Laserfiche WebLink
r y <br /> 3. There are numerous can lights penetrating the one hour floor/ceiling and roof/ceiling <br /> assemblies. The lights should be surface mounted unless shown to comply with one of <br /> the exceptions to Section 714.4.2 <br /> 4. The western handrail on the North Stair should extend a minimum of 12" past the top of <br /> the highest riser. As this is an existing stair opening with limited ability to adjust the <br /> stairway, it may be more practical to continue the handrail around the wall as if the <br /> stairway were continuous between adjacent flights. Section 1014.6 <br /> 5. The location and nomenclature of the maximum occupant load signs for the assembly <br /> spaces should be shown on the plans. Section 1004.3 <br /> 6. A sign stating Exit in raised characters and braille and complying with ICC A117.1 should <br /> be shown adjacent to the exterior exit doorways and Door 203A. Section 1013.4 <br /> In order for the processing of your application to continue, it will be necessary to provide the <br /> Building Division with two new sets of revised construction documents reflecting the corrections <br /> requested. Please include a response letter which indicates how the corrections were resolved. <br /> All codes cited refer to the 2015 International Building Code (IBC),'2015 International Existing <br /> Building Code (IEBC), the 2015 International Fire Code (IFC), the 2015 International Mechanical <br /> Code (IMC), and/or the 2015 Washington State Energy Code (WSEC), as amended by the State <br /> of Washington and adopted by the City of Everett. The current IBC referenced standard for <br /> accessible design is the 2009 "Accessible and Usable Buildings and,Facilities" (ICC/ANSI <br /> A117.1). Federal ADA regulations and standards may be more restrictive. <br /> These comments address building issues only. Additional revisions or additions may be required <br /> by other departments (such as Utilities, Traffic, Planning or Fire). All required submittals must <br /> be of sufficient detail and information to ensure that the proposed structure will be constructed <br /> in compliance with all adopted codes. <br /> Sincerely, <br /> Tony Lee <br /> Building Official <br /> ({� 3002 Wetmore Ave. 0 425.257.8400 ( \ }. PDieverettwa.gov <br /> C�� F,verett,WA 98201 425.257.8401 fax <br /> everettwa.gov <br />