• <br /> d. The words'NO PARKING FIRE LANE'shall be in 3-inch stroke white letters 18 inches in <br /> height,and placed 8 inches measured perpendicular from the red paint stripe on the pavement. <br /> In.most cases,both sides of the access road shall be marked. Where long drives are to be <br /> marked,the repetitions shall alternate sides of the drive. <br /> e. Marking shall also include the addition of metal signs stating'NO PARKING-FIRE LANE- <br /> TOW AWAY ZONE-EMC 46.28.130'to be installed at intervals or locations designated by <br /> the Fire Code Official. The signs shall be approximately 12 inches in width and 18 inches in <br /> height and have red letters on a white background. Metal signs shall be installed on either 2- <br /> inch metal pipes for private property or treated 4-inch by 4-inch wood posts for public <br /> property and shall be located so that the bottom of the sign is a minimum of 7 feet above the <br /> curb. Where fire lanes arc adjacent to buildings or structures and when approved or directed <br /> by the Fire Code Official,the signs may be placed on the face of the building or structure. <br /> f. Where directed by the Fire Code Official, specific areas shall be designated and those areas <br /> are to be marked with diagonal striping across the width of the fire lane. Diagonal marking <br /> shall be used in conjunction with painted curbs and/or edge striping and shall run at an angle <br /> of 30 to 60 degrees from one side to the other. These diagonal lines shall be in red traffic <br /> paint,parallel with each other,at least 6 inches in width and 24 inches apart. Lettering shall <br /> appear as above. <br /> 5. Premise Identification-Premises shall be clearly identified by the correct address at the street entry. <br /> Buildings shall be clearly identified so as to be visible and legible from the access road. Individual <br /> apartments and suites,where applicable,shall be clearly and legibly identified from the access road. <br /> See EMC 16.03, Section 505.1.1 (Address Posting Policy). <br /> Address shall be placed at road entry. <br /> 6. A fire hydrant shall be located within 10 to 75 feet of a fire department connection or standpipe per <br /> 2009 IFC, Section 903.3.7. <br /> 7. Fire Hydrants-Two hydrants are required per plan sent via e-mail. <br /> 8. Security Fence-Any security fence erected around the construction site shall be located so as to not <br /> obstruct any existing hydrant,fire protection equipment,or Fire Department access. If Fire <br /> Department access is obstructed, gates or other openings shall be provided for access. <br /> 9. Based upon 84,575 square feet of Type III_B,sprinklered construction,the fire flow requirement is <br /> 2,000 gpm. <br /> 10. Portable Fire Protection-A portable fire extinguisher with a minimum U.L.rating of <br /> 2-A:10-13:C shall be provided within 75 feet of travel on all floors of each b iilding during <br /> construction and prior to occupancy. <br /> 11. Fire Alarm System-An approved automatic fire detection system shall be provided as required by <br /> City Ordinance No. 3021-07, Chapter 16.76,of the Everett Municipal Code. <br /> Plans for such system shall be submitted to the Fire Code Official for review and approval prior to <br /> installation. Submittal shall include cut sheets of all equipment intended for use. Appropriate trip <br /> C;725) <br />