Laserfiche WebLink
1 <br /> Ltr. B0206-022 <br /> July 17, 2002 <br /> Page 4 <br /> iii) The lateral distance from the center line of the water closet to the farthest side wall <br /> must be a minimum of 42 inches. Section 1106.11.5.1 <br /> iv) The height of the water closets should be shown from 17 — 19 inches A.F.F. <br /> Section 1106.11.5.2 <br /> v) The lavatories should be provided with a clear floor space of 30 wide by 48 inches <br /> deep to allow for a forward approach. The folding door and frame are currently <br /> shown in this area. Section 1106.11.7.1 <br /> vi) The height of the lavatories should be detailed in accordance with Section <br /> 1106.11.7.2 <br /> 5) If the rooms in the C Wing are not used for patient care which specializes in treating <br /> conditions that affect mobility, than a minimum of two rooms must be accessible and <br /> comply with the items noted above. A letter from the ownership must be provided for this <br /> exception to be employed. Section 1103.1.6 <br /> 6) The toilets in Patient toilet rooms B353 & B352 should be shown with a clear floor space <br /> that complies with Section 1106.11.5.1 <br /> Please prepare a response letter showing where each item in this correction letter is addressed <br /> on the plan set. <br /> Upon resubmission of the drawings, your application will be given priority and plan review l <br /> will recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to <br /> ensure that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Tony R. Lee <br /> Plans Examiner <br />