8. The glazing at the stair landing in Unit 4 should be shown to be a minimum of 36" a.f.f or safety <br /> glazing. Section R308.4.7 <br /> 9. The attic access hatches in units 1 &4 should be shown in an unobstructed, readily accessible <br /> location and not over closet shelves. Section R807.1 <br /> 10. Deck lateral load connections should be detailed on the plans. Section R507.1 <br /> Please provide a response letter, which shows where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmission of the drawings, your application will be given priority and plan review will <br /> begin. <br /> All required submittals must be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Tony R. Lee <br /> Building Official <br />