• • <br /> We observed the following conditions: <br /> Roof Framing/Third Floor Units <br /> The roof framing was reviewed from the ground and from the third floor units, where <br /> possible. <br /> 1. The majority of the north half of the roof between the west end of the building(above <br /> Unit 111) and the unit separation above Units 116/117 has collapsed down onto the <br /> flat roof sheathing. There are areas of roofing/roof framing that remain in this section <br /> (typically above the decks). <br /> 2. The roof framing over the exterior walkway south of the central stairwell is typically <br /> not charred or is covered with undamaged soffit away from the stairwell. The roof <br /> framing around the central stairwell and above the adjacent exterior walkways has <br /> significant char. A portion of the roof framing to the north of the stairwell over the <br /> walkway has been completely consumed by the fire. The framing over the remainder <br /> of the walkway to the north stairwell is charred to varying degrees, with the more <br /> significant char closer to the north end of the building. <br /> 3. We reviewed Units 111/112 and 113/114 from the hallway and entered Units 115, <br /> 116 and 117. The flat roof is collapsed above Units 111, 113 and 114. The flat roof <br /> joists have char above Unit 112. A small portion of the flat roof is collapsed above <br /> the kitchen and bath in Unit 115,adjacent.to Unit 114. There is severe char on <br /> several joists in the northwest corner of the nook in Unit 117 and the adjacent <br /> northeast corner of the nook in Unit 116. <br /> 4. The flat roof framing is typically not charred or covered with GWB above the <br /> southern bedrooms (this was noted in Units 112 through 116). Note that we did not <br /> review the flat roof joists above Unit 111. However, we noted several areas where <br /> the flat roof sheathing was significantly decayed. <br /> 5. While moisture was observed in Unit 11.8, no structural damage was observed. <br /> 6. Units 119 and 120 were not accessed because they were locked. <br /> Third Floor Framing/Second Floor Units <br /> The third floor was reviewed from the second floor units. <br /> 7. We did not enter Units 101 or 102, only reviewed them from the hallway. There are <br /> charred floor joists above Unit 101. While Unit 102 appeared to have only minimal <br /> char; further review is necessary to determine if there is structural damage to the floor <br /> framing above. The deck outside Unit 101 also has charred framing. <br /> 8. While moisture was observed in Units 103 and 106,no structural damage was <br /> observed. Units 109 and 110 appeared to have only minor moisture. <br /> 9. Units 104, 105, 107 and 108 were not accessed because they were locked. <br /> 10. The exterior walkway is typically covered by the soffit east of the central stair,but <br /> charred framing starts above Unit 104. In one location at the walkway outside Unit <br /> 102/103,two joists are completely consumed by char and are not supported by the <br /> exterior beam(at a vent location below Units 112/113). The exterior beams and posts <br /> are charred to varying degrees at the north end of the walkway for approximately 40'. <br /> 16001ltrthe bluffs 1/4/16 <br /> 2 <br /> L <br />