• <br /> • <br /> MODULE SPECIFICATION DC CONDUCTOR AMPACITY CALCULATIONS <br /> MANUFACTURER SILFAB ARRAY TO JUNCTION BOX(CEC ART 310.15) <br /> A EXPECTED WIRE TEMPERATURE(FREE AIR) 30 CELSIUS <br /> MODEL NO. SLA-M 300 ADD 22°C OR 40°F FOR CONDUITS EXPOSED TO <br /> PEAK POWER 300W B SUNLIGHT ON OR ABOVE ROOF 52 CELSIUS <br /> TEMPERATURE CORRECTION FACTOR 0.76 <br /> RATED VOLTAGE(VMP) 32.8 V CEC TABLE 310.15(B)(2)(A) <br /> RATED CURRENT(IMP) 9.16 A C #OF CURRENT CARRYING CONDUCTORS 4 <br /> 0.80 .80(FOR 4 TO 6 CONDUCTORS IN CONDUIT) OR 1.00(FOR 3 OR LESS CONDUCTORS IN CONDUIT) <br /> D CONDUIT FILL CORRECTION <br /> OPEN CIRCUIT VOLTAGE(Voc) 39.85 VNEC TABLE 310.15(B)(3)(A) 'StTort energy today* <br /> SHORT CIRCUIT CURRENT(Isc) 9.71 A E CIRCUIT CONDUCTOR SIZE #10 AWG 7 <br /> F CIRCUIT CONDUCTOR AMPACITY 40 AMPS NEC TABLE 310.15(B)(16) <br /> G REQUIRED CIRCUIT CONDUCTOR AMPACITY 15.0 AMPS REQUIRED CIRCUIT CONDUCTOR AMPACITY=MAXIMUM OPTIMIZER OUTPUT CURRENT(AMPS)(FROM OPTIMIZERS <br /> OPTIMIZER SPECIFICATION SPECIFICATIONS) <br /> H DERATED AMPACITY OF CIRCUIT CONDUCTOR 24.32 AMPS TEMPERATURE CORRECTION X CONDUIT FILL CORRECTION X CIRCUIT CONDUCTOR AMPACITY <br /> OPTIMIZER MAKE SOLAREDGENEC TABLE 310.15(B)(2)(A) <br /> OPTIMIZER MODEL NO. P320 NOTE:"H"MUST BE LARGER THAN"G" 24.3A > 1 5.OA=OK ;, <br /> MAXIMUM INPUT DC POWER 320 W <br /> ,,i <br /> si I <br /> ABSOLUTE MAX INPUT VOLTAGE(VOC) 48 VDC DC CONDUCTOR AMPACITY CALCULATIONS + ►t <br /> MAX SHORT CIRCUIT CURRENT(ISC) 11 ADC JUNCTION BOX TO INVERTER <br /> 1001 COOPER POINT <br /> AMBIENT TEMPERATURE ADJUSTMENT RD SW,STE 140-290, <br /> MAX OUTPUT CURRENT 15 ADC A EXPOSED CONDUIT 30 CELSIUSI OLYMPIA,WA 98502 <br /> MAX OUTPUT VOLTAGE 60 ADC PHONE:360-637-4343 <br /> TEMPERATURE CORRECTION FACTOR 0.96 NEC TABLE 310.15(B)(2)(A) <br /> #OF CURRENT CARRYING CONDUCTORS 4 HEIDI PASCHAL <br /> INVERTER SPECIFICATION CONDUIT FILL CORRECTION 0.80 .80(FOR 4 TO 6 CONDUCTORS IN CONDUIT) OR 1.00(FOR 3 OR LESS CONDUCTORS IN CONDUIT) PROJECT MANAGER <br /> NEC TABLE 310.15(B)(3)(A) <br /> INVERTER MAKE SOLAREDGE CIRCUIT CONDUCTOR SIZE #10 AWG I 1111111111111.11111111111111111 <br /> INVERTER MODEL NO. SE6000H-US CIRCUIT CONDUCTOR AMPACITY 40 AMPS NEC TABLE 310.15(B)(16) <br /> B REQUIRED CIRCUIT CONDUCTOR AMPACITY 15.00 AMPS REQUIRED CIRCUIT CONDUCTOR AMPACITY=MAXIMUM OPTIMIZER OUTPUT CURRENT(AMPS)(FROM OPTIMIZERS 6.300 DC KW <br /> MAXIMUM AC OUTPUT 6,000 W SPECIFICATIONS) <br /> MAX INPUT VOLTAGE 480 V C DERATED AMPACITY OF CIRCUIT CONDUCTOR 30.72 AMPS TEMPERATURE CORRECTION X CONDUIT FILL CORRECTION X CIRCUIT CONDUCTOR AMPACITY 6.000 KW CEC AC RATING <br /> NEC TABLE 310.15(B)(2)(A) CENTRAL INVERTER SYSTEM <br /> MAX INPUT CURRENT 16.5 A NOTE:"C"MUST BE LARGER THAN"B" 30.7A > 15.OA=OK 123° 270° <br /> NOMIMALAC VOLTAGE 240 v AC CONDUCTOR AMPACITY CALCULATIONS TILT AZIMUTH <br /> MAX AC CURRENT 25.0 A INVERTER TO MAIN SERVICE <br /> AMBIENT TEMPERATURE ADJUSTMENT <br /> A <br /> EXPOSED CONDUIT 30 CELSIUS 4706 GLENWOOD AVE <br /> TEMPERATURE CORRECTION FACTOR 0.96 NEC TABLE 310.15(B)(2)(A) EVERETT, <br /> #OF CURRENT CARRYING CONDUCTORS 2 WA 98203 <br /> CONDUIT FILL CORRECTION 1.00 .80(FOR 4 TO 6 CONDUCTORS IN CONDUIT) OR 1.00(FOR 3 OR LESS CONDUCTORS IN CONDUIT) <br /> NEC TABLE 310.15(B)(3)(A) CHRISTOPHER CONNAIR <br /> CIRCUIT CONDUCTOR SIZE #8 AWG <br /> CIRCUIT CONDUCTOR AMPACITY @ 90° 55 AMPS NEC TABLE 310.15(B)(16) (937)305-5812 <br /> INVERTER'S MAXIMUM AC OUTPUT CURRENT 25.00 AMPS INVERTER MANUFACTURER SPECIFICATIONS <br /> B REQUIRED AC CONDUCTOR AMPACITY 31.25 AMPS REQUIRED AC CONDUCTOR AMPACITY=1.25 X MAXIMUM INVERTER'S OUTPUT CURRENT(AMPS) APN:00505700003905 <br /> C DERATED AMPACITY OF CIRCUIT CONDUCTORS 52.80 AMPS TEMPERATURE CORRECTION X CONDUIT FILL CORRECTION X CIRCUIT CONDUCTOR AMPACITY <br /> NEC TABLE 310.15(B)(2)(A) <br /> NOTE:"C"MUST BE GREATER THAN"B" 52.8A >31.2A=OK <br /> DATE DESCRIPTION <br /> DATE 4/23/19 <br /> DRAWN: <br /> DRAWN BY: PD <br /> ELECTRICAL <br /> CALCULATIONS <br /> e ( <br />