7. Specify header size, species and grade in all bearing walls (interior and exterior). Show on <br /> plans. <br /> 8, Provide detail(s) of roof construction including collar tie connections, rafter to top plate <br /> connection, vented blocking, show minimum 1 inch clear air space over insulation, ridge <br /> beam size, species and grade. <br /> 9. Provide attic ventilation calculation. Show location and size of all attic ventilation. <br /> 10.The duplex outlets shown on the plans do not meet the minimum requirements of the <br /> electrical code. <br /> 11. The Existing "Roof Chimney"is not shown on the elevation drawings. Please define the <br /> function of the Roof Chimney. <br /> 12. Provide"Typical Wall Section"showing all components (new and existing). <br /> 13. The structure as shown does not meet the prescriptive requirements for lateral bracing per <br /> section R602.10 IRC. Provide lateral analysis prepared by a licensed WA State Engineer. <br /> 14. Section CC on sheet _ (pages not numbered) does not match the floor plan shown on <br /> sheet . Please revise section drawing to match floor plan. <br /> 15. The floor plan does not match the structure shown on the site plan. Please revise for <br /> consistency. <br /> 16. Show how water heater is accessed. <br /> 17.Specify tempered safety glass in windows installed in hazardous locations as defined in <br /> section R308 IRC. Show on plans. <br /> 18. Provide minimum 50 CFM exhaust fan in laundry closet. Show on plans. <br /> 19. Specify all window and door sizes on plans. <br /> 20. The proposed Electric Heat Pump shown on the floor plan, shall not be located in the public <br /> right-of-way (site plan shows the building on the property line). The site plan does not <br /> show the location of the heat exchanger. Provide location of the heat exchanger on the Site <br /> Plan for Planning department review. <br /> If you have any questions, please email or call me at (425) 257-8976. Upon submittal of the <br /> drawings, your application will be given priority and plan reviews will recommence. All required <br /> submittals shall be sufficient detail and contain sufficient information to ensure that the propos:-,' <br /> structure will be constructed in compliance with all adopted codes,. <br /> Please prepare a response letter showing where each item in this correction <br /> letter is addressed on the plan set. <br /> ',Page <br /> 2 of ....:'' <br /> t -r r. 3200 Cedar Street • Everett, WA 98201 • (475) 257-8810_•-Fax (4251 2S7-R c7 st <br />