Mr. Randy Heltne <br /> Everett Housing Authority <br /> Plan Check Number: B1807-032, First Review <br /> September 14, 2018 <br /> 14.The overframing design on Sheet A-7 is incomplete. The framing appears to require ridge <br /> members and a vertical load-bearing element at the intersection of the ridge members. <br /> Connections shall be specified between the framing. The west end of the west-most ridge <br /> member may bear directly on the sheathing; blocking shall be provided at the load point as <br /> needed. The structural design shall be reviewed and revised as needed. Calculations <br /> substantiating the design of the overframing members shall be submitted for review. Note that <br /> the 2x8 joists have spans up to 16 feet that appear to be overstressed. See IBC Sections <br /> 107.2.1, 1603.1, 1604.1, 1613.1, and 2306.1, ASCE 7-10 Chapter 30, and AWC SDPWS-15 <br /> Section 3.4.1. <br /> 15.The roof plan on Sheet A-7 specifies roof trusses spanning 41.5 feet. The trusses ae non- <br /> uniform and have interrupted top chords due to the roof geometry. It is not clear that the roof <br /> construction can performed as specified for the required span. Note that the first two trusses <br /> will be approximately 24-inches deep or less. Preliminary design documentation including <br /> manufacturer's literature substantiating the feasibility of the design shall be submitted for <br /> review. See IBC Sections 104.11 and 1604.1. <br /> 16. Continuing with the previous comment, holdowns shall be specified for the roof trusses to <br /> resist uplift loading due to wind. Calculations substantiating the holdowns shall be submitted <br /> for review. See IBC Sections 107.2.1, 1604.1, 1613.1, and 2306.1, ASCE 7-10 Chapter 30, and <br /> AWC SDPWS-15 Section 3.4.1. <br /> 17.The roof plan on Sheet A-7 does not specify framing for the east roof eve. The plywood <br /> sheathing is not structurally adequate for the approximately 2-foot cantilever. A detail shall be <br /> provided showing the required construction. The construction shall be sufficient to resist both <br /> gravity loading (e.g., self-weight, snow) and uplift due to wind. See IBC Sections 107.2.1, <br /> 1603.1, 1604.1, 1613.1, and 2306.1, ASCE 7-10 Chapter 30, and AWC SDPWS-15 Section <br /> 3.4.1. <br /> 18.The floor framing plan on Sheet A-4 specifies a new steel beam at the existing exterior east <br /> wall. See IBC Sections 107.2.1, 1603.1, 1604.1 The following comments shall be addressed: <br /> a. The calculations are based on a 24'-8"span while Sheet A-2 indicates the span is 28'-3". <br /> The calculations do not include an additional 15 psf partition load per IBC Section 1607.5. <br /> It appears that the W12x45 beam noted in the calculations is overstressed and should be <br /> revised. Note that the point loading, presumed to be from the roof, should be clarified. <br /> b. The required size of the beam shall be specified on Sheet A-4. <br /> c. Sheet A-2 appears to specify a 4x6 post at the north end of the beam. The support at the <br /> south end shall also be specified. <br /> d. Details and calculations for the connections between the beam and posts shall be <br /> submitted for review. <br /> Page 8 of 11 <br /> CITY OF EVERETT• 3200 Cedar Street • Everett,WA 98201 • (425) 257-8810 • Fax(425) 257-88 <br />