a. The electrical plans state that there will be a generator— please clarify. <br /> 6. It should be verified that the elevator will be provided with standby power (see <br /> comment above) and comply with the emergency operation and signaling device <br /> requirements of Section 2.27 of SAME A17.1. Section 1009.4 <br /> 7. The location of each smoke alarm and carbon monoxide detector should be shown on <br /> the plans. Sections 907.2.11 and 915.1.1 <br /> Construction <br /> 1. Two-hour shaft wall detail W5/A7.1 references GA File No. WP 7051 - that listing <br /> requires proprietary 1/2"GWB (type C). If that wall adjoins a dwelling unit, the insulation <br /> specified in the listing should be provided. Sections 703.2 & 1207 <br /> 2. A symmetrical, one-hour, fire-resistive listing should be shown for the V-A exterior walls <br /> that are 10'feet or less from the southern property line. Section 705.5 <br /> 3. Stair Section 20/A7.9 shows two-hour shaft partitions resting on one-hour floor/ceiling <br /> assemblies (walls are not continuous). Detail 13/A7.1 depicts the typical construction <br /> requirement of a continuous shaft: for clarity — please reference this detail on the wall <br /> section. Section 707.5 <br /> 4. The South Stair has enclosures that extend past the stairway opening (to the East). <br /> These extensions have two-hour walls resting on one-hour floor/ceiling assemblies. The <br /> framing supporting the two-hour walls should be shown as two-hours as well (to the <br /> foundation). Otherwise, the fire barriers should be continuous to the foundation. Section <br /> 707.5.1 <br /> 5. A listing should be provided for wall types W12 &W13. Section 703.2 <br /> Egress <br /> 1. The egress plans show that the barrier as required by Section 1023.8 is in place; <br /> however it is located at the first riser of the stairway going up, which is an awkward <br /> arrangement. Due to the landing restrictions of the egress level, it may be less <br /> hazardous and more prudent to place the barrier in the middle of the mid-level landing <br /> 1/2-story below the egress level. <br /> 2. A wall tag should be provided at the western partition of the exit passageway leading <br /> from the South Stair of the 1st floor. <br /> 3. The 406-706 series of 90-minute stair enclosure doors should be shown on the door <br /> schedule. Section 716.5 <br /> 4. An additional roof access ladder should be provided from the platform in the South Stair <br /> to just under the roof. Section 1011.12 <br /> 5. If the electrical service is greater than 1200 amps, Section 1006.2.2.6 may apply (two <br /> exists from electrical room). <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425)257-8813 Page 2/V <br />