Laserfiche WebLink
Plan Check /t B-40648 <br />June 14, 1993 <br />Page Three of T'hree <br />22. Provide insulation details for the exterior duct work per table 5-11. <br />23. Indicate fire/smoke dampers on the mechanical plans. <br />24. Duct penetrations of fire-rated corridor walls must be protected with combination <br />fire/smoke dampers. Section 4306(j)5. <br />In order for the processing of your application to continue, it will be necessary.to provide the <br />Building Department with two complete new sets of drawings reflecting the correcuons requested. <br />Upon re-submittal of the drawings, your application will be given priority and plan review <br />recommence. <br />All required submittals shall be of suffici�nt detail and contain sufficient information to ensure that <br />the proposed swcture will be constructed in compliance with all adopted codes. <br />Since <br />f S cPal <br />ssocia Engineer/Building <br />�tljmpien6J <br />