<br /> VENTILATION SCHEDULE ENERGY RECOVERY VENTILATOR SCHEDULE Tb
<br /> AREA SQ NO. CFM/ CFM/SQ ° EXHAUST CFM EXHAUST CFM AIR CHANGES E.S.P. EXHAUST E.S.P. TEMPERATURE ENTHALPY ELECTRICAL
<br /> SYSTEM ROOM NAME FT PEOPLE PERSON REMARKS
<br /> OSA @ 80% EFF OSA PROVIDED REQUIRED PROVIDED PER HOUR EQUIP- MANUFACTURER/ LOCATION CONFIGURATION EXHAUST INCHES FAN SUPPLY INCHES SUPPLY RECOVERY RECOVERY WEIGHT REMARKS DY K E M A N
<br /> 0110011,•
<br /> QUIET ROOM 215 8 5 0.12 76 80 - - - 1 TAG MODEL CFM W.G. BHP CFM W.G. BHP EFF. EFF. VOLTS PH. MCA LBS '
<br /> BRANCH MANAGER 132 3 5 0.06 27 30 - - - 1 - ERV-4 RENEWAIRE / HE3XINV CENTRAL MECHANICAL ROOM HORIZONTAL 1715 0.75 0.60 1715 0.75 0.60 69% 56% 208-230_ 1 24.3 903 1, 2, 3, 4, 5 ARGHITEGTURE 0 DESIG
<br /> ERV-1 SHARED OFFICE 225 3 5 0.06 32 35 - - - 1
<br /> BREAK ROOM 234 8 5 0.06 64 225 - 250 6 1
<br /> www.dykeman.net 1716 Wes Marine View Drive
<br /> CORRIDOR 400 - - 0.06 30 30 - - - 1 NOTES:
<br /> 425.259. 2nd Floor---7198201eMarine ie
<br /> SECURE STORAGE 84 - - - - - - - 5 1. PROVIDE MOTORIZED ISOLATION DAMPERS ON OA AND EA STREAMS
<br /> LAPTOP BAR 270 7 5 0.12 76 80 - - - 1 2. UNIT TO BE CONTROLLED BY TIMER OR OCCUPANCY SENSOR
<br /> E
<br /> E ADULT STACKS 1300 13 5 0.12 237 250 - - 1
<br /> 3. PROVIDE BYPASS ECONOMIZER WITH ENTHALPY CONTROLS
<br /> ERV-2 LIVING ROOM 540 10 5 0.12 127 130 - - 1
<br /> CONSULTA
<br /> 4. PROVIDE WITH 2" MERV 8 FILTERS NT:
<br /> GROUP STUDY A 126 4 5 0.12 40 50 - - - 1 5. FOR ELECTRIC HEAT SEE ELECTRIC DUCT HEATER SCHEDULE.
<br /> GROUP STUDY B 126 4 5 0.12 40 50 - - - 1
<br /> EVERGREEN ROOM A 647 16 5 0.06 139 140 - - 1
<br /> ERV-3 ROOM B 647 16 5 0.06 139 140 - - - 1
<br /> PERMIT SET
<br /> EVERGREEN
<br /> FAMILY RR(ADA) 76 - - - - - 50 50 - 3
<br /> STAFF RR 50 - - - - - 50 50 - 3 www.ha rrisgroup.com
<br /> Our difference
<br /> : s
<br /> is engineered.
<br /> ELEC-29 44 - - - - - - 50 - 5
<br /> ELEC-31 44 - - - - - - 50 - 5
<br /> JANITOR 85 - - 1.0 - - 85 85 - 4
<br /> PUBLIC COMPUTING & COPIER 700 26 5 0.12 247 250 - - - 1
<br /> LOUVER SCHEDULEr� I,I..I PROJECT NO: 0070298.00
<br /> TEEN STACKS /REFERENCE 665 7 5 0.12 124 125 - - 1 AIR FREE AREA DIMENSION NET FREE AREA PRESS. NOTES
<br /> - ADULT SEATING 800 16 5 0.12 196 200 - - - 1 EQUIP. MFG'/ MODEL NUMBER TYPE SERVICE TYPE FLOW VELOCITY W X H REQUIRED DROP -
<br /> ERV-4 TEEN LOUNGE 400 4 5 0.12 73 75 - - - 1 TAG
<br /> CFM FT/ MIN. IN. X IN. SQ. FT. IN. W.G.
<br /> CHILDREN'S STACKS 1280 13 5 0.12 235 250 - - - 1 L-1 RUSKIN/ELF15J STATIONARY QUIET RM, BRANCH MANAGER, BREAK RM, CORRIDOR, STORAGE INTAKE 470 600 24X18 0.78 0.07 REGISTRATION ATS MP:
<br /> SEATING AREA 515 8 5 0.12 112 125 - - - 1 L-2 RUSKIN/ELF15J STATIONARY QUIET RM, BRANCH MANAGER, BREAK RM, CORRIDOR, STORAGE EXHAUST 470 1000 24X18 0.47 0.15 - -
<br /> STUDY LEARNING 200 6 _ 5 0.12 62 75 - - - 1 L-3 RUSKIN/ELF15J STATIONARY LAPTOP BAR, ADULT STACKS, LIVING ROOM, GROUP STUDY INTAKE 600 600 24X18 1.00 0.05
<br /> CIRCULATION /SORTING AREA 1200 8 5 0.12 194 200 - - - 1 L-4 RUSKIN/ELF15J STATIONARY LAPTOP BAR ADULT STACKS, LIVING ROOM, GROUP STUDY EXHAUST 600 1000 24X18 0.60 0.15
<br /> CIRCULATION MANAGER 114 2 5 0.06 19 25 - - 1 ,`,
<br /> L-5 RUSKIN/ELF15J STATIONARY EVERGREEN ROOM A, EVERGREEN ROOM 6 INTAKE 300 600 18X12 0.50 0.05 l
<br /> ;,°1 WASIN
<br /> STORAGE 33 - - - - - - - - 5 L-6 RUSKIN/ELF15J STATIONARY EVERGREEN ROOM A, EVERGREEN ROOM B EXHAUST 300 1000 18X12 0.30 0.15 ,�'' -Xi'
<br /> a
<br /> WORKROOM 230 4 5 0.06 39 50 - - - 1 !�
<br /> i i.0
<br /> SF-1 PEGASUS ENCLOSURE 336 - - - - - - - - 2
<br /> 1926 _at
<br /> MAINTENANCE STORAGE 230 - - - - - - - - 24�
<br /> VOICE AND DATA SERVICES 300 - - - - - - - - 2 ';;.i*(4,1.
<br /> SW-
<br /> NOTES: /� �+ [PROJECT IDENTIFICATION: D
<br /> D 1- MIN- OSA CFM REQUIRED= (# PEOPLE XCFM/PERSON)+ (AREA XCFM/SQ.FT.) AIR TERMINAL DEVICE SCHEDULE
<br /> 2. VENTILATION PROVIDED BY NATURAL VENTILATION WITH A MINIMUM OF 4% FLOOR AREA ON OPERABLE OPENINGS ITEM MARK MANUFACTURER MODEL MATERIAL MOUNTING FINISH REMARKS
<br /> PEGASUS ENCLOSURE: 336 SQ. FT. X 4% = 14 SQ. FT OPERABLE OPENING REQUIRED, 76 SQ. FT PROVIDED
<br /> Evergreen Branch
<br /> MAINTENANCE STORAGE: 230 SQ- FT- X 4% = 10 SQ. FT OPERABLE OPENING REQUIRED, 21 SQ. FT PROVIDED CEILING DIFFUSER CDS TITUS MCD STEEL SURFACE ENAMLED BORDER TYPE 1
<br /> VOICE AND DATA SERVICES: 300 SQ. FT. X4% = 12 SQ. FT OPERABLE OPENING REQUIRED, 21 SQ. FT PROVIDED CEILING GRILLE CGS TAUS 50F ALUMINUM SURFACE ENAMLED BORDER TYPE 1
<br /> 3.THE EXHAUST SYSTEM OPERATES CONTINUOUSLY WHILE OCCUPIED; THE LOWER EXHAUST RATE OF 50 CFM IS PERMITTED CEILING DIFFUSER CDL TITUS MCD STEEL LAY-IN ENAMLED BORDER TYPE 3 Library Expansion
<br /> CEILING GRILLE CGL TITUS 50F ALUMINUM LAY-IN ENAMLED BORDER TYPE 3
<br /> 4- MIN- EXHAUST CFM REQUIRED= (AREA X CFM/SQ.FT-)
<br /> 5. UNOCCUPIED SPACE PLENUM SLOT DIFFUSER PSD TITUS TBD-10 STEEL SLOT ENAMLED FOR
<br /> NOTE: NECK CONNECTION SIZE AND TERMINAL SIZE AS NOTED ON MECHANICAL FLOOR PLAN City of Everett
<br /> PLUMBING FIXTURE SCHEDULE
<br /> - LOCAL CONNECTIONS
<br /> TAG DESCRIPTION AT
<br /> W V HW CW
<br /> LAVATORY (ADA)-ZURN Z5111.602.1.06.10.5, 20"X 17"COUNTERTOP LAVATORY; VITREOUS CHINA W/SINGLE FAUCET ELECTRIC DUCT HEATER SCHEDULE 9512 Evergreen Way
<br /> HOLE; BATTERY POWERED, CHROME PLATED, SENSOR FAUCET W/5"SPOUT AND THERMOSTATIC MIXING VALVE; PRESSURE ELECTRICAL Everett WA 98204
<br /> L1 CHROME PLATED GRID DRAIN; 1-1/4"X 1-1/2"CHROME PLATED, CAST BRASS P-TRAP LESS CLEANOUT; STANDARD STOP 1-1/2" 1-1/2" 1/2" 1/2" TAG LOCATION MFG/ MODEL CFM KW SIZE DROP (IN. W.C.) V PH REMARKS
<br /> LAVATORY SUPPLY KIT(CONNECTIONS 1/2"IPS X 3/8"OD); ADA COMBINATION TRAP AND SUPPLY WRAP PROTECTOR
<br /> KIT. DH-1 ERV-1 OSA SUPPLY DUCT INDEECO/QUZ 470 4 10"X10" 0.05 208 1 1, 2
<br /> DH-2 ERV-2 OSA SUPPLY DUCT INDEECO/QUZ 600 5 12"X12" 0.05 208 1 1, 2
<br /> LAVATORY(ADA)-COSENTINO BATHROOM COLLECTION, SILESTONE MATERIAL. REFLECTIONS MODEL, CENTER
<br /> DRAIN, 72"X 24",WALL MOUNT MODEL, PROVIDE WITH STAINLESS STEEL BRACKETS, COORDINATE COLOR WITH DH-3 ERV-3 OSA SUPPLY DUCT INDEECO/QUZ 300 3 10"X10" 0.05 208 1 1, 2
<br /> L2 ARCHITECT,ZURN AQUASENSE Z6913-XL FAUCET, PROVIDE 2 FAUCETS AT LAVATORY FIXTURE,THERMOSTATIC 2" 1-1/2" 1/2" 1/2" DH-4 ERV-4 OSA SUPPLY DUCT INDEECO/QUZ 1715 14 2011X14" 0.05 208 1 1, 2 BID SET
<br /> MIXING VALVE, STANDARD STOP LAVATORY SUPPLY KIT(CONNECTIONS 1/2"IPS X 3/8"OD), ADA COMBINATION TRAP
<br /> AND SUPPLY WRAP PROTECTOR KIT.
<br /> LAVATORY(ADA) -COSENTINO BATHROOM COLLECTION, SILESTONE MATERIAL, REFLECTIONS MODEL, CENTER NOTES:
<br /> DRAIN, 60"X 24",WALL MOUNT MODEL, PROVIDE WITH STAINLESS STEEL BRACKETS, COORDINATE COLOR WITH This drawing is:
<br /> C L3 ARCHITECT,ZURN AQUASENSE Z6913-XL FAUCET, PROVIDE 2 FAUCETS AT LAVATORY FIXTURE,THERMOSTATIC 2" 1-1/2" 1/2" 1/2" 1. INDEECO CONTROL OPTION 'K'WITH SCR POWER CONTROLLER. 1. Copyright 2017 Instrument
<br /> n, Inc. C
<br /> MIXING VALVE, STANDARD STOP LAVATORY SUPPLY KIT(CONNECTIONS 1/2"IPS X 3/8"OD), ADA COMBINATION TRAP 2. PROVIDE WITH BUILT-IN DISCONNECT SWITCHES- 2. The Architects Instrumof Professional Service.
<br /> 3. For use on this project only. Obtain Architect's
<br /> AND SUPPLY WRAP PROTECTOR KIT. written permission for any other use or reproduction.
<br /> SINK(SINGLE COMPARTMENT) -JUST MODEL SL-ADA-1815-A-GR W/FRONT OVERFLOW, 18"X15"MAX. 6-1/2"DEEP,
<br /> S1 CENTER DRAIN, CHICAGO 201 AGN8AE3 317XKCPGOOSENECKSPOUTWITH LAMINAR FLOW SPOUT END,WRISTBLADE 2" 1-1/2" 1/2 1/2" PRO JECTiNUMBER:
<br /> LEVER HANDLES, CERAMIC DISC CARTRIDGES, GRID DRAIN, SCREWDRIVER STOPS&SUPPLIES, 17 GA CHROME
<br /> PLATED P-TRAP, PLUMBEREX HANDY-SHIELD MAXX SERIES P-TRAP AND H&C SUPPLY COVERS OR EQUAL. 2O 17-OOH
<br /> WATER CLOSET-ZURN Z5615.031.01.H4.00 1.6 GPF WALL HUNG TOPSPUD FLUSHVALVE TOILET;VITREOUS CHINA; ELECTRIC HEATER SCHEDULE
<br /> WC1 BATTERY POWERED, CHROME PLATED, SENSOR FLUSH VALVE; ELONGATED, STANDARD WHITE, OPEN FRONT TOILET 4" 2" 1" REVISIONS: I
<br /> SEAT, LESS COVER, WITH STAINLESS STEEL CHECK HINGE; PROVIDE WALL CARRIER. MOUNT WATER CLOSET PER EQUIP. CONTROL ELECTRICAL
<br /> WASHINGTON STATE ADA REQUIREMENTS. TAG LOCATION MFG/MODEL# WATTS ORIENTATION OPTION V/PH REMARKS
<br /> MARK DATE DESCRIPTION
<br /> EH-1 RISER ROOM KING/PAW1215 500 WALL MOUNT INTEGRAL 120V/1 1 08-17-17 DD COST EST.
<br /> 08-17-17 DD SUBMITTAL
<br /> 08-14-18 PERMIT SUBMITTAL _
<br /> NOTES: 09-10-18 BID SET
<br /> 1- COORDINATE LOCATION OF UNIT WITH ARCHITECTURAL FEATURES AND ALL OTHER TRADES
<br /> DUCTLESS SPLIT SYSTEM HEAT PUMP SCHEDULE
<br /> OUTDOOR CONDENSING UNIT INDOOR AIR HANDLER _
<br /> B EQUIP. AREA SERVED MFG'/ MODEL NUMBER NOMINAL COOL CAP. MBH HEAT CAP. WEIGHT NOISE ELEC. REQ. EQUIP. MFG'/MODEL NUMBER AIRFLOW ELEC. REQ. WEIGHT REMARKS B
<br /> TAG TON TOTAL SENS- TOTAL MBH HSPF LBS DBA SEER MCA VOLTS PH- TAG CFM MCA VOLTS PH. LBS PROJECTiTEAM:
<br /> CU-2 VOICE & DATA SERVICES MITSUBISHI/PUZ-A36NKA7 3.0 36.0 27.72 38.00 9.20 214 53 18.8 25.0 208/230 1 AHU-1 MITSUBISHI/ PKA-A36KA7 920 1.0 208/230 1 46 1,2,3,4,5,6
<br /> PRINCIPAL IN CHARGE: I RH
<br /> PROJECT MANAGER: I RH
<br /> NOTES: PROJECT ENGINEER: 1 KLY
<br /> 1. PROVIDE WIRELESS REMOTE CONTROLLER DRAWN BY: I XXX
<br /> 2. INSTALL UNIT 72" AFF
<br /> KEYPLAN:
<br /> 3. INDOOR UNIT POWER WIRING FROM OUTDOOR UNIT. `
<br /> 4. NO ECONOMIZER PROVIDED PER WSEC SECTION C403.3 EXCEPTION 10.
<br /> 5. PROVIDE AND INSTALL OPTIONAL WIND BAFFLE ACCESSORY.
<br /> 6. ROUTE CONDENSATE TO FLOOR DRAIN IN ADJACENT RISER ROOM
<br /> DRAWING�TITLE:
<br /> A
<br /> A
<br /> SCHEDULES