v. <br /> 4 <br /> Original Response: Assumed property line shown on site plan between two <br /> buildings, see sheet A001. <br /> New Comment: The assumed property line is shown along the northern side of the <br /> new building, past the existing building, located a few inches away. As such, the <br /> northern wall of the new building would not be permitted to have any openings <br /> (window or otherwise) and the entire wall would need to be one-hour fire-rated <br /> (exposure from both sides). It is suggested that the assumed property line be shown to <br /> come out of the gap between the buildings at an angle that may allow unprotected <br /> openings in the existing and new buildings. <br /> 3. Original Comment: The assumed property line must remain 90 degrees vertical <br /> without horizontal offsets. The eves on the North side of the building are not permitted <br /> to cross over the assumed property line. Section 705.3 <br /> Original Response: See assumed property line sheet A001. <br /> New Comment: Due the location of the assumed property line, the exterior walls of <br /> the existing, non-sprinklered building that are less than 25 feet to the assumed <br /> property line are required to have a parapet (other exceptions may apply as well). <br /> Section 705.11 <br /> 10. Original Comment: The mechanical room is not permitted to open into the exit <br /> passageway on the ground floor. Section 1023.4 <br /> Original Response: Door swing at mechanical room updated to swing into Mechanical <br /> room. See floor plan on sheet A100. <br /> New Comment: The door swing did not need to change, the issue was the opening <br /> up of the mechanical room (at all) into the exit passageway. With the addition of the <br /> fire-rated doors to the exit enclosure, the lowest hall is no longer an exit passageway <br /> 14. Original Comment: The emergency escape and rescue window from the sleeping <br /> room in Unit 1 opens into a covered parking area. The window must open directly into <br /> the public way. Section 1030.1 <br /> Original Response: Due to this restriction, the entire unit 1 had to be reconfigured. <br /> See floor plan sheet A100. <br /> New Comment: The room has been changed to a bathroom. The private garage is a <br /> U Occupancy (and should be shown as such on the plans). Section 406.3.4.1 would not <br /> permit an opening (must be all gypsum board), however, if the opening were fixed, 20- <br /> minute rated it would comply. Section 406.3.4.1 <br /> Structural <br /> 17. Original Comment: Per IBC 2015 1603.1.4 & 1603.1.5. Please provide the <br /> governing base shear in each direction and indicate the overstrength factor (S2) on the <br /> General Structural Notes. <br /> Original Response: See added notes to General Structural Notes. <br /> New Comment: Please provide the governing base shear values on the drawings in <br /> both directions. Wind may be the governing design in both directions, please provide <br /> the values and indicate if the values are expressed in ultimate or allowable loads. <br /> 21. Original Comment: On detail 7/S601, please verify that uplift forces are not acting <br /> on the anchor bolt provided. The beam is supporting the shear wall does not jclut4e- <br /> Page2of4 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax (425) 25748'57"--- <br /> " <br />