SUBSTATIONS 11-1 AND 11-2 SECTION 26 11 16 <br /> PROJECT#22349762 SECONDARY UNIT SUBSTATIONS <br /> BOEING- EVERETT SITE SERVICES <br /> c. Fault close asymmetrical rating of 61 kA. <br /> d. Fused switch fault close rating of 99 kA Asym rms. <br /> B. Windows: Provide with three rupture-proof viewing windows; two to inspect each set of <br /> switchblades, and one to view the blown fuse indicators (where the selected fuse type <br /> has such indicators). <br /> C. Fuses: Fuses shall be sized as recommended by the transformer manufacturer, <br /> consideririg fan cooling, temperature-rise specification, and cycle loading. Comply with <br /> the following: <br /> 1. The selected fuse size shall achieve the best balance of IEEE/ANSI recommended <br /> protection levels, load carrying capability, and coordinate properly with the secondary <br /> switchgear breakers. <br /> 2. The sizes shown on the drawings are approximate, and are subject to revision by the <br /> manufacturer, if required, with no change in price. <br /> 3. Current-limiting type, rated minimum of 50-kA RMS symmetrical current-interrupting <br /> capacity. <br /> a. Gould-Shawmut CS-3 <br /> b. Cutler-Hammer CLE <br /> c. General Electric EJO-1, Type 9F62 <br /> 4. Indicator integral with each fuse to show when it has blown. <br /> 5. Spares: Include three fuses in use and three spare fuses in storage clips in switch. <br /> D. Construction. <br /> 1. Dual gang operated quick make/quick break mechanisms which shall operate the <br /> contacts independently of the speed of movement of the operating handle. The <br /> operating handle shall be non-removable. <br /> 2. The mechanism shall be field adjustable for alignment, open gap, and sequencing. <br /> 3. All switch current carrying components, fuse clips, interconnecting buses, outgoing <br /> buses, and incoming lug landings shall be copper, with silver plating at joints and <br /> terminations. <br /> 4. All buses and conductors shall be insulated, except for the switch moving parts and <br /> contacts. Insulation on buses shall consist of Noryl sleeves, or fluidized bed epoxy. <br /> Corners, joints, insulator connection points, and the lug landing pads shall be <br /> insulated with removable PVC boots. Coordinate the boots for the lug landing pads <br /> with the number and size of cable terminations identified. Heat shrink coverings and <br /> insulated tapes are not acceptable. <br /> 5. All live parts shall be insulated from ground by polyester. <br /> 6. The switch connecting rods shall be polyester insulated. <br /> 7. The switch load side bus shall be connected to the transformer incoming terminals <br /> via cables. <br /> 8. Each primary termination provision shall have adequate space for termination of four <br /> (4) 15kV 500 kcmil shielded cables per phase from the top and bottom of the air <br /> terrninal chamber, including adequate allowance for cable bending limitations. <br /> a. Provide A.B. Chance ground stud, part#C600-2102, on accessible part of <br /> phase bus in each switch for connection of owner's maintenance grounding <br /> equipment <br /> 2611 16-7 <br /> (07/15/18) <br />