Laserfiche WebLink
If the Engineer suspects that damage to any loop, not identified in the Plans as being <br /> replaced, may have resulted from Contractor's operations or is not operating adequately, <br /> the Engineer may order the Contractor to perform the field tests specified in Section 8 <br /> 20.3(14)D. The test results shall be recorded and submitted to the Engineer. Loops that <br /> fail any of these tests shall be replaced. <br /> Loops that fail the tests, as described above, and are replaced shall be installed in <br /> accordance with current WSDOT design standards and Standard Plans, as determined <br /> by the Engineer. <br /> If traffic signal loops that fail the tests, as described above, are not replaced and <br /> operational within 48 hours, the Contractor shall install and maintain interim video <br /> detection until the replacement loops are operational. The type of interim video <br /> detection furnished shall be approved by the Engineer prior to installation. <br /> 8-20.3(14)C Loop Sealant <br /> Loop sealants shall be installed per manufacturer's recommendations. <br /> 3M Black 5000 sealant shall be installed so that the sealant is protected from wheel <br /> tracking prior to the sealant being fully cured. When 3M Black 5000 loop sealant is <br /> installed below the final lift of an HMA installation, a minimum of 5 consecutive days of <br /> cure time is required before the final lift is installed. <br /> 8-20.3(14)D Test for Induction Loops and Lead-in Cable <br /> Section 8-20.3(14)D is supplemented with the following: <br /> Induction Loop Tests <br /> Test A and Test D are revised as follows: <br /> Test A—The DC resistance between the 2 lead-in cable wires, including the loop, shall <br /> be measured by a volt ohmmeter. The resistance shall not exceed 5-ohms or lower the <br /> Q of the circuit below 5 where Q is equal to the "Inductive Impedance @ 50 kHz" divided <br /> by "Resistance". <br /> Test D - An inductance test shall be made to determine the inductance level of each <br /> inductance loop. The Contractor shall record the inductance level of each inductance <br /> loop installed on the project and shall furnish the findings to the Engineer. An induction <br /> level, as measured from the controller cabinet, below 50-microhenries is considered a <br /> failure. <br /> Existing Lead-in Cable Test <br /> When new induction loops are scheduled to be installed and spliced to an existing two- <br /> conductor shielded detector lead-in cable, the Contractor shall perform the following: <br /> 1. Disconnect the existing detector lead-in cable in the controller cabinet and at the <br /> loop splice. <br /> 2. Megger test both detector lead-in cable conductors. A resistance reading of less <br /> than 100-megohms is considered a failure. <br /> 3. Detector lead-in cables that fail the test shall be replaced and then retested. <br /> 4. After final testing of the detector lead-in cable, the loop installation shall be <br /> completed and the loop system tested according to Tests A, C and D. <br /> Swift Green Line—Corridor Stations Special Provisions SP137 <br /> May 2017 <br />