MARY, FL.
<br /> GREATER THAN 30 FT. � BTANDARD FOR FIRE DOORS AND WfNDOWS. (IBC 715.4) IN ACCORDANCE WITH 104.11 OF THE IBC, "ALTERNATIVE MATERIALS, DESIGNAND METHOD OF 2) EVACUATION MODELING OF BOEING BUILDING 40-58 USING BUILDINGEXODUS SOFTWARE.
<br /> 2) FIRE DOORS SHALL BE OF A DESIGN THAT HAS BEEN TESTED TO MEET THE CONDITIONS CONSTRUCTIOM'A SMOKE MANAGEMENT STUDY HAS BEEN PERFORMED IN LIEU OF PROVIDING OCTOBER 8, 2014. HUGHES ASSOCIATES, INC. LAKE MARY, FL.
<br /> OCCUPANCY SEPARATION REQUIREMENTS: C)F ACCEPTANCE OF NFPA 252, STANDARD METHODS OF FIRE TESTS OF DOOR ASSEMBLIES. SMOKE AND HEAT VENTS. (IBC SECTION 910.2.1 REQUIRES SMOKE AND HEAT VENTS)
<br /> F-1 TO S-1: NO SEPARATION REQUIREMENT
<br /> (IBC 715)
<br /> F-1 TO B: NO SEPARATION REQUIREMENT 3) UNLESS OTHERWISE SPECIFIED, FIRE DOORS SHALL BE SELF-CLOSING OR
<br /> S-1 TO B: NO SEPARATION REQUIREMENT AUTOMATIC-CLOSING. (IBC 715.4.7) '
<br /> K. DOORS SHALL SWING IN THE DIRECTION OF EGRESS WHEN SERVING 50 OR MORE OCCUPANTS
<br /> � OR A GROUP H OCCUPANCY UR IN AN EXIT ENCLOSURE. (IBC 1008.1.2)
<br /> L. DURING ITS SWING,ANY DOOR IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ■ �� y .
<br /> ONE-HAL_F OF THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING � �n` H U G H E S BAN
<br /> UNOBSTRUCTED AND SHALL NOT PROJECT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN �� �� R��S �d�� i.%''
<br /> � �� ASSOCIATES °�� � - NIN ��
<br /> AISLE, CQRRIDOR, PASSAGEWAY OR LANDING WHEN FULLY OPEN. (IBC 1008.1.5) ,��,� �;;,° _,.,� c�,
<br /> �'r f 6 � 2
<br /> FIRE PROTECTION S� CODE C 4 N S U L T I N G
<br /> 725 PRIMERA BLVD � SUITE 215 "``� � .
<br /> LAKE MARY � F�ORIDA � 32746 900 SW 16th Street Suite 307 of,�!'ct,stti�'� �'4�
<br /> P 407.647.3737 � F 407.647.4929 f •�r, ��
<br /> www.haifire.com RCIlt011� Washington 98057 , 'sslov�,t��
<br /> Project: 1 HRB00390 ' n.
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE W a s ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE ,�o,
<br /> oF y CGB 10130114 LIFE SAFETY NOTES � `�
<br /> 0 ISSUE FOR CONSTRUCTION CGB HRB 10I09114 P� �N�r THIS DESIGN AND/OR CHECKED W25483�� 10/30/14 �
<br /> 5 � SPECIFICATION IS APPROVED CGB 10I30114 SHEET �r
<br /> �o�,�� BRPH ARCHITECTS ENG I NEER TITLE `O
<br /> �cGNeERsiNc. BOEING 777X CWC BUILDING �
<br /> 1 REVISION-RELEASE 1 CGB HRB 10I30/14 � APPROVED BY DEPT. DATE HRB 10I30114 ti
<br /> N0.3137 CHECKED AL 1 N
<br /> � BUILDING 40-58 �
<br /> P�F �o APPROVED Jpg NO. COMP N0. 00
<br /> /c�TF OF AUTN��\�P APPROVED 4O-5H-AL� v
<br /> - � ARCHITECTURAL MASTER EVERETT, WA °wc No. 40-58-AL1 '