Mr. Randy Heltne <br /> Everett Housing Authority <br /> Plan Check Number: B1807-032, Second Review <br /> October 17, 2018 <br /> 14.This comment has not been completely addressed. See IBC Sections 107.2.1, 1603.1, 1604.1, <br /> 1613.1, and 2306.1, ASCE 7-10 Chapter 30, and AWC SDPWS-15 Section 3.4.1. The following <br /> comments shall be addressed: <br /> a. The overframing design on Sheet A-7 is incomplete. The required construction of the <br /> overframing is unclear; see Comment 13 for additional information. The west end of the <br /> west-most ridge member may bear directly on the sheathing; blocking shall be provided at <br /> the load points as needed. The structural design shall be reviewed and revised as needed. <br /> b. Calculation page 6 appears to indicate that the existing single 2x8 joists are overstressed <br /> and shall be doubled. The framing plans do not indicate double framing at the roof joists. <br /> 15. No additional comment. <br /> 16. No additional comment. <br /> 17. No additional comment. <br /> 18.This comment has not been completely addressed. The floor framing plan on Sheet A-4 <br /> specifies a new steel beam at the existing exterior east wall. See IBC Sections 107.2.1, <br /> 1603.1, 1604.1 The following comments shall be addressed: <br /> a. This comment has not been addressed. The calculations do not include an additional 15 <br /> psf partition load per IBC Section 1607.5. The beam design should be revised. <br /> b. No additional comment. <br /> c. The plan appears to specify the south post as a 5 1/8x5 1/4 while the north post is a 5 1/4 <br /> —square. Verify the required post size. <br /> d. Verify that Detail 5/S4.2 provides the end support condition for the W12 beam. The detail <br /> shall be referenced in the framing plans. <br /> e. Continuing with Comment 18d, the following should be addressed for Detail 5/S4.2: <br /> i. Verify if stiffener plates should be provided for the W12 bottom flange. These may be <br /> required if the beam does not directly bear on the post. Note that stiffeners may still <br /> be required if the beam bears directly on the post. <br /> ii. Verify the connection capacity, including bolt bearing, if the beam does not directly bear <br /> on the post. Calculations substantiating the capacity shall be submitted for review. <br /> iii. Vertical-slotted holes shall be provided in the connection plates if the beam is intended <br /> to transfer loads through direct bearing on the post. <br /> 19.This comment has not been completely addressed. The following comments shall be <br /> addressed for the headers shown in the floor and roof framing plans on Sheets A-2, A-4 and A- <br /> 7, respectively: <br /> a. The south wall header shall be specified. See IBC Section 1603.1. <br /> b. No additional comment. <br /> c. No additional comment. <br /> d. No additional comment. <br /> Lateral System: <br /> 20. No additional comment. <br /> Page 7 of 10 <br /> CITY OF EVERETT• 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax(425) 25 - <br />