Laserfiche WebLink
SNO ISLE PUBLICATIONS <br /> 30 DAY PEAK DEMAND CALCULATION WORKSHEET <br /> PANEL 'DG' <br /> NEC 220.87 AND WAC 296-46B-900(3)(j) <br /> 30-day demand study from : 2/20/2019 to 3/21/2019, <br /> Phase to Phase Voltage (Volts) : 208 <br /> Phases (1=Single Phase, 3=Three Phase) : 3 <br /> 30 Day Peak Demand On : 2/22/2019 = 64.13 Amps <br /> Apparent Peak Demand = 23.10 KVA <br /> NEC 220.87(2) adjustment factor X 1.25 KVA <br /> Adjusted Peak Demand = 28.88 KVA <br /> Seasonal adjustment factor X 1.00 KVA <br /> Seasonal adjustment peak demand = 28.88 KVA <br /> Occupancy adjustment factor X 1.00 KVA <br /> Occupancy adjustment peak demand = 28.88 KVA <br /> Other adjustement factor(s) X 1.00 KVA <br /> Measured Peak Demand with Adjustments = 28.88 KVA <br /> New Calculated Demand Load Added Publication + 5.16 KVA <br /> Metered Demand Based <br /> CALCULATED DEMAND LOAD : 34.04 KVA <br /> CALCULATED DEMAND CURRENT : 94 AMPS <br /> Note: See WAC 296-46B-900 (3)(j)for additional metering requirements <br />