Laserfiche WebLink
� <br />Ltr. D.Olson (B0306-025) <br />June 27, 2003 <br />Page 2 <br />5. The wood used in the exterior wall details on Sheet A8.3 should be shown to be fire- <br />retardant treated. Section 503.43 <br />6. It should bc noted that all full-height glazing in window type BB is required to be safety <br />glazing. Section 2406.4 <br />7. The guardrail surrounding the central stairs should be shown to be a minimum of 42" high. <br />Section 509.2 <br />8. The iloors in the toilet rooms should be shown to exiend up a minimum of 5" onto the wall <br />surface. Section 307.1.1 <br />9. Hall 125 shauld be relabelc�l as a corridor. Section 1004.3.4 <br />10. Maximum occupant load signs must be posted in Rooms 124, I l9 and the main Floor. The <br />signs and vcrbagc should be shown on the plans. Section 1007.2.6 <br />1I. Door #302 should swing in the direction of travel and be provided with panic hardware. <br />Sections 1007.2.5, 1003.3.1.5 & ]003.2.2.2.4 <br />l2. The details of conswction should be completed for the lighthousc. <br />13. The hot water supplies and drains under the accessible lavatories should be shown recessed, <br />insulated or guarded against contact. Section 1106.I IJ.4 <br />Please prepare a responsc Iettcr showing where each item in this correction letter is addressed on the <br />plan set. <br />Upon resubmission of the drawin�s, your application will be given prioriry and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient intorma[ion to ensure that <br />the proposed stnicture will be conshucted in compliance with all adopted codes. <br />Sincercly, <br />��� <br />Tony R. Lce <br />Plans Examiner <br />