Laserfiche WebLink
A <br /> 3. There are numerous can lights penetrating the one hour floor/ceiling and <br /> roof/ceiling assemblies.The lights should be surface mounted unless <br /> shown to comply with one of the exceptions to Section 714.4.2 <br /> Response: Recessed downlights have been changed to surface- <br /> mounted downlights. See sheet A201. <br /> 4. The western handrail on the North Stair should extend a minimum of 12" <br /> past the top of the highest riser.As this is an existing stair opening with <br /> limited ability to adjust the stairway, it may be more practical to continue the <br /> handrail around the wall as if the stairway were continuous between <br /> adjacent flights. Section 1014.6 <br /> Response: Due to the limitations of the existing stair opening,the <br /> handrail extension has been wrapped around the wall. See sheet <br /> A401. <br /> 5. The location and nomenclature of the maximum occupant load signs for the <br /> assembly spaces should be shown on the plans. Section 1004.3 <br /> Response: This requirement has been noted on the level 2 Life Safety <br /> Plan on sheet G001, and on the Level 2 Floor Plan on sheet A101. <br /> 6. A sign stating Exit in raised characters and braille and complying with ICC <br /> A117.1 should be shown adjacent to the exterior exit doorways and Door <br /> 203A. Section 1013.4 <br /> Response: This requirement has been noted on the Life Safety Plans <br /> on sheet G001, and on the Floor Plans on sheets A101 and A102. <br /> ,t <br /> Andrew Stewart <br />