Laserfiche WebLink
.. ! �.,..1'�1Udt�, <br /> � <br /> O � MECHANICAL NOTES: <br /> O 1. DUCT MATERIAL IS 26 GA. GALV. AND FLEX DUCT. DUCTWORK SHALL BE SUPPORTED PER 2015 IMC <br /> WAC CHAPTER 6. SECTION 603 <br /> 2. MATERIAL IN DUCTS SHALL HAVE A FLAME SPREAD INDEX OF LESS THAN 25, SMOKE DEVELOPMENT <br /> OF 50 PER 2015 IMC WAC CHAPTER 6. SECTION 602 <br /> 3. LOW PRESSURE DUCT SYSTEMS SHAL� HAVE LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND <br /> CONNECTIONS OF SUPPLY AND RETURN DUCTS AND PLENUMS SECURELY FASTENED AND SEALED WITH <br /> WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS EMBEDDED-FABRIC SYSTEMS OR APPROVED TAPES <br /> INSTALLED IN ACCORDANCE WITH 2O15 IMC WAC CHAPTER 6 SECTION 603.9. <br /> CD-1 CD-1 <br /> 10" 10" 4. WHEN ISOLATION SLEEVES ARE USED AT LINE CONNECTIONS TO PLENUMS, THEN THEY SHALL COMPLY <br /> WITH IMC CHAPTER 6 <br /> WALL MOUNT <br /> 72` ,O` ,O RETURN 5. 10" DIFFUSERS WITH NO MANUAL DAMPERS. USE FLOW CONTROLS AT WYES, TYPICAL AS NOTED ON PLAN * <br /> 6. MINIMUM OUTSIDE AIR VENTILATION PER 2015 IMC WAC CHAPTER 4, TABLE 403.3.1.1. <br /> 10 12 <br /> 1 � �O 1 2 7. OUTSIDE AIR DAMPERS SHALL COMPLY WITH 2O15 WSEC, SECTION C403.2.4.3. <br /> HP-1 <br /> �1 8. SINGLE PACKAGE UNITARY FAN COOLING UNITS HAVWG A TOTAL COOLING CAPACITY OF GREATER THAN <br /> �� 20,000 Btu/h REQUIRE ECONOMIZERS PER WSEC 403.3. EXCEPT AS PERMITTED BY C403.3 EXCEPTION 1 <br /> � - - - - - - - - - - - - - 12/ - - - °� T _ TCURBF <br /> SUPPLY PLENUM <br /> #PWS131 MECHANICAL NOTES: (cont.) <br /> OCCUPIED SET POINT MECHANICAL EQUIPMENT INSTALLATION IN OR ON THIS BUI�DING SHALL BE IN ACCORDANCE WITH <br /> TO BE CONTROLLED BY THE REQUIREMENTS OF THE 2015 IMC WAC CHAPTER 6. <br /> nLIGHT OCCUPANCY <br /> SENSORS ROUND FLEX DUCT SHALL BE U.L. LISTED CLASS 1, STANDARD 181 - FACTORY MADE AIR DUCTS AND AIR <br /> CONNECTORS. MEASURED IN ACCORDANCE TO ASTM C 518 OR ASTM C 177 AT 75DEG F MEAN - <br /> TEMPERATURE. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURES INSTALLATION INSTRUCTIONS <br /> CD-1 CD-1 <br /> 10" 10" MECHANICAL DRAWINGS SHOW DUCTWORK SIZES TO BE CLEAR INSIQE DIMENSION. � <br /> DUCT INSULATION SHALL COMPLY WITH 2O15 IMC WAC CHAPTER 6, SEC. 604. <br /> ELECTRICIAN MUST VERIFY ALL ELECTRICAL REQUIREMENTS AND LOCATIONS. <br /> THERMOSTAT SCHEDULING TO BE PERFORMED ON SITE BY OTHERS. <br /> ALL HVAC EQUIPMENT LEAVES FACTORY WIRED FOR 240 VOLT OPERATION <br /> THE ACCEPTABLE OPERATING RANGE FOR THE 240V & 208V TAPS ARE: <br /> OTAP RANGE <br /> 240 253-216 <br /> M EC HAN I CAL P LAN 208 220-187 <br /> 1/4" = 1'-0" SITE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THE RIGHT TAP IS CONNECTED FOR <br /> THE APPLIED SITE VOLTAGE. <br /> MINIMUM VENTILATION RATES PER IMC SECTION 403 AIR FILTERS IN HVAC UNITS OR SYSTEMS ARE TO BE CHANGED EVERY 30 DAYS BY OTHERS ON SITE. <br /> Rp <br /> room# name Az(sf) sfJ1000 Occ. Dens Pz(calc) Pz(used) (cfm/person) Ra (cfm/sf) Vbz(cfm) REGISTER AIR FLOW TEST AND BALANCE OF HVAC SYSTEM TO BE PROViDED AND PERFORMED BY OTHERS ON SITE. <br /> 1 Classroom 817 0.817 35 29 29 10 0.12 388 <br /> 388cfm HVAC SITE CONTRACTOR IS RESPONSIBLE FOR BALANCING THE SYSTEM. (2015 IMC WAC 403.3.3.1.5) <br /> Az=room area(sf� <br /> Occ. Dens=occupant density(from Table 403.3) . <br /> Pz(caic)=zone population or occupant quantity(calculated) <br /> Pz(used) =zone population or occupant quantity(user can override the calculation-increase only) <br /> Rp=people outdoor airflow rate in brea#hing zone {cfm/person) <br /> Ra=area outdoor airFlow rate in breathing zone (cfm/sf) <br /> Vbz=Breathin zone outdoor airflow rate per eq.41( R *Pz+Ra*Az) <br /> PACKAGE *SPVU* HfGH EFFICIENCY WALL MOUNT HEAT PUMP - SCHEDULE <br /> DOAS/ERV/ELECTRICAI �O DOAS/ERV/ELECTRICAL Q COOLING CAPACITY 3Q HEATING CAPACITY �4 DOAS UNIT HEAT STRIPS <br /> ENERGY RECOVERY ELECT. INFORM. C . NF RM. <br /> COMP TOTAL ECON. DOAS LOW VENTILATION MODE FULL VENTILATION MODE COOL SENS. COOL SENS. HTG HTG OUTDOOR ELEC. ELEC. OPER. • <br /> BARD TYPE CFM BLR. 100% ERV ECM ECM OUTSIDE ENT ENT CAP. CAP. CAP. CAP. OUTSIDE CAP. CAP. SUMMER DB/WB HRS HRL WWFER INDOOR WHR HEAT HEAT WGT. ADDITIONAL <br /> TAG QTY MODEL # TONS SCROLL NOM. TYPE. FREEFLOW �SA V-PH ERV BLOWER V-PH ERV B�OWER DB DB WB EER IPLV BTUH BTUH BTUH BTUH DB COP BTUH BTUH EFFICIENT DEG'S BTUH BTUH EFFlCIENT DB MOP V-PH MCA MOP CKT V-PH MCA BTUH CKT KW BTUH LBS. REMARKS <br /> PART/fUL VENTIL. MOTOR MOTOR PART LOAD PART LOAD FULL LOAD fUL1 LOAD PqRT/LOAD FULL/LOAD � <br /> 750 388 AMPS-1.3 AMPS-.87 AMPS-2.2 AMPS-1.74 <br /> HP-1 1 C36HA-A10ZP4XXR 3 2-STAGE 1100 ECM NO 450 230�� WATTS-296 WATTS-95 230/1 WATTS-497 WATTS-192 95 80 67 11.0 14.5 23.4K 18.5K 35K 26.3K 47 3.3 22.7K 31K 65% 95/70 6,318 1,711 80� 1,711 23,328 230/1 27 40 A 240/1 52 60 B 10 34,130 678 1, 2, 3, 4, 5, 6, 7, 8 <br /> ADDITIONAL REMARKS; C36H1 The sequence of operation for the Integrated DOAS system. <br /> 1 - PLAN # __________ ERV Watts - low 296 watts Blower Full �oad 192 watts 1. Upon a call from the occupancy sensor the(DOAS} ERV and the indoor(ECM) motor will <br /> 2 - INCLUDE BARD WALL CURB #TCURBF3642A-4. <br /> 3 - THERMOSTAT, BARD # 8403-060, 7-DAY PROGRAMMABLE. ERV Am s - Low 1.3 Am s Blower Full Load 1.74 Am s start in low vent mode and ventilate the space continuously as occupied. <br /> 4 - WALL CO2 SENSOR. #8403-067 ERV CFM - Low 300 CFM Blower Part Load 95 Watts Note: 1 on the HVAC Schedule. <br /> 5 - OCCUPANCY SENSOR, (SUPPUED BY BLAZER) ERV Watts - Med 415 Watts Blower Part Load 0.87 Am s 2. Upon a call from the CO2 sensor the(DOAS) ERV and the indoor(ECM) motor will <br /> 6 - GPS (FIELD INSTALLED CONTROL KIT}. ERV Am s - Med 1.8 Am s <br /> 7 - 2" Fi�TER. ERv CFM - Med 375 CFM Com ressor Full 2588 Watts change to full vent mode and ventilate the space until the CO2 sensor is satisfied and then <br /> 8 - ERV (�OAS) ENERGY RECOVERY. ERV Watts - Hi 497 Wotts Com ressor Full 11.46 Am s revert back to the low vent mode during the occupied time. <br /> 9 - UNIT COLOR IS *BUCKEYE GRAY* ERV Am s - Hi 2.2 Am s Com ressor Part 1734 Watts Note: 2 on the HVAC Schedule. <br /> 10 - PRE INSTA�LED OUTDOOR THERMOSTAT, SET AT 40DEG'S. ERV CFM - Hi 450 CFM Com ressor Port 7.99 Am s 3. The Heating and Cooling section will only work if there is a Heating or Cooling call from . <br /> ** M.C. TO REFER TO INSTALLAT�ON INSTRUCTIONS FOR START UP AND EQUIPMENT SET. Outdoor Fan 380 Wotts the thermostat. This action works entirely independent of the DOAS ventilation portion. <br /> *'� M.C. TO CHECK SITE VOLTAGE AND SET CORRECT TAP ON TRANSFORMER. Outdoor Fan 1.67 Am s Note: 3&4 on the HVAC Schedule. <br /> ** M.C. TO SET AND PROGRAM THERMOSTAT PER cusroMERs RE4uiREt�Etvrs. 4. This action will keep repeating itself as required by the occupancy sensor, CO2 sensor <br /> and Room Thermostat. <br /> 8-18-17 REVISE HEAT PUMP SCHEDULE,ADD SEQUENCE OF OP. RMS COPYRIGHT 2017, BLAZER INDUSTRIES, INC. � MODULAR Approved for Const: Job No: 99031 <br /> 9-6-17 ADD SUPPLY PLENUM NUMBER (#PWS131) LDG THIS MATERIAL IS TFiE EXCLUSIVE PROPERTY C/assroom for. <br /> OF BLAZER INDUSTRIES, INC.AND SHALL ■■ 2$ X 32 KC DA - Eve rett S�D■ File Copy: <br /> NOT BE REPRODUCED, USED, OR DISCLOSED <br /> TO OTHERS EXCEPT AS AUTHORIZED BY THE �� INDUSTRIES,�NC. Drawn B : �DG � <br /> DATE REVISION BY WRITTEN PERMISSION OF BLAZER INDUSTRIES. � ��blazerind.com WA. GOLD Pacific Mobile 17 BLMP-04 A9 WA <br /> ■■ P.O.BOX 489 ■ Aumsville,OR 97325-0489 �ssue�ate: 9-6-17 <br /> �, <br />