'Drew Martin <br /> From: Drew Martin <br /> Sent: Wednesday,August 7, 2019 1:54 PM <br /> To: Mark Mcllvain <br /> Cc: 'Lupe Sandoval'; 'tammirdg@aol.com'; Cindy Bergsma <br /> Subject: City of Everett Permit Services: 8417 Evergreen Way(M1908-009) <br /> Mark, <br /> This permit is for additional mechanical units and ductwork in the Panda Express space. The drawings include sheets for <br /> (2)Type II hoods. Type II (and Type I) hoods need must be submitted separately under their own permit <br /> application. The following provides direction and preliminary comments; a full review of the submittal documents will <br /> not be performed until the submittal issues are addressed as listed below. <br /> Please address the following: <br /> 1. Submit two new copies of the mechanical drawings with the hood information removed. The following list of <br /> sheets pertaining to the hoods is based on our review, but shall be verified by the applicant: M-400, M-401, M- <br /> 500. All information associated with the mechanical hoods shall be removed from other sheets. See Note <br /> 22/M-100 and Section 3/M-501. Once again,these are offered as examples and not a comprehensive list. The <br /> applicant shall verify all hood information is removed. <br /> 2. RTU-1, RTU-2, and RTU-3 are already included in Permit No. M1908-008. They shall be removed from the <br /> mechanical drawings. They should be depicted on Sheet M-100 but identified for reference only. The RTU- <br /> schedule on Sheet M-000 should be removed. <br /> 3. The applicant shall verify that the unit weights specified in the mechanical drawings do not exceed the design <br /> values specified in the previously approved building (i.e.,structural) drawings under Permit No. B1805-010). <br /> 4. Provide a revised valuation for the mechanical permit. It is presumed that the current valuation includes the <br /> hoods,which should be removed. <br /> 5. Submit a separate application for the hoods, including separate drawing sets. <br /> 6. Verify that the hoods are Type I. Based on this being a restaurant preparing food, it seems that the hoods <br /> should be Type I unless they meet the Type II definition per IMC Section 202 "Hoods:Type II" and Section <br /> 507.3. Note that Note 22/M-100 identifies grease duct cleanouts and Sections 18/M-500 identifies the <br /> equipment under the hoods as"cooking equipment". <br /> 7. The hood drawings shall show all connection requirements between the hoods and the supporting <br /> structure. The hoods shall be provided with lateral bracing in addition to gravity support. <br /> 8. Detail 5/M-500 indicates the fire wrap to extend 18" above combustible material, but does not show this <br /> consistently, nor is it consistent in Details 18/M-500 and 3/M-501. Other details should similarly be <br /> reviewed. All details shall consistently show the requirement. <br /> 9. Detail 5/M-500 states to provide a hinge and flexible electrical cable. The detail shall also require a restraint per <br /> IMC 506.5.3. <br /> 10. Verify the hoods have the required clearance to combustible construction. Detail 18/M-500 appears to indicate <br /> metal stud framing, but the construction drawings consist of wood stud framing. <br /> _ Drew Martin,P.E.,S.E. <br /> Associate Engineer—Commercial Plans Examiner I Permit Services <br /> LNBi <br /> 425.257.8813 I 3200 Cedar Street, 2nd Floor, Everett,WA 98201 <br /> EVERETT Hours: Monday—Friday 7:30am-12:OOpm and 1:OOpm-4:OOpm <br /> everettwa.gov I Facebook I Twitter <br /> 1 3 <br />