18249.10 Everett Housing i _ rity October 5, 2018 <br /> Comment Response Page 7 of 8 <br /> 26. Section B-B/A-6 provides a detail for the floor construction at the new steel beam. The detail does <br /> not appear to represent the likely construction at this location. Most notably,the sheathing will <br /> consist of existing and new sheathing connecting from the west and east sides, respectively. The <br /> bolt heads should recess into the nailer to avoid performance impacts to the diaphragm. The detail <br /> should be reviewed and revised as needed.See IBC Section 107.2.1. <br /> Please see detail 5/S4.2 for the construction of the steel beam. <br /> 27. The construction drawings to not provide detailed to transfer loads from the roof diaphragm to the <br /> shear walls,and shear loads from the second story shear walls and floor to the first story shear <br /> walls. Details providing a complete load path interconnecting the elements of the lateral force <br /> resisting system shall be submitted for review. See IBC Sections 1604.1,1604.4,and 2306.1,and <br /> AWC SDPWS-15 Section 4.1.1. <br /> Please refer to the attached structural drawings and details showing the shearwall nailing and <br /> holddown connections between floors. <br /> 28. Sheets A-6 and A-7 indicate that a prefabricated roof truss may align with the existing east wall <br /> below and provide a load path between the roof diaphragm and wall line. Design loads for the <br /> trusses should be specified in the structural design criteria. If the truss is not part of the lateral load <br /> path,tributary roof diaphragm loads shall not be directly applied to this wall line.See IBC Sections <br /> 107.2.1, 1603.1.8,and 1604.4,and ASCE 7-10 Section 1.4. <br /> Please refer to the updated truss framing plan. <br /> 29. The wood shear walls do not appear to include holdowns at the ends to provide overturning <br /> resistance.The sill plate anchors specified in the drawings do not qualify as holdowns. Holdowns <br /> shall be provided connecting the boundary elements(i.e.,studs at the wall ends)across floor <br /> framing and to the foundation. Calculations substantiating the design of the holdowns and <br /> boundary elements should be submitted for review. See IBC Sections 1604.1, 1604.8.1, 1604.10, <br /> 2304.10.6,and 2306.1,and NDS-15 SDPWS Sections 3.4,4.1.4,and 4.3.6.4.2. See also IBC Section <br /> 1901.2,and ACI 318-14 Sections 17.2.3.4.3 and 17.2.3.3. <br /> Holddown callouts have been added to the plans. <br /> O <br /> 250 Avenue South,Suite 200 <br /> Edmonds, <br /> WAWA 98020 <br /> ENGINEERING ph.425.778.8500 I f.425.778.5536 <br /> www.cgengineering.com <br />