Laserfiche WebLink
OUTDOOR AIR HANDLING Uf�IT W TH GAS HEAT SCHEDULE <br /> SUPPLY FANS ARRAY EXHAUST FANS ARRAY INOIRECT GAS-FIRED HEAT AHU ELECTRICAL* FILTERS <br /> PRE-FILTERS ( 2") FINAL FILTERS ( 4") �� DIMENSIONS OPERATING ' <br /> MARK SERVICE �'PE NUMBER OF TQTAL MIN ESP TSP BHP HP NUMBER OF TOTAL ESP TSP BHP HP INPUT OUTPUT TURN DOWN TEMP. SCCR (L x W x H) REMARKS <br /> AIRFLOW OUTSIDE V/PH VFD AIRFLOW V/PH VFD FLA MCA MOP V/PH 1PD FPD IPD FPD WEIGHT (LBS.) <br /> (CFM) AIR (CFM) {IN. WG) (IN. WG) (Total) (Total) FANS (CFM) (IN. WG) (IN. WG) (Total) (Total) (MBH) (MBH) RATIO RISE (AMPS) MERV MERV (INCHES) <br /> (IN. WG) (IN. WG) (IN. WG) (IN. WG) <br /> AHU-1 45-a12 BUILDING HORIZONTAL 6 50,000 5,000 3.5 7.0 82.49 90 480J3 YES 4 47,000 1 A 2.0 33.61 34 480/3 YES 3,062 2,450 30:1 45 160 187 250 480/3 10000 8 0.50 1.00 13 0.50 1.50 248 x 150 x 127 18,000 1 TO 12 - <br /> AHU-2 45-012 BUILDING HORIZONTAL 6 50,000 5,000 3.5 7.0 82.49 90 480/3 YES 4 47,000 1.0 2.0 33.61 34 480/3 YES 3,062 2,450 30:1 45 16Q 187 250 480/3 10000 8 0.50 1.00 13 0.50 1.50 248 x 150 x 127 18,000 1 TO 13 <br /> 1. AHU MANUFACTURER TO PROVIDE UL LISTED & LABELED BIJRNER CONTROL PANEL, BURNER IS CONTROLED WITH 2-10 VOLTS INPUT BY HONEYWELL (CMCS). <br /> 2. PROVIDE AN ARRAY OF SIX SUPPLY FANS AND AN ARRAY OF FOUR EXHAUST FANS. AHU SHALL BE CAPABLE OF PROVIDING 90� OF NOMINAL AIRFLOW WITH ONE FAN DOWN. <br /> 3. PROVIDE WITH A SINGLE 4$Q VOLTS/3 PHASE POWER CONNECTION. � ' <br /> 4. PROVIDE TWQ 120 VOLTS /SINGLE PHASE POWER CONNECTIONS FOR LIGHTS/ RECEPTACLE AND EMCS CONTROL PANEL. <br /> 5. PROVIDE ONE VFD PER FAN (NO VFD BYPASS), PROVIDE VFDS AS PER ELECTRICAL SPECIFICATION 26 29 23 , <br /> 6. ALL CONTROLS BY HONEYWELL (EMCS). <br /> 7. UNIT IS CAPABLE OF SUPPLYING 100% QUTSIDE AIR ( FOR SUMMER COOLING). <br /> 8. ELECTRICAL CONTRACTOR TO PROVIDE A QISCONNECT SWITCH. <br /> 9. PROVIDE 8" HIGH MEfAL BASE. <br /> 10. PROVIDE SMOKE DETECTdRS IN RETURN AIR DUCT ( BY ELECTRICAL CONTRACTOR�. �, <br /> 11. PROVIDE NJO OUTSIDE AIR DAMPERS: ONE SIZED FQR MINIMUM OUTSIDE AIR (5,000 CFM) AND ONE SIZED FOR ECONOMIZER FLOW (45,000 CFM) <br /> 12. UNIT IS EQUIPED WITH PREMIUM EFFICIENCY MOTORS <br /> 13. ALL DAMPERS PROVIDED BY MANUFACTURER <br /> * SEE NOTE #4 FOR 12Q VOLTS POWER REQUIREMENTS <br /> FAN SCHEDULE �:, <br /> MOTOR <br /> UNIT N0, LOCATION ARF� SERVED CFM ��N SW�� FAN RPM HP BHP RPM VOLTS PH VFD FAN TYPE DRIVE TYPE MANUFACTURER & MODEL OPER WT, (LBS.) REMARKS = <br /> EF-1 SUBSTATION TRANSFORMER 6,500 1.10 1198 3.00 2.02 1170 208 3 YES MIXED FLOW INLINE DIRECT GREENHECK QEID-22-75-830 370 1, 2, 3, 4, 5 . <br /> 0 0 I - -V 4 <br /> SF-1 HYDRAULIC PUMP ROOM HYDRAULIC PUMP ROOM 680 0.50 1550 0.25 0.24 1750 115 1 NO PROPELLER pIRECT GREENHECK SS1-12-432-A4 35 4, 6, 7 <br /> WALL <br /> NOTES: <br /> B 1. PROVIDE MOTORIZED DAMPER. 6. FAN SHALL RUN CONTINUOUSLY. - <br /> 2. CONTROLLED BY EMCS WITH ROOM SENSOR. 7. PROVIDE WALL HOUSING, FLUSH EXTERIOR WITH OSHA GUARD. <br /> 3. PROVIDE VFD PER ELECTRICAL SPECIFICATION 262923. ' <br /> 4. VENTILATION AIR SUPPLY. <br /> 5. SUPPLY VFD RATED MOT�R WITH GREENHECK SDR T1502268 SHAFT GROUNDING. � <br /> .�; <br /> �, <br /> ,;t .. <br /> OFFMAN � �: <br /> ISSUE FOR PERMIT . <br /> N G I N E E ft S _ <br /> j1 n ■ /� O■I'1 O A � 1601 Fifth Avenue,Suite 900�Seattle,WA 98101 � � <br /> UV I L i ph 206.623.0717�fax 206.624.3775 < <br /> � coffman.aom � <br /> LASTING ueanvity�resu�ts�re�atanships `- <br /> N <br /> h� <br /> C <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL D DATE T <br /> ��L so�, ACCEPTABILITY G.ROUTH 05.26.15 MECHANICAL EQUIPMENT SCHEDULES <br /> - EDC STATIC TEST FACILITY W3099715 CEI MS 10.02.15 � s�i►j �. THIS DESIGN AND/OR CHECKED W4440664 L� 03.10.17 � <br /> � AS-BU L S � �,~" ��' SPECIFICATION IS APPROVED NSOTU RA 05.26.15 TITLE sHEET � <br /> A EDC STATIC TEST FACILITY I T W3099715 CEI MS 09.01.16 \ <br /> = PHAS BOES�� �, �� APPROVED BY DEPT. DATE COFFMAN 05.26.�5 EDC STATIC TEST FACILITY - PHASE 2 M�A a P <br /> B EDC STATIC TEST FACILITY E 2 W4440664 CEI MS 03.10.17 CHECKED = <br /> ��j66�� APPROVED B U I L D I N G 45�0 1 � JOB N0. W3099715 coMP Na Q <br /> �'S�•I �yCs�'� APPROVEQ DWG N0. r <br /> �A� MECHANICAL MASTER EVERETT, WA 45-012-M2A <br />