My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
3323 HOYT AVE C D 2020-06-17
>
Address Records
>
HOYT AVE
>
3323
>
3323 HOYT AVE C D 2020-06-17
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
6/17/2020 1:18:37 PM
Creation date
6/17/2020 1:17:48 PM
Metadata
Fields
Template:
Address Document
Street Name
HOYT AVE
Street Number
3323
Unit
C D
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
56
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
U � <br /> Mr. Brad Rzechula <br /> Leading Edge Construction, LLC <br /> Plan Check Number: B1803-029, First Review <br /> May 4, 2018 <br /> 4. The project includes steel construction. The General Notes on Sheet S-1.0 shall be revised by <br /> adding a section specifying the requirements for steel construction. The requirements should <br /> include but are not limited to: steel grades including plates, anchors, and connection hardware, <br /> welding materials, protective coatings, and special inspection requirements for steel fabrication <br /> shops. See IBC Sections 1704.2.5 and 2205.1, AISC 360-10 Sections A.4 and B3.13, and AISC <br /> 303-10 Section 3.1. <br /> 5. Note 1 of the"Wood Framing"section on Sheet S-1.0 states that exposed wood framing shall <br /> be"treated". This note should be revised to state that the framing will be"preservative- <br /> treated". See IBC Section 2304.12. <br /> 6. Note 10C on Sheet S-5.0 states that the walls on Grid 3 are full-height. However, the <br /> architectural and structural drawings appear to indicate that the walls are discontinuous at the <br /> main floor (i.e., walls do not occur at the first story). The design should be reviewed and the <br /> note revised as needed. See IBC Section 107.2.1. <br /> 7. The main floor framing plan on Sheet S-4.0 indicates Mark"2"holdowns. The Holdown <br /> Schedule only includes Mark"1"holdowns. The design should be reviewed and revised as <br /> needed. See IBC Section 107.2.1. <br /> 8. Grid F appears to include multiple wood posts. The sizes of the posts do not appear to be <br /> specified. The drawings should be reviewed and revised as needed. See IBC Section 1603.1. <br /> 9. The Main Level framing plan on Sheet S-4.0 specifies both 14-inch joists (Plan Note 3) and 2x8 <br /> joists (Plan Note 7) between Grids A-A.5. The extent of each type of framing in this area <br /> should be specified on the plan. See IBC Section 1603.1. <br /> 10.The second story includes shear walls on Grid A that appear to require structural sheathing at <br /> the Main Floor level to transfer loads to Grid A.S. The requirement for sheathing should be <br /> verified and Sheet S-4.0 revised to show the extent of the sheathing between Grids A-A.5. <br /> Verify the sheathing should be installed per Note 2. See IBC Sections 1603.1 and 1604.4. <br /> 11. Detail 5/S-4.1 specifies a "positive connection nailer"to the steel beam. The detail should be <br /> revised to show the required construction of the connection. See IBC Section 107.2.1 <br /> Foundation System: <br /> 12. Detail 1/S-3.0 appears to show the typical footing for the HSS posts on Grid A per Sheet S-3.0. <br /> The following comments should be addressed: <br /> a. The section shall specify a minimum depth from the surface to the bottom of the footing of <br /> 18 inches. See IBC Section 1809.5 Item 1 and Everett Municipal Code Section <br /> 16.01.010(3). <br /> b. The columns bear on a pedestal above the footing that includes one #3 hoop. Three #3 <br /> hoops shall be provided within 5 inches of the top of the pedestal per ACI 318-14 Section <br /> 10.7.6.1.6. See IBC Section 1901.2. <br /> Pa e4of8 <br /> CITY OF EVERETT• 3200 Cedar Street • Everett,WA 98201 • (425) 257-8810 • Fax(425) 257-8857 <br />
The URL can be used to link to this page
Your browser does not support the video tag.