w <br /> • ' , C; <br /> Ltr. B0206-022.rc1 <br /> August 19,2002 <br /> Page 2 <br /> 4. Accessible patient rooms C330&C332: <br /> a. The fold-down side grab bar must meet the criteria in Section 1106.11.5.3 (42" bar <br /> that projects a minimum of 54" from wall). A cut-sheet should be provided. <br /> b. The 18" lateral distance from the wall to the centerline of the toilet should be <br /> dimensioned on the plans. Section 1106.11.5.1 <br /> 5. The letter from Providence Hospital regarding the mobility of patients served will be <br /> reviewed upon receipt. <br /> 6. The toilets rooms B353 & B352 should be in a minimum 60" wide stall. Currently, the <br /> shower wall is within the minimum clear floor space. Section 1106.11.5.1 <br /> Please prepare a response letter showing where each item in this correction letter is addressed <br /> on the plan set. <br /> Upon resubmission of the drawings, your application will be given priority and plan review <br /> will recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to <br /> ensure that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Tony R. Lee <br /> Plans Examiner <br /> v, <br /> ,t <br /> t <br /> �/ t <br /> la 1 <br />